Ca306_01d_oi_e.doc / Apr-16
Page 6 / 10
4.
Connections
The screw terminals and DIL switches for setup are located on the backplane of the unit:
1 2 3 4
1 2 3 4 5 6 7 8
GND G
C-
C+
CAN high
CAN low
GND (100R)
GND
10...35V
Power Supply
Current consumption depending on the supply voltage:
60
50
40
30
20
10
10
20
30
40
mA
Volt
The following cables are recommended for CAN communication, depending on the cable length:
Up to 300 meters:
Cable type
LIYCY 2 x 2 x 0,5 mm² (twisted and screened)
Resistance
40
/km
Capacity
130 nF/km
More than 300 meters:
Cable type
CYPIMF 2 x 2 x 0,5 mm² (twisted and screened)
Resistance
40
/km
Capacity
60 nF/km
Please use the leads like shown:
Pair 1 (white/brown)
CAN-Low and CAN-High
Pair 2 (green/yellow)
GND