SPA
32
The Interface Solution Experts
Site-Programmable Volt &
Milliamp Limit Alarm Trips
Change the Security Password Code
This menu is active when the Security Jumper is NOT
installed, or when the jumper is installed and a cor-
rect password has been entered. When the jumper
is installed, unless the correct password is entered,
accessing this menu causes the “PASS LOCK” mes-
sage to appear. Any attempt to make changes will be
“locked out” (READ ONLY mode).
Figure 18 shows the menu.
1. From the “PASS WORD” screen, press
SELECT to access “## PASS”.
2. Use the arrow buttons to increment or
decrement the password number to be
stored in unit memory.
3. Press SELECT when the desired
password number is displayed. This
returns the user to the Main Menu.
NOTES:
The password can be any number between
00 AND 99.
When the security jumper (Figure 3) is NOT
installed, pressing SELECT from
“PASS WORD” shows the current
password setting.
Figure 18. Changing the HLPRG SPA Password Code
PASS
WORD
CONF
ALRM
CONF
Z/FS
##
PASS
CONF
Z/FS
VIEW
SELECT
VIEW
SELECT
INCREMENT
DECREMENT
MAIN MENU