USE

GE 225 - 275 VPS - VPSX

M

33

© MOSA

1.0-09/02

INTRODUCTION

The “GECO” equipment entails a control unit for absolutely
modern generators.  Its strong holds are the following:

- Large-size graphical display (95x45 mm) to be able to display

all the electrical parameters at the same time (with characters
of 10mm).

- The membrane keyboard has built-in keys with relative

indicator LEDs.  It also offers a high degree of reliability and
ideal touch-sensitive keys.

- The HELP key with relative LED that flashes to point out that

a message is to be read

- The use of the dater clock to set the weekly TEST and to

display all the events that occur and that may be shown on
the Display.

- The control of 4 different mains/generator line systems:

N-L1-L2-L3

L1-L2-L3

L1-N-L2 (AMERICAN market)

N-L1

- Operational temperature range from -20 to + 60°C
- Protection rating IP64
- 5 possible languages: Italian-English-French-German-

Spanish

- Generator protection against OVERLOADS and SHORT-

CIRCUITS with setting of the rated current of the generator,
setting of the short-circuit current in percentage of the rated
current value of the generator and a tripping delay timing of
the protection device in tenths of a second.

Parameters Displayed

The LCD shows data and information in graphic and
alphanumeric forms. Press the “

⇓⇓⇓⇓⇓

” or “

⇑⇑⇑⇑⇑

” keys to view the data

pages. Press the “

” or “

+

” keys to see alternative data on the

same page.

N.B.

 on the display it appears MAINS or GENERATOR for

showing to whom the measure are referred.

The measure on the display are the followings:

-

Battery voltage

-

Mains and phase generator voltages, between the lines
and of the system

-

Phase currents

-

Phase and total active, reactive and apparent powers.

-

Active, reactive and apparent energy.

-

P.F. - Power factor of each phase.

-

Energy contact maker

-

Frequency of the generator.

-

Oil pressure instrument

-

Water temperature instrument

-

Fuel level instrument

-

Engine RPM

-

Number of successful starting attempts

-

Number of failed starting attempts

-

Number of total starting attempts

-

Total hours of use

-

Partial hours of use

-

Hours left to maintenance

KEYBOARD

HELP key – 

The illuminated LED means a help message is

available. By pressing the key, a help message concerning the
current operation  is displayed.

ENTER 

and

 EXIT keys - 

 Press ENTER to confirm operations

or to enter the menu. Press EXIT to refuse an operation or to
exit a menu and help message.

⇓⇓⇓⇓⇓

” and “

⇑⇑⇑⇑⇑

” arrow keys – 

Press these keys to shift to the

different pages of data display or to select parameters.

“–” and “+” keys

  –

 

Press these keys to display alternative

data of the selected data page or to modify the parameters.

OFF/RESET, MAN, AUT and TEST

 keys – Press these keys

to select the operating mode. The illuminated LED indicates
the selected operating mode; if it is flashing, remote control is
active.

03/09/02  84275-GB

Содержание GE 225 VPS

Страница 1: ...GE 225 VPS VPSX 842289003 GB 0 7 0 6 11 07 06 84228M00 preparato da UPT approvato da DITE ISTRUCTIONS MANUAL...

Страница 2: ...which will continue to satisfy the needs of its clients as well as to improve the transparency and the communications regarding all the company s actives in accordance with the official procedures and...

Страница 3: ...2 TRANSPORT AND DISPLACEMENTS M 20 SET UP FOR OPERATION M 21 START AND STOP M 31 CONTROLS M 33 USE OF THE GENERATOR M 33 1 USE OF THE GECO CONTROL UNIT M 37 USING THE GENERATOR M 38 6 TCM 35 REMOTE CO...

Страница 4: ...aws in force in the matter In no case MOSA division of B C S S p A will be held responsible for any damaga direct or indirect in relation with the use of the given information MOSA division of B C S S...

Страница 5: ...aces protected from dampness and heat You must take into account that some figures contained in it want only to identify the described parts and therefore might not correspond to the machine in your p...

Страница 6: ...rk European Community certifies that the product complies with the essential safety requirements provided by the applicable COMMUNITY DIRECTIVES In the Conformity Declaration are reported the HARMONIZ...

Страница 7: ...harm to persons or things Do not use without protective devices provided Removing or disabling protective devices on the machine is prohibited Do not use the machine if it is not in good technical con...

Страница 8: ...IONS No harm for persons Use only with safety clothing It is compulsory to use the personal protection means given in equipment Use only with safety clothing It is compulsory to use the personal prote...

Страница 9: ...mediately to a non polluted zone the person involved FIRE PREVENTION In case the working zone for whatsoever cause goes on fire with flames liable to cause severe wounds or death follow the first aid...

Страница 10: ...of the temperature Make sure that the machine does not move during the work block it possibly with tools and or devices made to this purpose Protect all the electric parts at risk because water infilt...

Страница 11: ...Installazione Installation Installation Luftzirkulation Instalaci n E D NL GE 225 VPS VPSX M 2 7 MOSA 1 0 07 04 26 07 04 84227 I...

Страница 12: ...as not been rough handling or taking away of parts contained inside the packing or in the set In case you find damages rough handling or ab sence of parts envelopes manuals etc we ad vise you to infor...

Страница 13: ...he lifting devices are correctly mounted adequate for the weight of the machine with it s packaging and conform to local rules and regulations Only authorized persons involved in the transport of the...

Страница 14: ...t the cable positive to the pole positive of the battery after having taken away the protection by properly tightening the clamp Check the state of the battery from the colour of the warning light whi...

Страница 15: ...or tap with the motor in operation or still hot as the liquid coolant may spurt out and cause serious burns Remove the tap very carefully GROUNDING CONNECTION The grounding connection to an earthed in...

Страница 16: ...ting with TCM35 Put the SWITCH BOARD selector on ON Connect TCM35 to the plug on the front panel and put the switch on 0 Turn the key on ON in the EP6 Engine Control wait for the various signals to go...

Страница 17: ...cet m S lecteurtransvasementpompeAUT 0 MAN Contr le groupe lectrogene GECO Potentiom tre r gulateur de tension S lecteur OFF ON DIAGN Bouton DIAGNOSTIC Vojant DIAGNOSTIC Protection moteur EP6 Descripc...

Страница 18: ...o identify and signal possible disfunctions in the EDC 4 system The engine protection is entirely secured by the EDC 4 electronic system while the oder devices of the electric board direct and check t...

Страница 19: ...e or keys to view the data pages Press the or keys to see alternative data on the same page N B on the display it appears MAINS or GENERATOR for showing to whom the measure are referred The measure on...

Страница 20: ...it can not be reset MAN mode The engine can be manually started or stopped using the START and STOP keys only in addition to load switching from mains to generator and vice versa by means of the MAINS...

Страница 21: ...e A19 Low engine W speed A20 High engine W speed A21 Starting failure A22 Emergency stop A23 Unexpected stop A24 Engine stop failure A25 Low generator frequency A26 High generator frequency A27 Low ge...

Страница 22: ...geover Rated voltage 250VAC max Rated current at 250VAC 8A AC1 2A AC15 Relay output 6 2 6 3 6 4 6 5 terminals battery voltage output Contact type 1 NO Rated voltage 30VDC Rated current at 30VDC 5A DC1...

Страница 23: ...55011 98 IEC EN 60255 21 2 95 IEC EN 60068 2 6 LLOYD RINA regulation sect E chap 3 or IEC EN 60068 2 52 96 IEC EN 60068 2 61 93 Sect 3 par 13 of the standard Sect 3 par 15 of the standard 4 kV 1 2 50...

Страница 24: ...USE GE 225 275 VPS VPSX M 33 5 MOSA 1 0 09 02 Terminal board connections seen from rear Overall dimensions 03 09 02 84275 GB...

Страница 25: ...reference environmental conditions and nominal values for voltage frequency power factors cos There are various types of power PRIME POWER PRP STAND BY POWER established by ISO 8528 1 and 3046 1 Norms...

Страница 26: ...asynchronous motor it is necessary to check that there are no utilities inserted into the installation which in the case of a voltage droop can cause more or less serious disservices opening of contac...

Страница 27: ...al pole on the thermic protection forcefully pressed to prevent its intervention ATTENTION USAGE WITH EAS AUTOMATIC START UP PANEL The electricity generating group in combination with the EAS automati...

Страница 28: ...ling of the TCM 35 with the generating set ready for remot starting permits to work far from the set itself The remote control is connected to the front plate X1 and or rear plate with a multiple conn...

Страница 29: ...is equipped with three tests two of which are effected automatically by the instrument 1 manual test trial push button 2 automatic test of the toroid relay connection guard 3 automatic test of the boa...

Страница 30: ...LED illuminates continuously and a start cycle will take place NOTE the EP6 shuts down the display during the crank C In order to cancel the AUTO operating mode push the AUTO pushbutton the yellow Led...

Страница 31: ...ibration Pro Programming rEAd Parameter reading StOP Stopping cycle MM SS Remote Start or Remote Stop cycle 5 0 LEDs for visual indication The EP6 features two LEDs see section 10 0 to indicate the fo...

Страница 32: ...tor voltage rises above the setting for at least 2 seconds the EP6 will energize the over voltage protection Hi U see section 4 0 to stop the engine The inh code inhibits the over voltage P 8 Generato...

Страница 33: ...00 teeth The Inh code disables the reading of the Speed section 3 0 the Over Under Speed alarms and the Crank termination see P 24 P 24 Crank OFF Inh Crank Termination setting 100 800 rpm If the speed...

Страница 34: ...mmed number of days and the engine will run for the programmed time To determine how the Automatic Periodic Test is programmed enter the Reading Mode section 6 0 parameter P 26 and P 27 IMPORTANT NOTE...

Страница 35: ...3 Oil level too high 4 Motor speed regulator defective 1 Clean or replace 2 Ask for intervention of Service Department 3 Eliminate excess oil 4 Ask for intervention of Service Department Black smoke 1...

Страница 36: ...alternator manual Ask for intervention of Service Department 7 Check winding diodes etc on alternator Refer to alternator manual Repair or replace Ask for intervention of Service Department No load vo...

Страница 37: ...the laws and or dispositions in force in the place WARNING Have qualified personnel do maintenance and troubleshooting work Stop the engine before doing any work inside the machine If for any reason...

Страница 38: ...all levels engine oil fuel level battery electrolyte if necessary top it up 3 Control of electrical connections and cleaning of control panel EVERY WEEK NO LOAD X WITH LOAD X X X X X For the electrici...

Страница 39: ...Clean the covers and all the other parts of the machine carefully Protect the machine with a plastic hood and store it in o dry place DIESEL ENGINE For short periods of time it is advisable about ever...

Страница 40: ...ncerning the cust off involve the manipulation of fluids potentially dangerous such as lubricating oil and battery electrolyte The dismantling of metallic parts liable to cause injuries or wounds must...

Страница 41: ...different from those above mentioned please call our Assistance Authorized Centers ACOUSTIC POWER LEVEL The machine respects the noise limits expressed in sound power given in the a m directives Thes...

Страница 42: ...Dimensioni Dimensions Dimensions MOSA 1 0 05 06 Abmessungen Dimensiones GE 225 VPS VPSX M 53 E D NL 22 05 06 84228 I...

Страница 43: ...O HI 30 l min solenoid valve E4 Hydraulic oil pressure switch F4 Hycraulic oil level gauge G4 Preheating glow plugs H4 Preheating gearbox I4 Preheating indicator L4 R C filter M4 Heater with thermosta...

Страница 44: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX M 61 1 MOSA REV 1 07 06 22 05 06 84228 I...

Страница 45: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX EP6 M 61 2 MOSA 1 0 05 06 22 05 06 84228 I...

Страница 46: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX M 61 3 MOSA 1 0 05 06 22 05 06 84228 I...

Страница 47: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX EP6 M 61 4 MOSA 1 0 05 06 22 05 06 84228 I...

Страница 48: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX M 61 5 MOSA 1 0 05 06 22 05 06 84228 I...

Страница 49: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX EP6 M 61 6 MOSA 1 0 05 06 22 05 06 84228 I...

Страница 50: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX M 61 7 MOSA 1 0 05 06 22 05 06 84228 I...

Страница 51: ...Schema elettrico Electric diagram Schemas electriques GE 225 VPSX EP6 M 61 8 MOSA 1 0 05 06 22 05 06 84228 I...

Страница 52: ......

Отзывы: