background image

Page 2

 

 
 

damped, to suppress high frequency noise.  It is always a good idea to use shielded cable for input signals and ensure the 
shield is properly grounded.  

NOTE:

 

The common on the inputs is 

NOT

 a ground.

 

Another  source  of  noise  is  spikes  generated  by  the  alarm  relay  contacts.    It  may  be  necessary  to  suppress  the  contacts 
externally.  This is particularly true when the internal relays switch other external relays that do not have spike suppression.  
Always ensure that all sources of spikes or noise are adequately suppressed from the environment. 

2.2 

Adjustments 

Since the instruments are crystal controlled, there are no user calibration adjustments.  Any of the programmable parameters, 
such as scaling, limits, analog out, and so on must be set up using the menu options. 

2.3 

Connections 

All connections are via the rear panel of the instrument – power, sensors, alarms, analog output, and communication. The 
rear panel is shown below and may vary slightly depending on what options are in the unit. 

 

Figure 2  ACT-3X Rear panel with Analog Output and USB Option 

2.3.1

 

Power Connections 

Power  to  the  unit  is  connected  to  the  terminals  under  the  sections  labeled 

POWER

  on  the  rear  panel.    Be  sure  the 

power supplied matches the specification indicated on the rear panel.  Refer to 

Figure 2

 above. 

If  the  unit  is 

ac  powered 

(115  -  230  Vac),  connect  the  Live  (Hot)  wire  to  the  terminal  marked 

and  the  Neutral 

(Return) wire to the terminal marked 

N

.  

NOTE:

  The  ground  connection  is  not  required  as  the  unit  is  fully  isolated 

from the mains.  

If  the  unit  is 

dc  powered

, connect the dc supply Positive to the terminal  marked ―

+

‖ and the dc supply Negative or 

Common to the terminal marked ―

-

‖.  

CAUTION: 

Ensure the dc voltage does not exceed the rating on the unit (12V 

±10% or 24V ±10% as marked). 

2.3.2

 

Sensor Connections 

A speed sensor (not included) can be connected to the terminals under the section labeled 

IN 

on the rear panel.  Refer 

to Figure

2

 an

3

Connections and their functions are as follows: 

+V(A) 

Positive  Supply  Output.    Used  to  provide  power  to  optical,  laser,  infrared  or  amplified  magnetic  sensors.  
Voltage out is +24Vdc, +12Vdc or +5Vdc (factory selected).  Maximum load is 30mA from the 24V supply 
or 60mA from the 5 or 12V supplies.   

PX+ 

This  output  is  for  use  with  two wire  proximity  sensors.    It  has  internal  current  sensing. Maximum  load  for 
proper operation with two wire sensors is 20 mA. 

SIG 

Signal Input.  Positive input signal from the speed sensor.   Accepts TTL pulses or ac signals, unipolar and 
bipolar, from 1.1 Vac to 50 Vac.  Connect the signal wire from three wire sensors or the positive side of two 
wire magnetic sensors to this terminal. Typical input impedance is 10 Kohms. 

COM 

Common or Negative Terminal.  Common or Negative connection for both signal and power. 

Refer to 

Figure 3

 on the following page for connection of Monarch standard sensors. The connections are typical for 

these types of sensors. 

Содержание ACT-3X

Страница 1: ...Totalizer Ratemeter User Manual and Reference Guide MONARCH INSTRUMENT 15 Columbia Drive Amherst NH 03031 USA Phone 603 883 3390 Fax 603 886 3300 E mail support monarchinstrument com Website www mona...

Страница 2: ...e personal injury or death may occur as a result 7 This instrument may not be safe for use in certain hazardous environments and serious personal injury or death could occur as a result of improper us...

Страница 3: ...4 3 2 3 UP and DOWN BUTTONS 5 3 2 4 RECALL BUTTON 5 4 0 OPERATION 5 4 1 Modes of Operation Channel 1 5 4 1 1 RPM Mode 5 4 1 2 Frequency Mode 5 4 1 3 Scale Mode Ratemeter 5 4 1 4 Single Event Capture S...

Страница 4: ...5 9 11 5 10 11 5 11 12 5 12 12 6 0 SERIAL OUTPUT 12 6 1 Data from the Serial Interface 12 6 2 Serial Commands 12 6 2 1 Run Mode Commands 12 6 2 2 Control Commands 13 7 0 SPECIFICATIONS 14 8 0 OPTIONS...

Страница 5: ...xed equipment or permanently connected If permanently connected disconnection from the supply must be possible via a customer supplied switch or circuit breaker rated at 120V or 240V dependent on loca...

Страница 6: ...ve Hot wire to the terminal marked L and the Neutral Return wire to the terminal marked N NOTE The ground connection is not required as the unit is fully isolated from the mains If the unit is dc powe...

Страница 7: ...nput is also referred to as Channel 2 CH 2 and will accept a TTL input or any signal up to 12Vdc It has a weak pull up internally and can be used with a set of potential free contacts The AUX input is...

Страница 8: ...is another input pulse It is more useful at slow speeds as it appears to be on continuously at higher inputs It gives an indication that a valid input trigger signal is present 3 1 3 MAX and MIN LEDS...

Страница 9: ...1 2 Frequency Mode In the Frequency Mode the unit displays input pulses per second or more commonly Hertz Hz This is the most basic mode of operation The range of measurement in this mode is 0 0833 t...

Страница 10: ...nding on the sense programmed It acts as a gate preventing the input signal from updating the unit 4 2 3 Single Event Capture When programmed as Single Event Capture this input acts as the second inpu...

Страница 11: ...become de energized Thus in the event of a power failure the relays will drop out by default creating the equivalent of an alarm condition 4 5 Analog AO and Current IO Output The ACT 3X has options f...

Страница 12: ...or 14 640 RPM the internal update rate is the period of the input frequency Thus the response of the alarms etc can be seen to be a function of the input Above an input of 244 Hz the alarms respond wi...

Страница 13: ...d scale factor Press RECALL to exit up one level without making a change or press SET to save the change The edit buttons function as follows RESET changes the digit being edited blinking digit UP inc...

Страница 14: ...EGative or POSitive Press the SET button to select the new setting or the RECALL button to exit without saving the settings 5 3 Sets the decimal point on the displayed reading To enter this menu item...

Страница 15: ...a change or press SET to save the change 5 6 2 FULL SCALE Sets the Full Scale value for the Analog output Press the SET button and use the buttons to edit the value as per above Press RECALL to exit u...

Страница 16: ...ent occurs Other information is sent on demand and is covered in the following section The messages are sent as standard ASCII and all messages end with a carriage return CR There is no Line feed sent...

Страница 17: ...mand Category Argument Value eg CH_1 TYPE SCALE 60 0 sets the Scale Mode Scale factor to 60 0 Command Argument eg DECPT NONE sets the Decimal Point to none Command Category Argument Action CH_1 Channe...

Страница 18: ...100 times per second Standard Gate or up to 1000 Fast Gate Dependent on input frequency Input must be measurement rate Scale Mode Scaling Computation Programmable scaling 0 0001 to 99 999 Front panel...

Страница 19: ...preadsheet Software available for download at www monarchinstrument com ROLS W Remote Optical Laser Sensor with 8 foot cable ROS W Remote Optical Sensor with 8 foot cable ROS P 25 Remote Optical Senso...

Страница 20: ...ing the circumference of the shaft you are monitoring This could also be a speed wheel tire etc The circumference x diameter 3 14159 In order to scale we need to know what we want as opposed to what w...

Страница 21: ...il the display shows and then press the SET button The display will show the current scale factor value with the right most digit flashing The UP and DOWN buttons change the flashing digit The RESET b...

Страница 22: ...an error in the placement of the sensors The tape edges won t be exactly 1 inch apart Assuming the edges were really 1 01 inches apart there would be 1 error So at 130 MPH your reading would be 128 7...

Страница 23: ...hat the device is set up for DHCP by default so it will get an IP address from your local server Once the search is complete the window will be populated as shown next The current device setting is sh...

Страница 24: ...ons to set the required value Press RECALL to exit up one level without making a change or press SET to make the change The edit buttons function as follows RESET changes the digit being edited blinki...

Отзывы: