background image

P/N XG0515

Page 19

Tuscany

 Gas Fireplace Insert

Installation

Appendix B - State of Massachusetts

Amendment

(gas Fireplace / equipment sold in the state of Massachusetts)

 5.08: Modifications to nFPA-54, chapter 10

 

(1) revise nFPA-54 section 10.5.4.2

 

by adding a second exception as follows:

existing chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manually reset device 

that will automatically shut off the gas to the burner in the event of a sustained back-draft

.

 

(2) revise 10.8.3

 by 

adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, 

including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in 

the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 

 

1. InstAllAtIon oF cArBon MonoXIDe Detectors.

 

At the time of installation of the side wall horizontal vented gas fueled equip-

ment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor 

level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon 

monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled 

equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon 

monoxide detectors

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with 

alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days 

to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm 

shall be installed.

 

2. APProveD cArBon MonoXIDe Detectors.

 

each carbon monoxide detector as required in accordance with the above provisions 

shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified. 

 

3. sIgnAge.

 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet 

above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print 

size no less than one-half (1/2) inch in size, “GAS VeNT DIReCTLY BeLOW. KeeP CLeAR OF ALL OBSTRUCTIONS”.

 

4. InsPectIon.

 The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, 

upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. 

(b) eXeMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 

 

1. The equipment listed in Chapter 10 entitled “equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the 

Board; and 

 

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or struc-

ture used in whole or in part for residential purposes.  

 

(c) MAnuFActurer reQuIreMents - gAs eQuIPMent ventIng sYsteM ProvIDeD

. When the manufacturer of Product 

Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions 

provided by the manufacturer for installation of the equipment and the venting system shall include:

 

1. Detailed instructions for the installation of the venting system design or the venting system components; and

 

2. A complete parts list for the venting system design or venting system. 

 

(d) MAnuFActurer reQuIreMents - gAs eQuIPMent ventIng sYsteM not ProvIDeD

. When the manufacturer of a Prod-

uct Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, 

the following requirements shall be satisfied by the manufacturer:

 

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and 

 

2. the “special venting systems”

 shall be Product Approved by the Board, and the instructions for that system shall include a parts list and 

detailed installation instructions. 

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for 

venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

 

(3) After nFPA-54 section 10.10.4.2

 add a new section 10.10.4.3 as follows:

When more than four gas appliances are to be vented through a common gas vent or common horizontal vent manifold, a plan of the proposed vent installation 

shall be submitted to the Inspector and the serving gas supplier for review and approval.

extraction from: Massachusets rules and regulations

5.00: Amendments to 2002 edition of AnsI Z223.1-nFPA-54

Содержание DelRay Tuscany 34DVI

Страница 1: ...lectricity Danger for cutter Entrapment hazard Battery hazard Rotating parts Low temperature Strong magnetic field Optical radiation Non ionizing radiation Radiation Hazardous to the Environment Danger of harming your hands Warning Iftheinformationintheseinstructions is not followed exactly a fire or explosionmayresultcausingproperty damage personal injury or death Irritant Cutting Watch your step...

Страница 2: ...e retain this owner s manual for future reference Safety Alert Key 3 Introduction 3 Models 3 Warranty Information 3 Overview 4 Before You Begin 4 Clearances 4 Inspecting Cleaning the Chimney 4 Section 1 Installation 5 Installing the Gas Line 5 Installing the Chimney Liner 5 6 Section 2 N A Section 3 N A Section 4 N A Section 5 N A Section 6 N A Section 7 Removing and Installing the Door 7 Installi...

Страница 3: ...r of death Biohazard Laser Radiation Danger of entrapment Hot surface General Warning Blank Gas bottles Watch for falling objects Electricity Danger for cutter Entrapment hazard Battery hazard Rotating parts Low temperature Strong magnetic field Optical radiation Non ionizing radiation Radiation Hazardous to the Environment Danger of harming your hands Safety Alert Key Irritant Cutting Watch your ...

Страница 4: ...e outside of the chimney and masonry for damage including cracked loose or damaged bricks andmortar orothermaterialsthatcouldinhibitthecorrect installationoftheflexiblechimneyliner Ensurethatanydamage or deterioration has been properly repaired Removeanyglazedcreosotethathasbuilt upinsidethechimney The existing passageway must be cleared of any obstructions that would prevent the flex liner instal...

Страница 5: ... control valve is located underneath the firebox in the control compartment The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5 kPa The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure...

Страница 6: ...e pipe with the screws provided Seal between the flashing and chimney cap with high temperature silicone See figure 6 STEP 6 Run a wide bead of silicone along the top of the clay liner and press the flashing and chimney cap down on top of the chimney STEP 7 Before placing the Tuscany in its location lay a piece of cardboard on the hearth to protect it Place the Tuscany just in front of the firepla...

Страница 7: ...fireplace opening and ensure that both the air intake and exhaust vents are properly installed As per previous section 3 Ensure that the gas line is properly connected to the flexible gas connector and tested for any leaks 4 Position the backing plate along the top of the insert and attach it using the three screws provided See figure 10a below 5 Loosen the four screws on the inside edge of the fa...

Страница 8: ...igure 12 Slide the insert into place Wiring Instructions for the Fan Switch Circuit 6 Connectthewirewiththeplastic Molex connectorontheleftsideof the control compartment to the wire which leads to the Fan Sensor Switch Run the fan s power cord out through the small notch on the bottom left side of the faceplate Figure 11b Wiring Schematic for the fan circuit Wiring Instructions for the On Off Circ...

Страница 9: ... Start the fireplace If the flame appears satisfactory replace the glass door If the flame does not appear satisfactory double check the air inlet and exhaust outlet pipe to ensure that they are unobstructed 2 The back log is factory installed along with the ceramic brick liner as shown below in figure 12b 3 Place the Front log onto the front log rest as shown in figure 12c The log has lip on the ...

Страница 10: ...34HDVI The Tuscany 34HDVI is supplied with a six ceramic fibre log logset Unpack the logs and handle them very carefully Step 1 RemovetheglassdoorasdescribedinthepreviousInstructions Air Inlets Pilot Assembly Fireplace Base Rear Bottom Log Notch in Log Log A Air Inlets Fireplace Base Log D Figure 27c Top Left Log Log D Air Inlets Fireplace Base Log E Step 5 Place Front Left log Log D as shown in f...

Страница 11: ...r cutter Entrapment hazard Battery hazard Rotating parts Low temperature Strong magnetic field Optical radiation Non ionizing radiation Radiation Hazardous to the Environment Danger of harming your hands Caution DO NOT COVER THE BURNERS WITH FIRESTONES OR FAUX RIVER ROCKS 1 Remove the glass door as described in the previous Instructions Back of Fireplace Air Inlets Figure 29a Firebox prior to faux...

Страница 12: ...and will settle on the floor What To Do If You Smell Gas Q Q Do not try to light any appliance Q Q Do not touch any electrical switch do not use any phone in your building Q Q Immediately call your gas supplier from a neighbour s To Turn Off Gas To Appliance 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Replace the lower Horizontal access panel 1 Turn off remote swit...

Страница 13: ...round the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor What To Do If You Smell Gas Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s To Turn Off Gas To Appliance 3 Push in gas control knob slightly and turn clo...

Страница 14: ...trol knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including near the floor If you then smell gas STOP Follow B in the safety information above on this label If you don t smell gas go to the next step 5 Locate pilot burner and follow steps below 6 Turn knob on gas control counterclockwise to PI LOT 7 Push in gas control knob completely and hold Light with ...

Страница 15: ... fireplace is first activated there may be some smoking and a visible film may be left on the glass This is a normal condition and is the result of burning of protective coatings on new metal Glass must be cleaned periodically to remove any film which is a normal by product of combustion which may be visible Film can easily be removed by removing the door as shown on Page 20 Handle the door carefu...

Страница 16: ...DVI 34HDVI 34RDVI NG Gas Valve RGC1021 RGC1015 RGC1006 RGC1006 LG Gas Valve RGC1022 RGC1016 RGC1005 RGC1005 NG Pilot RPA020 RPA020 RPA020 RPA020 LP Pilot RPA021 RPA021 RPA021 RPA021 Front Burner NG RBT1099 Rear Burner LPG Front Orifice NG Rear Orifice LPG Logs Spare Parts List ...

Страница 17: ...ance must be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability It is expressly agreed and understood that The Companies sole obligation and purchaser s exclusive rem...

Страница 18: ...Page 18 Tuscany Gas Fireplace Insert P N XG0515 Installation ...

Страница 19: ...ght of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve ...

Страница 20: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0515 120507 ...

Отзывы: