Part Number: 000016427 Rev 00 08/2020 33
Requirements - Cleaning - Operation
ENERGIZED PARTS CHART PKU0155
ICE MAKING
SEQUENCE OF
OPERATION
Control Board Relays
Relay
Length of
Time
1
Water
Pump
2
Harvest
Valve
3
Relay
Coil
3A
Compressor
3B
Compressor
Fan Motor*
Initial Start-up
1. Water Purge
Off
On
Off
Off
Off
15 Second
2. Refrigeration
Start-Up
Off
On
On
On
On
5 Seconds
Freeze
Sequence
3. Prechill
Off
Off
On
On
On
30 Seconds
4. Freeze
On
Off
On
On
On
Until 7 Second
Water
Contact W/
Ice Thickness
Probe
Harvest
Sequence
5. Harvest
Off
On
On
On
On
Bin Switch
Activation
Automatic
Shut-off
6. Automatic
Shut-off
On
Off
On
On
On
Until Bin
Switch
Re-closes
* Condenser Fan Motor: The fan motor is wired through a fan cycle pressure control; therefore, it may
cycle on and off