C. Adjusting the alarm limits
1. Press either the
-
or the
¯
button on the front panel.
The corresponding alarm limit is shown on display.
2. Now adjust the requested alarm limit with the corresponding screw located on the
right hand side of the front panel.
D. Display and signal output adjustment
Four adjustment screws are on the back panel.
Do not
change these settings as they
have been exactly adjusted at the factory or by the panel builder.
If, however, the instrument needs to be adjusted, proceed as follows:
1) set the input signal to the lowest possible value
2) adjust the display with the "DVM MIN". screw and the signal output with the "mA
MIN" screw.
3) set the input signal to maximum value, adjust the display with the "DVM MAX"
screw and the signal output with the "mA MAX" screw.