Moore Industries DPS 240 Скачать руководство пользователя страница 5

Page 3

DPS

Calibration

Each power supply is calibrated and checked at the
factory to ensure proper performance before shipping.
However, output values for each unit should be
checked by the user on-site before the equipment is
placed into service.

Indicators

There is a red LED indicator on the front panel of the
DPS 240, which lights when the unit is producing dc
output.  The indicator, labeled “OUTPUT ON”, goes
out if a short circuit, overload, or any other unaccep-
table condition occurs during operation.

Controls

The unit’s front panel has two multiturn potentiom-
eters labeled “VOLTAGE ADJUST” and “CURRENT
LIMIT”.  Voltage adjust allows the user to set dc out-
put to ±5.0% of the rated value.  Using the current
limit potentiometer, the user can calibrate the unit so
that the output voltage stays within the specified
range, even when input varies ±10%.  This protects
the DPS 240 from possible damage due to overheat-
ing.

Refer to table 1 for the equipment specifications of
the DPS 240.

Calibration Equipment

Table 2 lists the equipment required to calibrate the
DPS 240.  This equipment must be provided by the
user.

Table 2.  Calibration Equipment

Description

Variac or equivalent; capable of 105-264 Vac output

Accurate to 0.01 millivolt

Accurate to 1.0 milliamp

Powerstat, or equivalent; capable of output load of 175ý

Head measuring less than 2.54 mm (0.1 inch) in width

Equipment

Adjustable ac Power Source

Voltmeter

Milliammeter

Variable Power Resistor

Screwdriver, slotted

Содержание DPS 240

Страница 1: ...DPS 240 Milliamp DIN style Power Supply May 2016 221 703 00 E 240 Milliamp DIN style Power Supply DPS...

Страница 2: ...l Assistance and Repair our Quick Ship Facility HR DELIVERY 48 Moore Industries CENTER United States Canada TOLL FREE 1 800 999 2900 United Kingdom FREE PHONE 0800 525107 Australia TOLL FREE 008 25192...

Страница 3: ...onnection of calibration equipment and a red LED indicator that lights when dc output is present The terminal blocks three for input and eight for out put can be set into either the front or rear pane...

Страница 4: ...according to customer requirement adjustable 5 0 with front panel potentiometers Regulation 0 5 maximum low line to high line 70 typical rated at full load Load 1 0 maximum no load to full load Rippl...

Страница 5: ...ws the user to set dc out put to 5 0 of the rated value Using the current limit potentiometer the user can calibrate the unit so that the output voltage stays within the specified range even when inpu...

Страница 6: ...ure 1 depicts the correct calibration setup for the DPS 240 Before beginning to the calibration itself connect the unit as shown and set the load to 100 ohms for 24Vdc units or 175 ohms for 42 Vdc uni...

Страница 7: ...p Calibration Procedure To calibrate the DPS 240 1 Turn CURRENT LIMIT potentiometer fully clock wise 2 Vary setting of VOLTAGE ADJUST potentiometer from fully clockwise to fully counterclockwise Note...

Страница 8: ...epresentative or Moore Industries Customer Service Department The use of 14 22 AWG insulated copper wire is rec ommended in connecting the DPS 240 terminals To avoid transients and stray pick ups it i...

Страница 9: ...ction of the DPS 240 DPS CURRENT LIMIT OUTPUT ON T T GND AC ACC DC OUT DC OUT GND AC ACC DC OUT DC OUT AC POWRER SOURCE 117 220 OR 240 VAC 2 WIRE TRANSMITTER CURRENT DRIVEN DEVICE POWER SUPPLY VOLTAGE...

Страница 10: ...NOTES...

Страница 11: ...R BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVENT B...

Отзывы: