background image

 
6

ENG

1.7 Connecting the stove to a masonry chimney

A  wall  sleeve  should  be  bricked  securely  into  the  wall  of  the  chimney  at  the  appropriate 
height and the stovepipe inserted centrally. The pipe must not extend into the actual chimney 
opening, but rather must reach only to the inside of the chimney aperture. The gap between 
the stovepipe and sleeve must be sealed using glass fibre packing rope.

Only use stovepipe components that comply to National and Local Building Regulations.

1.8 Connecting to a stainless steel insulated chimney system

If your installation involves taking the chimney straight up and through the ceiling, you must 
comply with National, Local Building Regulations or flue manufacturers instructions concern-
ing clearances to combustible materials such as walls, floor joists and ceilings. The joint be-
tween the stove flue collar and the stovepipe must also be sealed using the glass fibre rope 
provided. It is important that the insulated flue system is properly supported both at ceiling 
level and at roof level. THE STOVE MUST NOT BEAR THE WEIGHT OF THE CHIMNEY SYS-
TEM (See chimney manufacturer’s instructions). Excessive weight on the stove will inhibit ex-
pansion and could lead to damage of the stove top. Damage caused to the stove in this way 
would not be covered by the manufacturers guarantee.

In  the  event  that  a  chimney  fire  resulting  from  faulty  operation  or  prolonged  use  of  damp 
wood fuel, close the air vents completely and contact your local fire department immediately.

Be aware of the following: 

Cleaning  procedure:  Discuss  this  with  chimney  sweep  or  qualified  installer 
prior to or during the stove installation

Chimney draft: If the chimney draft is naturally poor it is better to install the 
flue from the top of the stove so as to minimise any internal resistance of the 
flue gases.
 
Avoid having any more than 2 bends in the flue system and limit the length of 
the offset between bends.

Fresh air supply

A  wood-burning  stove  requires  air  for  combustion  and  therefore  you  may 
need to install additional ventilation to the room, especially so in well insulat-
ed houses. If the air supply in inadequate the chimney draft may be too weak, 
with the possible result that the stove will not burn properly; smoke spillage 
may also occur during the refuelling process.

On a positive note, a properly installed wood-burner will give even the most 
efficient houses a pleasant and natural ventilation.

Содержание 1412

Страница 1: ...Website www morsoe com MORSØ JERNSTØBERI A S DK 7900 NYKØBING MORS E Mail stoves morsoe com Website www morsoe com Instructions for Installation and Use 1412 1442 1452 EN 13240 74 6 efficiency Distributed by Morsø UK Valley Drive Swift Valley Rugby Warks CV21 1TW England ...

Страница 2: ...21 1 4 Stove placement clearance requirements 21 1 5 The chimney 22 1 6 Pipe connections 23 1 7 Connecting to a masonry chimney 24 1 8 Connecting to a steel chimney 24 1 9 Draught conditions 24 2 0 Firing the stove 26 2 1 Lighting instructions and fuelling intervals 27 3 0 Routine stove maintenance 30 3 1 External maintenance 30 3 2 Internal maintenance 30 3 3 Cleaning the stove 31 4 0 Alternative...

Страница 3: ...ately and instructions are enclosed with the soapstone packaging We recommend that two people perform the assembly and installation procedure The Morsø 1412 weighs 70 kg while the Morsø 1442 weighs 80 kg and the 1452 weighs 120 kg 1 2 Installing the stove The stove and chimney installations MUST comply to all current National and Local Building Reg ulations your approved Morsø dealer or your local...

Страница 4: ...adversely affected by heat The clearances to combustible materials in front of the stove should be a minimum of 700 mm When lit a wood burning stove gets hot and therefore adequate protect must be pro vided particularly in situations where there is a safety risk to children or the infirm A suitable safety guard around the stove should be considered The stoves handle also gets hot when the stove is...

Страница 5: ...ss doors for inspection and cleaning The size of the cleaning door in the chimney must at least equal to that of the cross section al area of the chimney 1 6 Fluepipe connections Your stove is supplied ready for a top flue connection 3 the rear flue outlet is fitted with a cover plate and is situated behind the rear heat shield convection panel Where a rear flue in stallation is required simply kn...

Страница 6: ...turer s instructions Excessive weight on the stove will inhibit ex pansion and could lead to damage of the stove top Damage caused to the stove in this way would not be covered by the manufacturers guarantee In the event that a chimney fire resulting from faulty operation or prolonged use of damp wood fuel close the air vents completely and contact your local fire department immediately Be aware o...

Страница 7: ...f the chimney is excessively cool it may help to prime the flue before the fire is lit Just place a screwed up sheet of newspaper in the flue ways of the sto ve and ignite The outside temperature is too high e g during the summer months There is no air movement wind outside The chimney is not tall enough with the result that the terminal sits in the lee of the roof surface or in the vicinity of ta...

Страница 8: ...l etc This means that it may take some time before you get to know the cor rect functioning of the stove under any given circumstances Although you can fire your Morsø stove with almost all kinds of wood you should not fire with wet wood or unseasoned wood Wood ought to be stored under a roof for at least 1 year and preferably 2 years with free access to wind Wood should be chopped as soon as poss...

Страница 9: ...aws well 4 After 5 10 minutes the chimney draft should be establis hed at this point close the fire door If all the necessary conditions are met a nice layer of embers will start to accumulate after another 15 20 minutes 2 1 Lighting and refuelling intervals A lot of air is needed when first lighting the stove When starting with a totally cold stove it may be helpful to leave the door ajar 2 3 cm ...

Страница 10: ... one layer with spacing of roughly 1 cm between the pieces of wood 7 When the secondary air supply top vent is opened all the way and the door is closed the new fuel will ignite in a few minutes 8 Once the new fuel has taken adjust the secondary air amount to the desired setting optimal combustion will continue until glowing charcoals are produced Under normal chimney draft conditions expect to re...

Страница 11: ...trongly recommend that you do not leave your stove alit at night It harms the environment and constitutes very poor use of the wood as the gases in the wood do not ignite at the low temperature but settle as soot unburned gases in the chimney and stove Extreme conditions such as poor draught in the chimney large quantities of wood or wet wood may in the worst case scenario cause an explosive ignit...

Страница 12: ...easons for sooted glass window fuel is too wet green pieces of fuel uncut wood are too thick operating temperature of the stove is too low too much air coming through bottom grate POOR CHIMNEY DRAFT Internal cast iron parts and or wear components The shaking grate baffle plate and other internal components that are in direct contact with the fire are all constituted as wear components or consumabl...

Страница 13: ...64 can easily be removed from the stove and should be regularly checked for debris and cleaned You must ensure that your chimney sweep removes all soot and debris from the stove after the sweep ing process Your chimney should be swept at least once a year however a regular inspection of your stovepipe and chimney will determine whether a more frequent approach should be adopted Ash As noted above ...

Страница 14: ...te complete 54141361 Access Door 44146400 Front grate 44141400 Glass panel 1410 790726 Glass kit with screws clips gasket 1410 62904000 Glass panel 1430 790721 Glass kit with screws clips gasket 1430 62904200 Glass panel 1440 790724 Glass window kit with screws clips gasket 1440 62904100 Side firebrick 79094700 Coal inserts fuel economisers 62905100 ...

Страница 15: ...re once it has ignited Continue in this manner until the entire grate is covered with glowing coals The level of fuel in the stove should never exceed the level of the front grate s Once the bottom half of the fuel bed is glowing you should partly close the bottom vent on the ash pit door Once the stove has reached your desired temperature you can maintain the output by opening further for more he...

Страница 16: ...16 MORSØ JERNSTØBERI A S DK 7900 NYKØBING MORS E Mail stoves morsoe com Website www morsoe com Morsø Jernstøberi A S 10 01 2008 72146800 ...

Отзывы: