![Moso ST10KTi Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/moso/st10kti/st10kti_user-manual_1837171020.webp)
The Solar
Town
Series Inverter
19
6.6 Check Inverter Installation Status
Check the upper straps of Inverter to ensure it is fixed on to the bracket.
Check the secure mounting of the PV-Inverter by trying to raise it from the bottom.
The PV-Inverter should remain firmly attached.
Select the installation location so that the status of display can be easily viewed.
Choose a strong mounting wall to prevent vibrations while inverter is operating.
6.7 Connector Guide
This product has a professional IP68 DC waterproof connector. You have to wire DC by yourself.
Please see
Figure 17
and
Figure 18
for DC connector disassembling guide.
Connectors must only be connected by qualified personnel
Only PV1-F cables can be used. The TÜV approval only allows
the use of PV1-F cables. Do not
use type H07RN-F cables.
The connectors must be not disconnected while under load. For protection against electric shock,
connectors must always be disconnected from the power supply during assembly.
Connectors that are not plugged must be protected against humidity and contamination by a
protective cap. Any kind of contamination may have adverse effect on the system and great care
must be taken during assembly to ensure that everything is clean.
Connectors provide IP68 protection but should
not be continually exposed to water (e.g. immersed
under water) and not placed directly on the top side.
Connecting to PV panel (DC input):
Figure 17
1.
Wire stripping 7mm
2.
Insert the wire into the core with pliers pressure;
3.
The core penetration into the terminal internal until clamping, then tighten the nut