P No.
Index P Name / Setting
Unit Function
characteristic current
3
F1
Hz
First frequency interpolation point of motor
protection characteristic
4
FNom
Hz
Rated frequency
5
IMax
%
Maximum overload current in relation to the
rated current of the motor
6
Time
s
Time for which the maximum current may be
connected
7
Ttherm
s
Set thermal time constant in seconds
735
0
MON_MotorI2tType
Motor protection module. Selection of I2T
monitoring method
Off(-1)
Protection disabled
FREQU(0)
Motor frequency-dependent evaluation i(f),
default setting
THERM(1)
Evaluation with thermal time constant i
Tth
. The
thermal time constant is set via parameter
P 733[7]
in [s]. The shut-off threshold based on
measurement tolerances is 110% of the
nominal value.
Table 5.7: “Temperature monitoring” parameters (continue)
NOTE
l
With a MSD Single-Axis Servo Drive Compact the temperature
sensor cable can be connected to both X6 and X7.
l
1)
(MSD Single-Axis Servo Drive Compact and
MSD Servo Drive Safety require an adapter)
NTC adapter - 220 kOhm available)
l
2)
With MSD Single-Axis Servo Drive Compact
The following table provides an overview of the selection options for sensor types
with P 732[0] as well as the connection options for the plug-in connectors X5, X6, X7
and X8 (Tech. option) for MSD Servo Drive and MSD Single-Axis Servo Drive
Compact.
MOOG
ID No.: CB40859-001 Date: 11/2020
MSD Servo Drive - Device Help
42
5 Motor
MSD
Servo
Drive
MSD Single-Axis Servo
Drive Compact / MSD
Servo Drive Safety
Sensor
type
Parameters
Plug-in
connector
Plug-in connector
X5
X6
X5
X6
(1)
X7
(1)
X8
(4)
KTY
P 732[0] = 1, 9
X
X
—
X
X
PTC
P 732[0] = 2, 4, 12
X
X
X
X
X
TSS
P 732[0] = 3
X
X
X
X
X
NTC
P 732[0] = 6, 7, 8, 10, 11
2)
—
X
—
X
—
PT
P 732[0] = 5
3)
, 13
X
X
—
X
X
1) X6/X7 bridged internally
2) not MSD Single-Axis Servo Drive Compact
3) only MSD Single-Axis Servo Drive Compact
4) Tech-opt card X8-HDSL: all settings P732[0].Type = 1..13 are possible! (with HDSL firmware (v3.44.20-xx))
Table 5.8: Temperature sensor connections with plug-in connectors.