4

If the unit is 

dc powered

, connect the dc supply Positive to the terminal

marked 

L+

 and the dc supply Negative or Common to the terminal

marked 

N-

.

NOTE:

On dc powered units, no connection is required to the terminal
marked 

GND

.

SENSOR CONNECTIONS

A speed sensor (not included) is connected to the terminals under the
section labeled 

INPUT 

on the rear panel.  Refer to Figure 2 and 3.

Connections and their functions are as follows:

+5V

Po5 Vdc to provide power to optical, laser, infrared or
amplified magnetic sensors.  Maximum load is 75 mA dc.

PX+

Po8 Vdc supply for use with two wire proximity
sensors. Maximum load for proper operation with two wire
sensors is 5 mA.

SIG

Positive input signal from the speed sensor. Accepts TTL pulses
or ac signals, unipolar and bipolar, from 1.5 Vac to 50 Vac.
(Contact the factory for increased sensitivity.) Connect the
signal wire from three wire sensors or the positive side of two
wire magnetic sensors to this terminal.  Typical input
impedance is 10 Kohms.

COM

Common or Negative connection for both signal and power
from most sensors.

7

Figure 4  Current Output Option Connections

NOTE:

The voltage source you use will determine the maximum
resistance of the load.  This voltage is referred to as the
compliance voltage and must be equal to the maximum
current through the load (20 mA) multiplied by the load
resistance, plus 4 Vdc.  For example, if the load is 1000 ohms,
the external voltage source must be:

(1000 ohms x 0.020 A) + 4 Vdc = 24 Vdc

Thus, for an external source voltage of 24 Vdc, the
maximum loop load (the sum of all resistances in the loop) is
1000 ohms.  24 Vdc is, in fact, a recommended voltage.  The
voltage supplied by an external source should 

NEVER

exceed 40 Vdc.  The ACT-1B 15 Vdc internal voltage source
(

+VA

) permits a maximum load resistance of 500 ohms.

Содержание ACT-1B-10

Страница 1: ...TRUMENT Instruction Manual 15 Columbia Drive Amherst NH 03031 2334 USA Phone 603 883 3390 Fax 603 886 3300 E mail techsup monarchinstrument com Website www monarchinstrument com Printed in the U S A M...

Страница 2: ...all material respects when used in strict compliance with such documentation or manual Notwithstanding the foregoing BUYER acknowledges that since software is complex and therefore may have defects B...

Страница 3: ...y that the product to which this declaration relates is in conformity with the following standards and therefore conforms with the requirements of Council Directive 89 336 EEC relating to electromagne...

Страница 4: ...ed Sensors Optical Monarch ROS 5W Proximity Monarch P5 11 Magnetic Monarch M 190W or MT 190W Infrared Monarch IRS 5W Laser Monarch RLS 5W IO Option 4 to 20 mA see page 7 for maximum load calculation F...

Страница 5: ...terminal connections on the rear panel of the instrument If specified at time of order placement the ACT 1B may be equipped with either an optional 4 to 20 mA current output IO or 0 to 5 Vdc analog ou...

Страница 6: ...d N Connect the Ground Earth wire to the terminal marked GND NOTE For full compliance with CE specifications the Ground GND connection must be made Analog Output Option AO The analog output is 0 to 5...

Страница 7: ...Contact the factory for increased sensitivity Connect the signal wire from three wire sensors or the positive side of two wire magnetic sensors to this terminal Typical input impedance is 10 Kohms COM...

Страница 8: ...the rear panel CAUTION The IO or AO COM is NOT isolated from the other COM connections Current Output Option IO The current output is 4 to 20 mA This output is a current sink and requires a source vol...

Отзывы: