Sizing Guide
(Continued)
In-Delta Connection
Size 1 and 2
I
e
1)
kW
FLA
1)
Hp
Trip Class
10
Trip Class 20 Trip Class 30
A
230
V
400
V
500
V
A
200
V
208
V
220-
240V
440-
480V
550-
600V
I
e
: AC-53a:
3.5-17: 90-
5
VMX-
I
e
: AC-53a:
4-19: 90-5
VMX-
I
e
: AC-53a:
4-29: 90-5
VMX-
29
7.5
15 18.5 29
7.5 7.5
10
20
25
SGY-I-17
SGY-I-22
SGY-I-29
38
11 18.5 22
36
10
10
10
25
30
SGY-I-22
SGY-I-29
SGY-I-35
50
11
22
30
47
10
15
15
30
40
SGY-I-29
SGY-I-35
SGY-I-41
61 18.5 30
37
59
15
15
20
40
50
SGY-I-35
SGY-I-41
SGY-I-55
71 18.5 37
45
69
20
20
25
50
60
SGY-I-41
SGY-I-55
SGY-I-66
95
22
45
55
90
25
30
30
60
75
SGY-I-55
SGY-I-66
SGY-I-80
114 30
55
75 113 30
30
40
75
100
SGY-I-66
SGY-I-80
SGY-I-100
139 37
75
90 133 40
40
50
100
125
SGY-I-80
SGY-I-100
SGY-I-132
173 55
90 110 166 50
50
60
125
150
SGY-I-100
SGY-I-132
SGY-I-160
229 55 110 160 215 60
75
75
150
200
SGY-I-132
SGY-I-160
SGY-I-195
277 75 150 185 270 75
75
100
200
250
SGY-I-160
SGY-I-195
See Size 3
338 90 185 220 312 100 100
125
250
300
SGY-I-195
See Size 3
See Size 3
Size 3
I
e
1)
kW
FLA
1)
Hp
Trip Class
10
Trip Class
20
Trip Class
30
A 230V 400V 500V A 200V 208V
220-
240V
440-
480V
550-
600V
I
e
: AC-53a:
3.5-17: 90-3
VMX-
I
e
: AC-53a:
4-19: 90-3
VMX-
I
e
: AC-53a:
4-29: 90-3
VMX-
277 75
150 185 270
75
75
100
200
250
See Size 2 See Size 2
SGY-I-242
338 90
185 220 312 100 100
125
250
300
See Size 2
SGY-I-242 SGY-I-302
419 132 220 300 419 150 150
150
350
450
SGY-I-242 SGY-I-302 SGY-I-361
523 160 300 375 523 150 150
200
450
500
SGY-I-302 SGY-I-361 SGY-I-430
625 200 355 425 625 200 200
250
500
600
SGY-I-361 SGY-I-430 SGY-I-500
745 220 425 530 717 250 250
250
500
700
SGY-I-430 SGY-I-500
-
866 280 500 630 831 250 300
300
600
800
SGY-I-500
-
-
1)
Maximum motor line current indicated.
For In-Delta connections, all six motor wires must be available for
connection, and it is critical to exactly follow the In-Delta wiring diagram in the Synergy Plus Quick Start Guide.
The Soft Starter will only sense the Phase Current, which is about 57.7% of the motor line current.
Please refer to the full user manual MAN-VMX-SGY-I-UM for further details