11
M400BFC Balanced Flue Heat-Circulating Fireplace
87D1505
Positioning, Safety Strips,
Securing the Fireplace
Slide fireplace into position.
Lift the fireplace front slightly and slide the metal safety
strips under front bottom edge about 1
Z\x
” (38 mm),
allowing the remainder to extend in front of firebox.
Overlap strips at least 1/2” (13 mm) to provide a posi-
tive joint. (Flat safety strips are packed with fireplace.)
(Fig. 12)
Safety strips are used to ensure that any combustible
materials in front of the fireplace are protected even
though a non-combustible hearth extension is required.
If fireplace is to be elevated above the floor, a “Z”
shaped metal safety strip must be fabricated and used
to protect combustible surfaces in front of the fireplace.
This “Z” shaped safety strip is not provided but must be
fabricated of metal with each horizontal leg at least 1
Z\x
”
(38 mm) wide and equal in length to the metals strips
provided with the fireplace.
NOTE:
Safety strips are not required over non-com-
bustible floors where all supports at the base of the
fireplace are noncombustible.
Four (4) nailing flanges are supplied with the fireplace
(found on the fireplace hearth). To level the box and
secure it firmly in place, remove the nailing flanges from
the hearth and install at the sides of the fireplace as
shown in Figure 13.
FPC549a
BFC
Nail flange/standoff
circulating models
8/21/00 djt
Nail Top
Standoffs
Nail Side-
Nailing
Flanges
FPC549a
Fig. 13
Fasten fireplace in position.
WF557
BR
11/10/97
Metal Safety Strips
(1,2 or 3 pcs.)
“Z” Safety
Strip
(not sup-
plied)
Fire-
place
Plat-
form
Hearth Ext.
Z\x
” (13mm)
Min. Overlap
1
Z\x
”
(38mm)
FP557b
Fig. 12
Safety strip installation.