Morningstar TRISTAR TS-MPPT-60 Скачать руководство пользователя страница 5

As with the power circuits, MorningStar MeterBus (RJ-11) and MODBUS Serial (RS-232 and EIA-485) 

ports all share a common negative with the negative power circuits of the system. With certain 

configurations involving these types of communications, single-pole battery breakers, switches or fuses 

cannot be used on the negative power conductors of the system. This is because the disconnect 

switches will be bypassed through the communications and damage can occur due to the unintentional 

current path through the smaller communications wiring and circuits. 

 

There are a few scenarios where using a single pole disconnect and/or overcurrent protection on the 

ungrounded conductor could present a problem. 

● EIA-485 MODBUS networks (Fig. 4) 

● Ethernet MeterBus Converter (EMC-1) systems (Fig. 5) 

● Systems which include Relay Driver(s) with an RJ-11 MeterBus connection (Fig. 6) 

● RS-232 MODBUS connections to 3rd party devices 

 

Note that the MeterHub provides an isolated connection between the MeterBus ports when creating a 

MeterBus network. Therefore, MeterBus networks will not be problematic except where the direct 

connection between a controller and a Relay Driver can cause harmful current through the MeterBus 

connection.  

 

The systems below are examples of where the use of a single-pole breaker would not be an option. 

When in doubt it is best to use a double-pole breaker to avoid any common negative communications 

issues.  

 

Fig. 4 – Positive grounded TriStar MPPT/ TriStar system with EIA-485 network: The  EIA-485 network 

wiring creates a common negative connection between the controllers. The single-pole battery breakers 

on the negative, ungrounded conductors as shown on the left will not break the negative connection to 

the controller when the other controller is connected and could cause damage to the communications 

circuits. Double-pole breakers which disconnect both the positive and negative conductors shown in the 

right can be used in order to  disconnect each controller independently without harm to the serial 

communications. 

Содержание TRISTAR TS-MPPT-60

Страница 1: ...n help keep voltage surges induced from nearby lightning from affecting the power electronics equipment and loads This is not an option for systems that include ground fault protection as it will be tripped if there is more than one ground bond A Single Point to Earth In addition to negative grounded systems all Morningstar controllers can be used in positive grounded systems if they are wired in ...

Страница 2: ...Positive Grounding Graphic Illustrations Fig 1 This system is grounded properly on the battery circuit only Charging and Load Control will function properly ...

Страница 3: ...rly Fig 3 This system will not charge properly It has been grounded in two locations and a ground loop will be created around the TriStar charge controller The controller will now no longer be able to properly control charging current since its circuit has been bypassed ...

Страница 4: ...e the chassis can be grounded the same for a positive ground system as it is for a negative grounded system Grounding the chassis is required by code in many jurisdictions Surge protection devices include a connection to the equipment ground in order to function properly to limit voltage surges from nearby lightning strikes Many Morningstar controllers include a chassis ground terminal If it doesn...

Страница 5: ...at the MeterHub provides an isolated connection between the MeterBus ports when creating a MeterBus network Therefore MeterBus networks will not be problematic except where the direct connection between a controller and a Relay Driver can cause harmful current through the MeterBus connection The systems below are examples of where the use of a single pole breaker would not be an option When in dou...

Страница 6: ...harm to the serial communications Also note that the fuse for the power circuit to the EMC 1 should be installed on positive wire Fig 6 TriStar MPPT and Relay Driver system with an RJ 11 MeterBus connection The MeterBus RJ 11 creates a common negative connection between the controller and relay driver The single pole battery breakers as shown on the left will not break the negative connection to t...

Страница 7: ...2 device is another option Ground fault Protection and Positive Grounded Systems One last consideration is Ground Fault Protection Ground Fault Protection protects the system from ground faults that may be created in the PV circuit Morningstar s Ground Fault Protection products GFPD 150V and GFPD 600V can be used with either negative or positive grounded systems to detect and interrupt ground faul...

Отзывы: