User’s Manual Supplement
TMZ (2TPRG) Dual Input Model
Description
PV1 (integer)
PV2 (integer)
SV1 (integer)
SV2 (integer)
Percent of range channel 1 (integer)
Percent of range channel 2 (integer)
TMZ dual input status information
Raw measurement from front-end channel 1
Raw measurement from front-end channel 2
TMZ dual input additional status information
PV1 (float)
PV2 (float)
SV1 (float)
SV2 (float)
Percent of range channel 1 (float)
Percent of range channel 2 (float)
TMZ dual input status information
TMZ dual input additional status information
TMZ on line (0) off line (1) mode
Model Type
0 = low level (single input)
1 = high level (single input)
2 = special RTD (single input)
19 = low level dual input
20 = high level dual input
Do not use
Register
0
1
2
3
4
5
6
7
8
9
256-257
258-259
260-261
262-263
264-265
266-267
268
269
512
513
514-531
Variable
PV1
PV2
SV1
SV2
PercentOfRange1
PercentOfRange2
errorStatus
Measured PV channel 1
Measured PV channel 2
errorStatus2
PV1
PV2
SV1
SV2
PercentOfRange1
PercentOfRange2
errorStatus
errorStatus2
TMZ_Offline
Model Type
Reserved
Read/
Write
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
w
Table S-2.
MODBUS Register Table
TMZ MODBUS Register Set
Table S-2 contains all of the MODBUS integer registers
supported by the TMZ (2TPRG) dual input model. These
registers constitute both the 30000 and 40000 register set.
Specifications and information subject to change without notice.