Parameterisation manual
Manual No.:
MWF-PA102
Microwave level measurement
MWF
Index
0
Date
08.08.18
Adaption of parameters with the MWF2-KIT
Page 9 of 9
4.3 Signal image with weak signal without indication of filling level.
A weak signal is indicated at approx. 1850mm, but no filling level is indicated or the filling level indication
varies.
There are two potential reasons for such a situation:
Reason 1:
The signal is generated by a disturbing installation in
an empty silo
.
Action:
Step back to register
Basic configuration
and follow the instructions in
chapter “
Line 20 and 22
– Setting of disturbance signal suppression
“.
Reason 2:
The signal is generated by the bulk solids surface, but the value for the parameter
amplitude threshold is too high.
Action:
Step back to register
Basic configuration
and follow the instructions in
chapter “
Line 16 and 17 - Adjustment of the sensitivity
“.