Parameterisation manual
Manual No.:
MWF-PA102
Microwave level measurement
MWF
Index
0
Date
08.08.18
Adaption of parameters with the MWF2-KIT
Page 6 of 9
Line 23 and 24
No input
Type of probe has to be
„
1
“. Please don´t do any changes!
Line 25 and 26
Adjustment of probe length [L]
If the probe has been shortened or another probe with a different rope length has been mounted, the
probe length
[L]
has to be adjusted.
1.
Insert in
line 25
the value of the probe length
[L]
in mm, measured from the reference point
[R]
.
Attention!!!
After shortening the probe, it could be necessary to adapt the value for the lower
measuring limit in
line 2
as well.
Line 27
Reset to MOLLET factory settings
Click on
START
in
line 27
and the
MWF will be reset to MOLLET factory settings.
All individual parameter settings will be overwritten with the primary MOLLET factory settings.
Line 28
Measuring of filling level
Click on
START
in
line 28
and the actual filling level will be scanned. The scanned value corresponds to
the length at the probe in mm, measured from the reference point [R].
Line 31 and 32
Recording of signal image
1.
Insert in
line 32
, in the lower, orange colored field the value of the probe length
[L]
in mm + 1000
mm rounded up to x000 and click on
ADJUST
.
Example: probe length 8600 mm, please insert value 10000.
2.
Click on
START
in
line 31
and the recording of the signal image will be started. The duration of the
recording is dependent on the probe length and can last up to 4 minutes.
3.
Recording of signal image is finished as soon as
„ok“ is permanent shown in the field
status
. Now
the signal image can be viewed in the register
Signal
.