Parameter LV-Calculation:
VE
VA
Setting 1-4 need analogue input proportional to master speed.
Setting 5-8 generate VE by internal f/V converter
Speed Ref
(Master)
Ref out
(Slave)
Clarification: When LV - Calc is set to 1, the output voltage will be equal to the input
voltage with Fact 1 = 1.0000 and Gain Tot = 1000.
Unit - Nr.
Allows entry of a serial device address between 11 and 99. It is not allowed
to use addresses containing a "0" (i.e. 20, 30, 40 etc.) as these are reserved
for collective addressing of several units.
Factory setting: 11.
Baud Rate
The following transmission rates can be selected:
Setting
Baud
0 9600
1 4800
2 2400
3 1200
4
600
Factory setting: = 0