MAIN MENU
SUB MENU 1
SUB MENU 2 SUB MENU 3
COMMENTS
RS485
PROTOCOL
Modbus RTU
Modbus ASCii
SiloPatrol (default)
Select for generic Modbus RTU protocol.
Select for generic Modbus ASCii.
Select for proprietary SiloPatrol protocol.
COMM
PARMS
Modbus RTU
9600,8,E,1
9600,8,N,1
9600,8,N,2
9600,8,O,1
19200,8,E,1
19200,8,N,1
19200,8,N,2
19200,8,O,1
Modbus ASCii
9600,7,E,1
9600,7,N,2
9600,7,O,1
9600,8,E,1
9600,8,N,1
9600,8,N,2
9600,8,O,1
19200,7,E,1
19200,7,N,2
19200,7,O,1
19200,8,E,1
19200,8,N,1
19200,8,N,2
19200,8,O,1
SiloPatrol
9600,8,N,1
baud rate, # bit, parity, # stop bit
Options available are dependant on the
protocol selected.
(default protocol: SiloPatrol)
DEVICE
ADDRESS
Modbus RTU
#1 - 247
Modbus ASCii
#1 -247
SiloPatrol
#1 - 16
Acceptable addresses are dependant on the
protocol selected.
(default address: #1)
RELAY
SETTINGS
RELAY ACTION
FORCE RELAY
RELAY THRESHOLD
OFF
CYCLE
OPERATE
ERROR
LOW
THRESHOLD
HIGH
THRESHOLD
NOT ACT (on)
ACT (off)
###.#
No relay action, energized whenever power is
applied.
Relay relaxed while SMU is sounding,
energized when bob idle.
(default: CYCLE OPERATE)
Relay relaxed when error is detected,
energized when error dismissed.
When distance => thres, relay relaxed
When distance < thres, relay energized
Use distance from latest measure, only
update on "good" cycles, relaxed if Genesis.
When distance > thres, relay energized
When distance <= thres, relay relaxed
Use distance from latest measure, only
update on "good" cycles, relaxed if Genesis.
Relay temporarily not activated (on) regardless of status.
Relay temporarily activated (off) regardless of status.
Distance threshold
range: 0 ~ 150ft / 0 ~ 45.7m
(default: 150ft)
MAIN MENU
SUB MENU 1
SUB MENU 2 SUB MENU 3
COMMENTS
4-20mA
SETTINGS
4mA DISTANCE
20mA DISTANCE
ERROR REACTION
FORCE CURRENT
TRIM 4mA
TRIM 20mA
CURRENT
UPDATE
#0 ~ 200ft
#0 ~ 200ft
<2mA
>23mA
OFF
< 2mA*
4mA
12mA
20mA
>23mA*
-50 ~ +50
-50 ~ +50
Continuously
End Of Travel
Can be configured as 4-20 or 20-4mA,
depending which value is closer to NEAR
SOCKET & NEAR EOT
(default: 4mA: CSL; 20mA: 0Ft
)
Tx value <2mA upon error detection.
Tx value >23mA upon error detection.
Selected 4~20mA signal temporarily emitted.
*denotes error signals
Display unit less number while calibrating, ±
0.25mA offset.
Display unit less number while calibrating, ±
0.25mA @ F.S.
4~20mA value will be updated progressively
as bob descends, holding a value that corre-
sponds to EOT (error signal may override
when bob reaches socket).
4~20mA value will be updated only when bob
reaches EOT (error signal may override when
bob reaches socket).
12
Menu Selection for ConfigueSensor App - Analog 4-20mA
(Factory Defaults are Shown in Bold)
Figure 12