31
OPERATION
MS-003650
(Rev 0 Draft 10)
3.2 AC Output Mode Switch Operation
The AC Output Mode Switch will always turn the inverter on directly in the ON (up)
position. To enable ON/OFF control with a wired remote switch or a communication
command (digital command), the switch must be in the REMOTE position. Select
remote switch or digital command using DIP Switch # 1.
Figure 24: AC Output Mode Operation and Bluetooth Activation
3.3
Protections
3.3.1
Low Voltage Disconnect (LVD)
The SureSine will disconnect AC Output when the battery discharges
below the Low Voltage Disconnect (LVD) set point (after a 4-minute delay).
AC Output will resume when the battery has recharged to Low Voltage
Reconnect (LVR) set point. The LVD/LVR thresholds are adjustable using DIP
Switch 4. See "Adjusting Settings" on page 11 for details.
Audible LVD Warnings:
• The SureSine will beep four (4) times when the battery discharges to the
LVD Warning threshold voltage.
• The SureSine will beep twice when Low Voltage Disconnect occurs.
• The LVD Warning occurs 0.3 V above the selected LVD threshold.