Head-Mount Enclosure Installation
(Including Moore Industries’ LH enclosure)
Installation Components Required: Sensor Probe, Spring,
Cap and Spacer(s).
1.
Determine the length of the thermowell assembly (see
the illustration to the left). Cut the WORM Spring to be
between 1 and 1½
inches
longer
than the
length of the
assembly (this is
necessary so that the
Spring’s compression
securely holds the
Sensor Probe to
the bottom of the
thermowell).
2.
Ensuring that
the uncut portion
of the Spring faces
down towards the
Sensor Probe, slide
the Spring over the
sensor wires and
onto the end of the
Sensor Probe.
3.
Slide the Cap over
the sensor wires onto
the top of the Spring.
4. Remove the
instrument from the
enclosure. Insert
the WORM sensor
into the thermowell.
Slide the appropriate
length(s) and number
of Spacers to keep
the WORM Spring
straight inside the
thermowell assembly
lag (Spacers may not
be required).
5.
Reinstall the
instrument into the enclosure, compressing the WORM
Spring into the thermowell with the bottom of the
instrument. Connect the sensor wires.
Generic Enclosure Installation
Installation Components Required:
Sensor Probe,
Spring, Stopper and Spacer(s).
1.
Determine the length of
the thermowell assembly
(see the illustration to the
right). Cut the WORM
Spring to be between 1
and 1½ inches
longer
than the length of the
assembly (this is
necessary so that the
Spring’s compression
securely holds the
Sensor Probe to
the bottom of the
thermowell).
2.
Ensuring that
the uncut portion
of the Spring faces
down towards the
Sensor Probe, slide
the Spring over the
sensor wires and
onto the end of the
Sensor Probe.
3.
Remove the
instrument from
the enclosure (if
necessary). Insert
the WORM sensor
into the thermowell.
Slide the appropriate
length(s) and number
of Spacers to keep
the WORM Spring
straight inside the
thermowell assembly
lag (Spacers may not
be required).
4.
Slide the Stopper
over the sensor wires
onto the top of the
Spring. Push the
Stopper firmly into the thermowell entry port to compress
the WORM Spring into the thermowell.
5.
Reinstall the instrument into the enclosure. Connect the
sensor wires.
Sensor
Probe
Spring
1-Inch
Spacer
2-Inch
Spacer
1-Inch
Spacer
Determine the
length of the
thermowell
assembly and
cut the Spring
to be between
1 and 1½
inches longer.
Sensor
Probe
Spring
Stopper
Generic Enclosure
1-Inch
Spacer
2-Inch
Spacer
1-Inch
Spacer
Determine the
length of the
thermowell
assembly and
cut the Spring
to be between
1 and 1½
inches longer.