Parameterisation manual 

Manual No.: 

MWF-PA102 

Microwave level measurement 

MWF

 

Index

    

0

 

Date 

08.08.18

 

Adaption of parameters with the MWF2-KIT

 

Page 6 of 9

 

 

Line 23 and 24 

No input 

 

Type of probe has to be 

1

“. Please don´t do any changes! 

 

Line 25 and 26 

Adjustment of probe length [L] 

 

If the probe has been shortened or another probe with a different rope length has been mounted, the 
probe length 

[L]

 has to be adjusted. 

 

1. 

Insert in 

line 25

 the value of the probe length 

[L]

 in mm, measured from the reference point 

[R]

 

Attention!!!

 

After shortening the probe, it could be necessary to adapt the value for the lower 
measuring limit in 

line 2

 as well.  

 

Line 27 

Reset to MOLLET factory settings 

 

Click on 

START

 in 

line 27 

and the

 

MWF will be reset to MOLLET factory settings.  

All individual parameter settings will be overwritten with the primary MOLLET factory settings.  

 

Line 28 

Measuring of filling level 

 

Click on 

START

 in 

line 28 

and the actual filling level will be scanned. The scanned value corresponds to 

the length at the probe in mm, measured from the reference point [R]. 

 

Line 31 and 32 

Recording of signal image 

 

1. 

Insert in 

line 32

, in the lower, orange colored field the value of the probe length 

[L]

 in mm + 1000 

mm rounded up to x000 and click on 

ADJUST

.  

Example: probe length 8600 mm, please insert value 10000. 

 

2. 

Click on 

START

 in 

line 31 

and the recording of the signal image will be started. The duration of the 

recording is dependent on the probe length and can last up to 4 minutes.  

 

3. 

Recording of signal image is finished as soon as 

„ok“ is permanent shown in the field 

status

. Now 

the signal image can be viewed in the register 

Signal

.  

 

 
 

 

Содержание MOLOSwave MWF2-KIT

Страница 1: ...arameterisation manual Manual No MWF PA102 Microwave level measurement MWF Index 0 Date 08 08 18 Adaption of parameters with the MWF2 KIT Page 1 of 9 HART modem with mA display Parameterisation manual...

Страница 2: ...2 of 9 1 Preparation Requirements MOLLET MWF2 KIT a Laptop or PC with Microsoft Windows 7 8 10 and Excel The MOLLET MWF2 KIT consists of 1 MWF HART D2 modem with mA display see first page 1 measuring...

Страница 3: ...suring value display or control device 4 Connect the loosened wire with the crocodile clip of the measuring wire B 5 Put both plugs of the measuring wires A and B into the sockets A and B at the front...

Страница 4: ...T D2 modem for monitoring the current output 4 20 mA This is done by pressing the red button for switching on the display After that you can read the actual measured value filling level 2 2 Parameteri...

Страница 5: ...ive and the amplitude threshold has to be increased In case of no signal in a filled up silo the MWF is too insensitive and the amplitude threshold has to be decreased Line 18 and 19 Setting of noise...

Страница 6: ...F will be reset to MOLLET factory settings All individual parameter settings will be overwritten with the primary MOLLET factory settings Line 28 Measuring of filling level Click on START in line 28 a...

Страница 7: ...click READ Line 11 Read out lower point of the switching output uSA click READ Line 13 Read out upper point of the switching output oSA click READ Line 15 Read out upper dead band TB click READ Line...

Страница 8: ...4 Signal images Examples of signal images useful for comparison with recorded signal images from you 4 1 Signal image of an empty silo Wave runs through without any significant signal up to the tensio...

Страница 9: ...s There are two potential reasons for such a situation Reason 1 The signal is generated by a disturbing installation in an empty silo Action Step back to register Basic configuration and follow the in...

Отзывы: