background image

5

//1 1&&2012

9

DF

5(

/$

<

9G

F

5(

/$

<

1&&2012

'&'&

$8726(783

$%9

56

5(

/$

<

5(

/$

<

/

/

/

/

,62/$7('

/2$'

/,1(6

,62/$7('

/2$'

/,1(6

//1

0$,1632:

9$&

9GF

32:(5

1232/$5,7<

:,5,1*',$*5$0

WR56

0$67(5

'(9,&(

(

Figure 4

6)        

Protective Earthing

- Each 

Dust

Alarm

®

ES

monitor is provided with a "protective conductor terminal" 

which shall be terminated to the local earth ground potential 

to eliminate shock hazard. Select wire size that can carry in excess of

the sum of all circuit's maximum amperage. Because the intrinsically

safe sensor probe does not pass a 500V dielectric withstand test to

earthing terminal, this probe shall be considered as electrically con-

nected to the enclosure.

7)  Access to Terminal Connections

(See Figure 4) - Loosen 

the cover lock screw and slide the lock mechanism down towards the

mounting point; tighten the screw to prevent parts from dislodging.

Remove the screw-on cover of the 

Dust

Alarm

®

ES

and set it aside.

Customer accessible connections are for power and relay outputs. All

Dust

Alarm

®

ES

sensors come from the factory compatible for MAINS

VAC or low voltage DC operation.

8)  Power Input

- Verify the intended voltage supply is compatible with

the voltage configuration indicated on the external nameplate. The

sensor can be powered with AC MAINS OR 24 VDC on separate

blocks. Connect the power wiring as shown in Figure 4. The customer

supplied power cable must have a minimum conductor size of 1mm

2

(18 awg). Additionally, the customer is responsible for installing a main

power disconnect as mentioned above. 

l

Minimum 80C field wiring shall be used.

l

Haz-Loc Versions: AC Mains Supply...AC input power terminals shall 

be protected by a fuse value no greater than 85mA.

l

Haz-Loc Versions: DC Supply...DC input power terminals shall be 

protected by a fuse value no greater than 250mA.

9)  Relay Output Contacts 

- The 

Dust

Alarm

® 

ES

relay contacts are

power failsafe, meaning that the relays will be in the same state in a

power failure as they would be in an alarm state. The SPDT (form C)

relay contacts are electrically isolated from all other parts of the sen-

sor. The relay terminal blocks are labeled true to the relay contacts, 

N/C-COM is active when relay is relaxed, and N/O-COM when relay is

powered. Connect relay contact wiring as shown in Figure 4. 

l

Minimum 80C field wiring shall be used.

l

Relay contact terminals shall be protected by a fuse value 

no greater than 5A.

10) RS-485 Terminal 

- The RS-485 output is an isolated digital signal

output that can be used to monitor the active signal being measured,

and the general status of the sensor. This digital connection can be

daisy chained to multiple sensors on the same RS-485 network to

minimize the amount of wiring. Protocol used on this network is

Modbus RTU.
The RS-485 network cabling should be a single route that travels from

device to device, with no branches that form T’s or stars. A network

termination should be activated on any device that is at the physical

end of an RS-485 network. For the dust sensor models, this is 

accomplished by:

ACTIVE

: termination jumper present (ends of RS-485 network)

DEACTIVATED

: termination jumper removed (all devices in the middle

of RS-485 network)
If the PLC/master device happens to be at the end of the network, 

then a termination selector should be activated within that device.
See the Set-Up & Configuration section for guidance of the 

calibration and configuration process.

11) USB PORT 

- A USB mini-B connector is provided to allow easy and

fast connection of the sensor to a portable PC with the 

Dust

Config

TM

application loaded onto it for sensor configuration. See bulletin # 764C to

navigate the 

Dust

Config

TM

application.

NOTE:

The sensor USB connector is NOT isolated from local 

earth ground; the USB connection is intended for local, temporary 

connection during the configuration process only.

12)  Re-assembly

- Replace the enclosure cover and secure cover

lock to protect the electronics from damage or contamination, unless

you are ready to proceed with setup of  the 

Dust

Alarm

®

ES

sensor at

this time.

$8726(7836:,7&+

86%PLQL%

56

02'%86

7(50,1$/

5(/$<

,1',&$7256

6(16(

67$786

,1',&$7256

561(7:25.

7(50,1$7,21

35(6(17DFWLYH

5(029('QRWDFWLYH

6(1625&21752/6 ,1',&$7256

&

//1 1&&2012

9

DF

5(

/$

<

9G

F

5(

/$

<

1&&2012

'&'&

$8726(783

$%9

56

5(

/$

<

5(

/$

<

SET-UP AND CONFIGURATION

Remove the enclosure cover of the 

Dust

Alarm

®

ES

unit and note the

controls and indicators on the label covering the top board assembly

(See Figure 5).  The following is a brief description of each:

Indicators

1)

GREEN LED - The green LED indicates power is applied to 

    the sensor, and there is no alarm status. Also, when the green

    LED is flashing the auto setup process is under way.

2)

RED LED - The red LED indicates an alarm condition. If the 

    red  LED  is  on  constant,  the  first  threshold  has  been 

    exceeded. If the red LED is flashing, the second threshold has

    been exceeded.

3)

YELLOW LED’s - The yellow LED’s indicate the state of the 

    relay it is adjacent too. When a yellow LED is lit, the 

    respective relay is powered. When the LED is off, the relay 

    is in a relaxed state.

RS-485  -

The  serial  communication  parameters  in  the  sensor

must be configured to match the master device on the RS-485

network before the Modbus output will function:

Figure 5

Parameter

Factory Default

Baud Rate:

38.4K

Parity:

NO

# Stop Bits:

2

Device #:

255

(aka: Modbus slave ID

or address #)

More details

on the next

page >>>

Содержание DustAlarm ES

Страница 1: ...uipment and the safety of all personnel Before discarding shipping container please inspect it thoroughly and verify that all parts ordered are accounted for Sometimes smaller parts become stuck under carton flaps and other packaging materials In the event that information contained herein does not completely satisfy your requirements or answer your questions you may contact Technical Support on o...

Страница 2: ...m of a dust collec tion system Signal output is varied as the measured dust changes When the signal generated by moving dust particles exceeds a preset threshold an alarm output is generated Influence of Particle Material The signals transmitted by different types of dust particles can vary greatly from one material to another For example Inorganic electro conductive materials metals create the lo...

Страница 3: ...cting where there is laminar flow and the dust particles are evenly dis persed within the air stream This ensures the sensor probe is exposed to a particle stream in an area where the most stable airflow condition exists Such an area has no airflow disturbance caused by elbows duct size transitions diverter valves etc In the event there are such flow disturbances near the selected mounting area en...

Страница 4: ...ion In installations where multiple cir cuits are used i e independent circuits for power input and relay out put individual disconnects are required The disconnects shall be with in close proximity of the equipment accessible to operators and marked appropriately as the disconnect for the associated circuit Ensure the disconnect ratings are appropriately sized to the circuit protected See Specifi...

Страница 5: ...n be daisy chained to multiple sensors on the same RS 485 network to minimize the amount of wiring Protocol used on this network is Modbus RTU The RS 485 network cabling should be a single route that travels from device to device with no branches that form T s or stars A network termination should be activated on any device that is at the physical end of an RS 485 network For the dust sensor model...

Страница 6: ...minutes and is indicated by a flashing green LED Ensure no unusual events occur that could provide for false measurements during this auto setup period At the end of the of the period the green LED will become constantly lit 5 Using the Auto Set up method will automatically configure these parameters Running average of measured signal 100 sec time constant default Alarm 1 threshold 5x measured val...

Страница 7: ...Pressure Insulation Material Probe Material Probe Length Ship Dims Weight Approvals MET US C ATEX IECEx Conformity 95 240VAC 10 50 60 Hz 18 28VDC 10 5VA AC 2 5W DC 1500A 250VAC 300A 30VDC 6 562 ft 2000m max II 2 Max 392 F 200 C at probe location CLll Class III installations Process tempera ture must not exceed 325 F 164 C 4 to 149 F 16 to 65 C 22 to 149 F 30 to 65 C Max 95 RH non condensing 3A 250...

Страница 8: ...B U L L E T I N 764A Monitor Technologies LLC 44W320 Keslinger Rd t Elburn IL 60119 t 630 365 9403 t 800 766 6486 t monitor monitortech com t www monitortech com ARB JSC MAR 19 2021 DOC 001 764A 4 ...

Отзывы: