EAS15-806-GB.doc
EAS 15 - 806
REV.1-07/11
E01 Remote stop
During the generator operation, in AUT mode, if the stop input is closed for a longer time than 0,5sec, the alarm as per table is executed. The display
visualizes E01
E02 Emergency stop
During the generator operation, if the emergency input is closed for a longer time than 0,3sec, the alarm as per table is executed. The display visualizes
E02
E03 Alarm auxiliary
During the generator operation, if you close the input 83 (auxiliary alarm) for a longer time than E3.05 (programmable), the alarm as per table is
executed. The display visualizes E03
During the alarm, if enabled, the siren output closes for a time equal to U.08.
During the alarm, if enabled, the output alarm closes until the cause of the alarm has disappeared.
It is possible to deactivate the siren and the alarm by pressing “RESET”.
3 - EAS ELECTRICAL PANEL PROGRAMMATION INSTRUCTION
3.1- Access procedure USER MENU and ADVANCED MENU description
USER MENU:
Access to the user menu is possible through this procedure:
1) Press RESET button.
2) Hold TEST button for 5 s.
the display shows the first parameter of the USER MENU: “
U01
- Automatic test interval time”
The description of the user menu parameters is showed on the specific table.
Warning: the changes of advanced menu parameters, could cause serious functioning problems at the EAS electrical
panel or the generator.
ADVANCED MENU:
Access to the advanced menu is possible through this procedure:
1) Hold RESET button for 8s.
the display shows
-
2) Hold START button for 2s.
the display shows
- -
3) Hold STOP button for 2s.
the display shows
- - -
4) Hold MEAS button for 2s.
the display shows
- - - -
5) Press START button
the display shows the first parameter of the ADVANCED MENU: “
P1.01
– Nominal frequency ”
The description of the advanced menu parameters is showed on the specific table.
3.2 - Parameters modification instructions (user and/or advanced menu)
TEST button allows to see the default value of the parameter.
START button allows to increase the value and STOP button allows to decrease the value. For the time, START button increases the hours value and
STOP button increases the minutes value.
RESET button saves the value of the modified parameter, and AUT button exits from it.
MEAS button allows to change (increase) the number of the parameter in a same menu.
MAN button allows to change (increase) the number of the menu (only for advanced menu).
Once the programming is done, press AUT then RESET to save and exit to the programming mode to function mode.
3.3 – Setting the generator voltage
Any panel has original factory settings, it may be necessary anyway to adjust it once installed. It is therefore necessary that readings on the display are
checked with
an external tester to make sure they’re correct. In case of difference it is strictly necessary to recommence the setting procedure so that to
avoid any malfunction.
-Switch on the generating set in MAN mode
- keep on pressing for about 8” the TEST button
until the TEST LED switches on
- Press the button to increase voltage. – Press the button to decrease voltage
- When this setting procedure is over, press button for about 1” to confirm and then exit from the procedure.