ZU25102A_e.DOC / Mrz-08
Page 18 / 26
Parameter
Description
Reset Value:
With every reset command, the counter presets to the datum set here
(e.g. 000 000) and the analogue output follows the new counter state
according to its output scaling.
Round Loop:
This register limits the counting range to a repeating loop. With setting of
1000, in upwards direction 999 is followed by to 000, and in downwards
direction the counter sets to 1000 when reaching zero.
Setting this register to 000 000 provides counting over the full range.
Power up Mode:
Sets the action of the counter upon power up:
0 = Loads the previous value from power down memory
1 = sets counter to zero
Set-Up-Settings:
Analogue Offset:
Allows adjusting the analogue zero output in a range of approx. +/- 100mV
(respec/- 200
μ
A) if necessary.
Analogue Gain:
Sets the maximum output swing of the analogue output. Setting of 1000
results in a 10 volts respectively 20 milliamps output swing.
Direction:
Can be used to invert the polarity of the analogue output signal when
converting quadrature A/B input signals or A=impulse and B=direction.
0 =
no inversion of the polarity
1 = inversion of the polarity