7. 

Reattach

 the front cover of the Alarm using the fasteners at the four corners of the cover.  DO NOT 

OVERTIGHTEN.  “Snug” the fasteners in place and verify that the cover is fully seated to the enclosure base.

8. 

Test 

the Installation

a.

 Test

 connection at the alarm and wiring

i. 

For Normally Open Contact Inputs: 

  Short the two wires together at the input device end for each input device. This should cause the 

alarm to flash the Beacon, illuminate its Channel Alarm Indicator(s) and sound (if so configured) 

until the Test/Cancel button is pushed. If the alarm fails to go into an alarm condition, check the 

connections and the batteries and retest until results are satisfactory.

ii. 

For Normally Closed Contact Inputs: 

  Short the two wires together and then separate the wires at the input device end for each input 

device. This should cause the alarm to flash the Beacon, illuminate its Channel Alarm Indicator(s) 

and sound (if so configured) until the Test/Cancel button is pushed.  If the alarm fails to go into an 

alarm condition, check the connections and the batteries and retest until results are satisfactory.

b.

 Connect

 the wires from the Alarm Box to the wires of the input device at the junction box for each 

device.

c. 

Replace

 the junction box cover.

d. 

Simulate

 an alarm condition and manually trigger the alarm using the input device (Clock Gauge, float 

switch or other dry contact device). 

e. 

Troubleshoot

 as needed.  If the Alarm does not go into an alarm condition, check wiring at junction 

box and verify that the installation procedure was performed correctly. The alarm can be silenced after 

being activated by pressing the Test/Cancel button.

9. 

IMPORTANT: 

Install the included Warning Tag where it will be visible to the operator filling or unloading 

the tank that is fitted with this alarm.

Failure to follow any or all of the warnings and instructions in this document could result in a hazardous 

liquid spill, which could result in property damage, environmental contamination, fire, explosion, serious 

injury or death. 

Le fait de ne pas se conformer à l’un ou l’autre des avertissements ou à l’une ou l’autre des directives

apparaissant dans ce document pourrait donner lieu à des déversements de liquides dangereux, lesquels 

pourraient engendrer des dommages matériels, des risques de contamination environnementale,  

d’incendie ou d’explosion, des blessures graves ou la mort.

Operation

The 918SB may be used anywhere that a single set of dry contacts are available. The 918SB can be configured 

to respond to either Normally Open (default configuration) or Normally Closed contacts. Two possible primary 

applications are used as an overfill alarm or as an interstitial alarm. These two uses are addressed below.

The 918DB may be used anywhere that up to two set of dry contacts are available. The 918DB can be configured 

to respond to either Normally Open (default configuration) or Normally Closed contacts. Two possible primary 

applications for each channel are as an overfill alarm or as an interstitial alarm. These two uses are addressed below. 

The 918QB may be used anywhere that up to four set of dry contacts are available. The 918QB can be configured 

to respond to either Normally Open (default configuration) or Normally Closed contacts. Two possible primary 

applications for each channel are as an overfill alarm or as an interstitial alarm.  These two uses are addressed 

below.

Use as an Overfill Alarm

Use with the Morrison Brothers 918 Clock Gauge or other similar input device.

1. Prior to filling a tank, test for an existing overfill condition, the battery level and overall operation of the 

Alarm.

a.

 

Press and hold the “Test/Cancel” button for more than 5 seconds while listening to the Audible Alarm 

and observing the Beacon, the Channel Alarm Indicator(s) and BATTERY LOW Indicators

 

(see Figure 1).

Содержание 918DB Series

Страница 1: ...or death Le fait de ne pas se conformer l un ou l autre des avertissements ou l une ou l autre des directives apparaissant dans ce document pourrait donner lieu des d versements de liquides dangereux...

Страница 2: ...ort es cette unit autres que celles indiqu es dans ces directives engendreront l annulation de la garantie du produit Pour assurer votre s curit il est important de vous conformer la r glementation lo...

Страница 3: ...the wires to the wires in the junction box of the input device s at this time Although not required it is recommended to run the wires in some type of conduit in order to protect them against possibl...

Страница 4: ...ery Assembly see instructions below If the Audible Alarm still does not sound the Beacon does not illuminate or the BATTERY LOW indicator illuminates replace the Alarm Box or call Morrison Bros Co Cus...

Страница 5: ...ault ENABLED OFF DISABLED 918SB 918DB 918QB 3 Channel 1 Normally Closed Open ON Normally Closed Contacts OFF default Normally Open Contacts 918SB 918DB 918QB 4 Channel 2 Normally Closed Open ON Normal...

Страница 6: ...ure is disabled the Alarm will flash its Beacon illuminate its Channel Alarm Indicator s 918DB and 918QB and sound the Audible Alarm if so configured until the battery can no longer power the Alarm Bo...

Страница 7: ...at is fitted with this alarm Failure to follow any or all of the warnings and instructions in this document could result in a hazardous liquid spill which could result in property damage environmental...

Страница 8: ...than 10 minutes at which point it will silence itself b If the Autosilence feature is NOT enabled and the alarm is not silenced by the operator then the 918 Series Alarm will continue to alarm until...

Страница 9: ...scheduled maintenance operations MONTHLY Test the battery level and overall operation of the Alarm see 2 below YEARLY Check the Enclosure for water ingress see 3 below Battery replacement instruction...

Страница 10: ...Alarm Circuit Board d Disconnect the battery cable from the Alarm Circuit Board J7 Gently depress the retaining tab of the connector and pull the connector free see Figure 6 e Remove and retain the t...

Страница 11: ...el Input Connector see Figure 2 m Reattach the front cover of the Alarm using the Phillips head fasteners at the four corners of the cover DO NOT OVERTIGHTEN Snug the fasteners in place and verify tha...

Страница 12: ...12 Morrison Bros Co Dubuque IA 800 553 4840 918SB 0134 PP rev 8 3 2017...

Страница 13: ...13 Morrison Bros Co Dubuque IA 800 553 4840 918SB 0134 PP rev 8 3 2017...

Отзывы: