7.0 REMOTE START
The EP6 features REMOTE START only in AUTO
operating mode.
To operate the REMOTE START, follow the
instructions.
A) - Turn the KEY-SWITCH to the ON position; the
Display and LEDs illuminate for 1 sec.
B) - Wait until the end of the LEDs test.
C) - Push the AUTO pushbutton as soon as possible
(otherwise, after 20 seconds the EP6 enters
the STARTING FAILURE); the [AUTO] yellow
LED will illuminate as described in the next
section
7.1 - REMOTE START SWITCH:
If the REMOTE START input is activated, the
[AUTO] yellow LED illuminates continuously and
the display will indicate the count down of the internal
start delay
timer by means of the message [MM.SS]
(Minutes and seconds). The engine will start after
the programmed
start delay
time. If the REMOTE
START is deactivated, the EP6 drives the
stop
delay time
. The display will indicate the count down
by means of the message [MM.SS] (Minutes and
seconds), and the [AUTO] yellow LED will flash.
The engine will stop after the programmed
stop
delay
time.
Note
start delay time: see section 6.0 parameter
[P.0]
Note
stop delay time: see section 6.0 parameter
[P.1]
8.0 SAFETY
Test, we recommend the following procedures.
- disconnect the power supply of the EP6
(consult
your genset supplier)
- wait for the desired start time (external clock
reference)
- apply the power supply to the EP6
(consult your
genset supplier)
- select the ‚AUTO‘ operating mode
The EP6 will start the engine after the programmed
number of days and the engine will run for the
programmed time. To determine how the Automatic
Periodic Test is programmed enter the Reading
Mode (section 6.0 parameter [P.26] and [P.27]).
IMPORTANT NOTES
If the supply (battery voltage) is removed, the
EP6 loses the counts and timings. If the supply
restores, the EP6 starts to count the A.P.T.
according to the programmed parameters [P.26]
and [P.27]. It is important to synchronize the
power on sequence with the desired Automatic
Periodic Test.
10.0 FRONT PANEL
High voltage is present inside the EP6. To avoid
electric-shock hazard, operating personnel must
not remove the protective cover. Do not
disconnect the grounding connection. Any
interruption of the grounding connection can cre-
ate an electric shock hazard. Before making
external connections, always ground the PANEL
first by connecting the control panel to ground.
NOTE
!
9.0 Automatic periodic TEST
The EP6 does not use a clock to count the
programmed days ([P.26] setting, section 6.0). The
maximum error and drift of the counter is +/-0,5%.
The user may experiment with shifting the periodic
tests. To avoid error accumulation, and in case
your unit is programmed to allow Automatic Periodic
PROTECTIONS
EP6 ENGINE PROTECTION
M
39.12.
4
© MOSA
1.0-10/05
12/10/05 M39GB
4 digits DISPLAY
Ideograms
Button
[F1]
Button
[ENTER] (*)
Key
(OFF-ON-START)
Button [+]
(*)
Button [-] (*)
Button
[AUTO]
AUTO (Yellow
Led)
[UP DOWN]
Button
Green LED
engine on
Front view
Closing
cover
Cables outlet
Rear view
Recommended hole dimensions:
91mm (+/- 0.5) x 91mm (+/- 0.5)
Rear cover
(*) The use of these buttons is
reserved only to the manufacturer
of the generating set.
11.0 DIMENSIONS
Содержание GE 225 VPS
Страница 44: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX M 61 1 MOSA REV 1 07 06 22 05 06 84228 I...
Страница 45: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX EP6 M 61 2 MOSA 1 0 05 06 22 05 06 84228 I...
Страница 46: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX M 61 3 MOSA 1 0 05 06 22 05 06 84228 I...
Страница 47: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX EP6 M 61 4 MOSA 1 0 05 06 22 05 06 84228 I...
Страница 48: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX M 61 5 MOSA 1 0 05 06 22 05 06 84228 I...
Страница 49: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX EP6 M 61 6 MOSA 1 0 05 06 22 05 06 84228 I...
Страница 50: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX M 61 7 MOSA 1 0 05 06 22 05 06 84228 I...
Страница 51: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX EP6 M 61 8 MOSA 1 0 05 06 22 05 06 84228 I...
Страница 52: ......