ELECTRICAL INSTALL ATION

      Permanently Connected Equipment:

Disconnecting devices shall be included in the system 

installation.  The disconnects shall be within close prox-

imity  of  the  equipment,  accessible  to  operators,  and

marked appropriately as the disconnect for the associated

circuit.   Assure  the  disconnect  ratings  are  appropriately

sized for the circuit protected (See Specifications).

Circuit Separation:

Two cable entry locations are provided to aid in maintain-

ing  separation  of  “hazardous  live”  (typically  mains  volt-

ages such as 115VAC and 230VAC) and limited circuits

(typically control voltages less than 30Vrms or 42.4VDC

such as the data communication signals).  However, since

the 

Wireless

EZ

Communication  Interface's  single  wiring

compartment can not absolutely protect against physical

contact  between  multiple  circuits,  it  is  required  that  all

wiring used must have an insulation rating of 300v mini-

mum, and a temperature rating of 176˚F (80˚C) minimum.

Protective Earthing:

Each 

Wireless

EZ

Communication  Interface  is  provided

with a "protective conductor terminal"   which shall be ter-

minated to the local earth ground potential.  This terminal

shall  be  used  to  eliminate  shock  hazard  in  the  unlikely

event of internal insulation breakdown.   Select wire size

that can carry in excess of the sum of all circuit's maxi-

mum amperage.

EMI Optimizing:

(See Figure 5)

Ferrite beads are provided for installation in the wiring to

minimize affects of EMI.  Wrap the large ferrite bead with

the incoming power wires (including protective earth con-

ductor)  two  to  four  full  turns  through  the  bead’s  core.

Wrap small ferrite bead with incoming data wires(RS-485)

two  to  four  full  turns  through  the  bead’s  core.    Position

each bead immediately inside the cable entrance of the

enclosure.

Power Input:

1) 85 to 265VAC Source:

(See Figure 6) Verify the 

    intended voltage supply is compatible with the voltage

    configuration indicated on the electronics and the 

    external nameplate.  Standard mains supply voltage 

    (85VAC to 265VAC as ordered) can be connected to 

    the unit's H/L1 and N/L2 terminals.

Figure 5

Figure 6

Содержание WirelessEZ

Страница 1: ...e safety of all personnel Before discarding shipping container or the internal packing materials please inspect the packaging thoroughly and verify that all parts are accounted for This product is shi...

Страница 2: ...In some challenging applications it maybe necessary to install a higher performance antenna that requires co axial cabling between the radio and the antenna The co axial cable introduces loss into th...

Страница 3: ...en 6 lower then the box with a means to disperse any accu mulated water in the conduit so that water does not pour into the box Likewise if installing with cable and the cord connectors provided posit...

Страница 4: ...176 F 80 C minimum Protective Earthing Each WirelessEZ Communication Interface is provided with a protective conductor terminal which shall be ter minated to the local earth ground potential This term...

Страница 5: ...n 9322 or Alpha 6302 The order of connection is not important i e the WirelessEZ Communication Interface can be connected between SMUs if necessary The WirelessEZ Communication Interface creates a wir...

Страница 6: ...6 Figure 9...

Страница 7: ...on is used to terminate the RS 485 link to achieve maximum communication reliability If no RS 485 communica tions is to be used simply turn OFF this selection If there is to be RS485 communications th...

Страница 8: ...e insure cover is fully engaged and that wire entries are properly sealed Cleaning Requirements In the event that the antenna is fouled by external contam ination reliable communication of the RF wire...

Страница 9: ...WirelessEZ Communication Interface 2 Verify electrical power is connected that it is the proper voltage as indicated on the nameplate and that the magnitude is within the specified limits 3 Verify sta...

Страница 10: ...MECHANICALS WirelessEZ Communication Interface Left Standard Antenna Center high Gain Antenna Right Yagi Antenna DIMENSIONS ARE ShOWN IN INChES WITh MILLIMETER EqUIVALENT IN BRACkETS General Safety C...

Отзывы: