VENT INSTALLATION
BELOW GRADE INSTALLATIONS
When it is not possible to meet the required vent terminal clearances of 12" above grade level, a snorkel kit is recommended.
It allows installation depth down to 7" (178mm) below grade level. The 7" (178mm) is measured from the center of the
horizontal vent pipe as it penetrates through the wall.
Ensure that sidewall venting clearances are observed. If venting system is installed below ground, we recommend a
window well with adequate and proper drainage to be installed around the termination area.
If installing a snorkel, a minimum 24" vertical rise is necessary. The maximum horizontal run with the 24” vertical pipe is
36". This measurement is taken from the collar of the fireplace (or transition elbow) to the face of the exterior wall. See the
Sidewall Venting Graph for extended horizontal run if the vertical exceeds 24".
1. Establish vent hole through the wall.
See Figure 16, page 18.
2. Remove soil to a depth of approximately 16" below base of snorkel. Install drain pipe. Install window well (not supplied).
Refill hole with 12" of coarse gravel leaving a clearance of approximately 4" below snorkel.
See Figure 26.
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe coming through the wall.
5. Apply high temperature sealant caulking (supplied) around the 4" and 7" snorkel collars.
6. Slide the snorkel into the vent pipes and secure to the wall.
7. Level the soil so as to maintain a 4" clearance below snorkel.
See Figure 26.
• Do not back
fi
ll around snorkel.
• A clearance of at least 4" must be
maintained between the snorkel and
the soil.
W
ARNING
If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fasten brackets to
wall first, then secure to snorkel with self drilling #8x
1
/
2
sheet metal screws. It will be necessary to extend vent pipes out as
far as the protruding wall face.
See Figure 27.
Figure 27 - Snorkel Installation,
Recessed Foundation
Figure 26 - Below Grade Installation
Screws
Minimum
4" Clearance
Ground
Window Well
Gravel
Drain
Foundation Wall
Firestop
24"
Minimum
Foundation
Recess
Watertight Seal
Around Pipe
Sheet Metal
Screws
Wall Screws
Snorkel
Содержание Direct Vent Gas Fireplace HBDV300
Страница 43: ...54D5031 43 1 2 3 5 6 7 10 4 9 11 REPLACEMENT PARTS FIREPLACE COMPONENTS ...
Страница 45: ...54D5031 45 8A HBDV400 8B HBDV300 11 12 13 14 15 3 4 5 6 7 8 2 1 2T 2I 2C 10 REPLACEMENT PARTS MILLIVOLT ENGINE ...
Страница 51: ...54D5031 51 NOTES ...
Страница 52: ...52 54D5031 NOTES ...
Страница 53: ...54D5031 53 NOTES ...