Below is the AC cable specification table when select the cable for installation.
Table 7
Cable and Micro-breaker Requirement
Model
ST5KTi
ST6KTi
ST8KTi
ST10KTi
ST12KTi
ST13KTi
ST15KTi
Cable (Cu)
4mm
2
4mm
2
4mm
2
4mm
2
4mm
2
6mm
2
6mm
2
Micro-Breaker
16A
20A
25A
30A
32A
32A
36A