Dip switch settings function

 

„

 

Pin 1 & Pin 2

Valve on to stop engine timer

 

Pin1 

Pin2 

Valve on stop engine delay 

OFF OFF 

sec 

ON OFF 

10 

sec 

OFF ON 

15 

sec 

ON ON 

20 

sec 

List 2 Stop Period 

„

 Pin3

System frequency

ON

50Hz

OFF

60Hz

 

„

 Pin4

Escape motor by oil pressure switch

ON

Enable

OFF

Disable

 

„

 Pin5

Pressure switch type

ON

Normal Open

OFF

Normal Close

 

„

 Pin6

Idle / Pre-heat output delay time

ON

10

120

Sec

OFF

1

10

Sec

 

„

 

Pin7

Low DC Volt

ON

10.5VDC

OFF

21VDC

 

„

  Pin8 & Pin9 Cooling time

 

Pin8 Pin9 

Cooling 

time 

OFF OFF 

Sec 

ON OFF 

60 

Sec 

OFF ON 

150 

Sec 

ON ON 

300 

Sec 

List 3 Cooling Time 

„

 

Pin10

Idle / Pre-heat Function Select

ON

Idle

OFF

Pre-heat

 

4. Case Dimension

 

 

Fig. 3 GTR-168 Case Dimension of Back View

   

Fig. 3 GTR-168 Case Dimension of Back View

 

 

 