background image

Geräte montieren

21

05/05 AWB2300-1527D/GB

Geräte montieren

Die Motorschutzrelais ZB12 und ZB32 können direkt am 
Schütz montiert werden.

Das ZB32 kann zusätzlich in Kombination mit der Einzelauf-
stellung einzeln eingesetzt werden.

Tabelle 5:

Direktanbau

Tabelle 6:

Einzelaufstellung

X

Montieren Sie die Geräte wie in den nachfolgenden 
Abbildungen angegeben.

Abbildung 8: Montage ZB12, ZB32

Schütz

Motorschutzrelais

DILM7, DILM9, DILM12, DILM15

ZB12-...

DILM17, DILM25, DILM32

ZB32-...

Motorschutzrelais

Einzelaufstellung

ZB32-...

ZB32-XEZ

ZB32-XEZ

ZB32

ZB12, ZB32

Содержание ZB12 Series

Страница 1: ... Bonn E Mail info moeller net Internet www moeller net 2002 by Moeller GmbH Subjekt to alteration AWB2300 1527D GB Doku Doku Eb 05 05 Printed in the Federal Republic of Germany 0x 05 Article No 284910 4 patpks v y Rückentext Hardware und Projektierung Hardware and Engineering 05 05 AWB2300 1527D GB A A A Think future Switch to green Think future Switch to green Rückenbreite bis 10 mm 1 Blatt 0 106...

Страница 2: ...gt oder verbreitet werden Änderungen vorbehalten Gedruckt auf Papier aus chlor und säurefrei gebleichtem Zellstoff All brand and product names are trademarks or registered trademarks of the owner concerned 1st published 2004 edition date 02 04 2nd edition 05 2005 See revision protocol in the About this manual chapter Moeller GmbH Bonn Author Wolfgang Nitschky Editor Heidrun Riege Translator David ...

Страница 3: ... nur im eingebauten Zustand betrieben und bedient werden Before commencing the installation Disconnect the power supply of the device Ensure relosing interlock that devices cannot be accidentally restarted Verify isolation from the supply Connect to earth and short circuit Cover or fence off neighbouring live parts Follow the installation instructions AWA included with the device Only suitably qua...

Страница 4: ... 05 AWB2300 1527D GB Motorschutzrelais ZB12 und ZB32 Überlastüberwachung von EEx e Motoren 1 ZB12 and ZB32 motor protective relays Overload monitoring of EEx e motors 27 Anhang Appendix 53 Überblick Overview ...

Страница 5: ... Strombereiche der Motorschutzrelais 7 Temperaturkompensation 9 Phasenausfall 9 Wiedereinschaltung 10 Testfunktion 11 2 Projektierung 13 Überlastüberwachung von Motoren im EEx e Bereich 13 Einstellung der Überstromschutzeinrichtung 13 Kurzschlussschutz der Motorschutzrelais 14 Zulassungen 17 3 Installation 19 Hinweise zur Installation 19 Geräte montieren 21 4 Geräte betreiben 25 Einstellungen 25 R...

Страница 6: ...B12 0 16 und and ZB32 0 16 56 ZB12 0 24 und and ZB32 0 24 58 ZB12 0 4 und and ZB32 0 4 60 ZB12 0 6 und and ZB32 0 6 62 ZB12 1 und and ZB32 1 64 ZB12 1 6 und and ZB32 1 6 66 ZB12 2 4 und and ZB32 2 4 68 ZB12 4 und and ZB32 4 70 ZB12 6 und and ZB32 6 72 ZB12 10 und and ZB32 10 74 ZB12 12 76 ZB12 16 78 ZB32 16 80 ZB32 24 82 ZB32 32 84 Konformitätserklärung Declaration of Conformity 86 ...

Страница 7: ... und wartet Abkürzungen und Symbole In diesem Handbuch werden Abkürzungen und Symbole eingesetzt die folgende Bedeutung haben X zeigt Handlungsanweisungen an EEx e Zündschutzart Erhöhte Sicherheit PTB Physikalisch Technische Bundesanstalt Zerti fizierungsstelle für Geräte im EEx Bereich NM Niedrigster möglicher Einstellstrom HM Höchster möglicher Einstellstrom h macht Sie aufmerksam auf interessan...

Страница 8: ...ende Änderungsprotokoll j Warnung warnt vor schweren Sachschäden und schweren Verletzungen oder Tod Redaktions datum Seite Stichwort neu Ände rung ent fällt 05 05 6 Abschnitt Direktanbau j 8 Tabelle 1 Strombereiche ZB12 Relais j 9 Abschnitt Temperaturkompensation j 15 Tabelle 3 ZB12 in Direktanbau j 16 Tabelle 4 ZB32 in Direktanbau oder Einzelaufstellung j 21 Tabelle 5 Direktanbau j 54 Tabelle 9 W...

Страница 9: ...Funken und Lichtbögen an Motoren bei denen dies im normalen Betrieb nicht auftritt verhindert Die Motorschutzgeräte hierfür die sich selber nicht im EEx e Bereich befinden müssen durch eine akkreditierte Zulassungsstelle zertifiziert sein Die Richtlinie 94 9 EG ATEX 100a zur Angleichung der Rechtsvorschriften der Mitgliedsstaaten für Geräte und Schutzsysteme zur bestimmungsmäßigen Verwendung in ex...

Страница 10: ...ZB12 und ZB32 sind als Direktanbau an die Schütze DIL einsetzbar Direktanbau Zusätzlich ist das Relais ZB32 in Kombination mit einer Einzelaufstellung einzeln einsetzbar Einzelaufstellung Bei einer Überlastauslösung schalten die Hilfsschalter 95 96 und 97 98 um und unterbrechen den Steuerstromkreis des zugehörigen Leistungsschützes Sie schalten so indirekt den Stromfluss des zu überwachenden Motor...

Страница 11: ...ütz M1 Motor Strombereiche der Motorschutzrelais Die Z Relais werden mit Hilfe einer Strom Einstellscheibe auf den Motornennstrom eingestellt Mit verschiedenen Typen können Motoren von 0 1 bis 32 A Motornennstrom überwacht werden M1 M U V W F2 F1 L1 L2 L3 Q11 2 4 6 2 4 6 97 97 95 96 1 3 5 PE 3 L1 Q11 1 95 96 21 22 13 14 F2 0 S11 I 13 14 Q11 A1 A2 Q11 N F0 ...

Страница 12: ... ZB12 1 0 0 6 bis 1 0 ZB12 1 6 1 0 bis 1 6 ZB12 2 4 1 6 bis 2 4 ZB12 4 2 4 bis 4 0 ZB12 6 4 0 bis 6 0 ZB12 10 6 0 bis 10 ZB12 12 9 bis 12 ZB12 16 12 bis 16 Typ Strombereich I A ZB32 0 16 0 1 bis 0 16 ZB32 0 24 0 16 bis 0 24 ZB32 0 4 0 24 bis 0 4 ZB32 0 6 0 4 bis 0 6 ZB32 1 0 0 6 bis 1 0 ZB32 1 6 1 0 bis 1 6 ZB32 2 4 1 6 bis 2 4 ZB32 4 2 4 bis 4 0 ZB32 6 4 0 bis 6 0 ZB32 10 6 0 bis 10 ZB32 16 10 bi...

Страница 13: ...d ZB32 sind phasenausfallemp findlich Die Auslenkung aller drei Bimetalle wirkt auf eine Auslösebrücke die bei Erreichen des Grenzwertes einen Sprungschalter umschaltet Gleichzeitig verschieben alle drei Bimetalle die Differenzialbrücke Wird bei einem Phasenaus fall ein Bimetall weniger ausgelenkt bleibt die Differential brücke zurück und der Weg wird in zusätzlichen Auslöseweg umgewandelt so dass...

Страница 14: ...In der Stellung Automatik fallen die Kontakte nach der Abkühlung der Bimetalle automatisch zurück in der Hand stellung muss die Auslösung vor Ort am Motorschutzrelais quittiert werden h Soll mit einem ZB12 oder ZB32 Relais ein Wechselstrom motor oder ein Gleichstrommotor überwacht werden muss der Strom über alle drei Strombahnen geführt werden um Frühauslösungen zu vermeiden j Warnung Für den Expl...

Страница 15: ...taste öffnet den Öffner 95 96 Nach dem Loslassen fällt der Öffner wieder zurück Diese Funktion kann zum manuellen Ausschalten des Motors genutzt werden Das Ziehen der Testtaste führt zur Auslösung des Motor schutzrelais Der Öffner 95 96 öffnet und der Schließer 97 98 schließt Nach dem Loslassen der Testtaste muss das Motorschutzrelais wie nach einer Auslösung zurück gesetzt werden a Abschnitt Wied...

Страница 16: ...12 05 05 AWB2300 1527D GB ...

Страница 17: ... jedoch noch nicht sicher Sie erlangen die Explosionssicherheit erst durch zusätzliche Maßnahmen bei der Installation durch zweckentsprechende Auswahl und Einsatzbedingungen PTB Prüfregeln u a durch das Zusammenschalten mit einer richtig bemessenen und eingestellten Überstromschutzeinrichtung Einstellung der Über stromschutzeinrichtung j Warnung Die stromabhängige Schutzeinrichtung muss so ausge w...

Страница 18: ...otorschutzrelais Der Kurzschlussschutz der Motorschutzrelais wird durch Sicherungen realisiert Bei Direktanbau an ein Schütz wird die Vorsicherung des Schützes für die entsprechende Zuord nungsart mit berücksichtigt 1 0 1 0 2 0 4 0 6 0 8 1 2 4 6 8 10 20 40 1 2 4 6 8 10 2 3 4 5 6 7 8 9 10 J min s N 1 i Vorsicht Zum Schutz von EEx e Motoren ist nur die Zuordnungsart 2 zulässig ...

Страница 19: ...nbau Schütz Sicherung gG gL A Bemessungs Zuordnungsart 1 1 Zuordnungsart 2 1 kurzschlussstrom Iq kA ZB12 0 16 DILM7 DILM9 DILM12 DILM15 25 0 5 100 ZB12 0 24 1 ZB12 0 4 2 ZB12 0 6 4 ZB12 1 0 4 ZB12 1 6 6 ZB12 2 4 10 ZB12 4 16 ZB12 6 20 ZB12 10 50 25 ZB12 12 50 25 ZB12 16 50 25 1 nach IEC EN 60947 ...

Страница 20: ...tz Sicherung gG gL A Bemessungs Zuordnungsart 1 1 Zuordnungsart 2 1 kurzschlussstrom Iq kA ZB32 0 16 DILM17 DILM25 DILM32 25 0 5 100 ZB32 0 24 1 ZB32 0 4 2 ZB32 0 6 4 ZB32 1 0 4 ZB32 1 6 6 ZB32 2 4 10 ZB32 4 16 ZB32 6 20 ZB32 10 50 25 ZB32 16 63 35 ZB32 24 100 35 ZB32 32 125 63 1 nach IEC EN 60947 ...

Страница 21: ...EG ATEX 100a zum Schutz von EEx e Motoren Außerdem können nach EN 50281 1 1 und EN 50281 1 2 Motoren in den Zonen 21 und 22 Bereiche mit brennbarem Staub geschützt werden Die Motorabgangsverdrahtung ist nach IEC EN 60947 1 Tabelle 9 auszuführen ZB12 PTB 04 ATEX 3022 ZB32 PTB 04 ATEX 3022 Die Relais sind nach UL und CSA für die USA und Kanada approbiert Weitere Approbationen bestehen für c U s Chin...

Страница 22: ...18 05 05 AWB2300 1527D GB ...

Страница 23: ...chutz ist nur ein manuelles Rück setzen Einschalten nach Abkühlung der Bimetalle oder ein automatisches Zuschalten über eine Steuerungsverriege lung zum Motor bzw zur elektrischen Maschine zulässig Rücksetzungen dürfen manuell vor Ort oder durch geschultes Personal in der Leitwarte vorgenommen werden j Warnung Insbesondere darf bei EEx e Anwendungen nach Ausfall der Steuerspannung und Spannungsrüc...

Страница 24: ...ederanlauf F1 Sicherung F2 Motorschutzrelais K1M Leistungsschütz M1 Motor Die Selbsthaltung des Leistungsschützes K1M verhindert einen automatischen Wiederanlauf M1 M U V W F2 F1 L1 L2 L3 Q11 2 4 6 2 4 6 97 97 95 96 1 3 5 PE 3 L1 Q11 1 95 96 21 22 13 14 F2 0 S11 I 13 14 Q11 A1 A2 Q11 N F0 ...

Страница 25: ...ination mit der Einzelauf stellung einzeln eingesetzt werden Tabelle 5 Direktanbau Tabelle 6 Einzelaufstellung X Montieren Sie die Geräte wie in den nachfolgenden Abbildungen angegeben Abbildung 8 Montage ZB12 ZB32 Schütz Motorschutzrelais DILM7 DILM9 DILM12 DILM15 ZB12 DILM17 DILM25 DILM32 ZB32 Motorschutzrelais Einzelaufstellung ZB32 ZB32 XEZ ZB32 XEZ ZB32 ZB12 ZB32 ...

Страница 26: ...auf einer Hutschiene oder direkt auf der Montageplatte montiert werden Tabelle 7 Maße zur Montage X Verdrahten Sie die Motorleitungen Abbildung 9 Hauptstromverdrahtung Folgende Leitungsquerschnitte sind möglich ZB32 XEZ Bohrmaße B x H mm 35 x 75 Schraube mm 2 x M4 x 12 1h H 3 ...

Страница 27: ...hnen Hilfsstrom bahnen ZB12 ZB32 95 96 97 98 1 x 1 6 1 x 1 6 1 x 0 75 4 mm2 2 x 1 6 2 x 1 6 2 x 0 75 4 1 1 x 1 6 1 x 1 6 1x 0 75 2 5 mm2 2 x 1 6 2 x 1 6 2x 0 75 2 5 AWG 1 x 14 8 1 x 14 8 1 x 18 12 2 x 14 8 2 x 14 8 2 x 18 12 Anzugsdreh moment Nm 1 8 1 8 1 2 1 Aderendhülse nach DIN 46228 ...

Страница 28: ...24 05 05 AWB2300 1527D GB ...

Страница 29: ...uf A und einer Handrücksetzung H zu wählen Abbildung 10 Schaltmöglichkeiten mit Wahlknopf Reset Die Stellung H verhindert einen automatischen Wiederan lauf und ist werksseitig bei den Motorschutzrelais vorge wählt In der Stellung H muss das Relais nach einer Auslösung händisch durch Drücken dieses Wahlknopfes zurückgesetzt werden i Vorsicht Bei einem kühlen Aufstellungsort des Motorschutzrelais z ...

Страница 30: ...aste Test Ein Drücken der Taste hat das Öffnen des Hilfskontaktes 95 96 zur Folge und kann zum Abschalten des Schützes genutzt werden Im stromlosen Zustand kann durch das Drücken der Taste die Funktion beider Hilfsschalter getestet werden TEST NC 95 NC 96 NO 97 NO 98 OFF j Warnung Funktionsuntüchtige Geräte dürfen nicht geöffnet und repariert werden Sie müssen von Fachpersonal ausge tauscht werden...

Страница 31: ...lic release 32 Current ranges of the motor protective relays 33 Temperature compensation 35 Phase loss 35 Reset 36 Test function 37 2 Configuration 39 Monitoring overload of motors in the EEx e area 39 Adjusting the overload current protection 39 Short circuit protection of the motor protective relays 40 Approvals 43 3 Installation 45 Notes on installation 45 Mounting the devices 47 4 Operating th...

Страница 32: ... ZB12 0 16 und and ZB32 0 16 56 ZB12 0 24 und and ZB32 0 24 58 ZB12 0 4 und and ZB32 0 4 60 ZB12 0 6 und and ZB32 0 6 62 ZB12 1 und and ZB32 1 64 ZB12 1 6 und and ZB32 1 6 66 ZB12 2 4 und and ZB32 2 4 68 ZB12 4 und and ZB32 4 70 ZB12 6 und and ZB32 6 72 ZB12 10 und and ZB32 10 74 ZB12 12 76 ZB12 16 78 ZB32 16 80 ZB32 24 82 ZB32 32 84 Konformitätserklärung Declaration of Conformity 86 ...

Страница 33: ...used in this manual have the following meaning X indicates actions to be taken EEx e Increased safety type of protection PTB Physikalisch Technische Bundesanstalt German Federal Testing Laboratory Accredited certification authority for devices operated in EEx e areas NM Lowest possible setup current HM Highest possible setup current h Draws our attention towards interesting tips and additional inf...

Страница 34: ...a chapter Modification index j Warning Warns of the risk of heavy material damage and of serious or lethal injury Edition date Page Subject New Modi fied Omitted 05 05 32 section Direct mounting j 34 table 1 ZB12 relay current ranges j 35 section Temperature compensation j 41 table 3 ZB12 direct mounting j 42 table 4 Direct mounting or individual installation of the ZB32 j 47 table 5 Direct mounti...

Страница 35: ... which usually does not occur under normal operating conditions The motor protective equipment used for this is operated at a location separate from the EEx e area and must be certified by an accredited certification authority The guidelines on the application of Directive 94 9 EC ATEX 100a on the approximation of the laws of the Member States concerning equipment and protective systems intended f...

Страница 36: ...AC current The ZB12 and ZB32 overload relays can be mounted directly on the DIL contactors Direct mounting Furthermore the ZB32 relay can be used individually in combination with an individual mounting Individual mounting In the event of overload tripping the auxiliary contacts 95 96 and 97 98 change over and disconnect the control voltage circuit from the corresponding contactor relay and Motor p...

Страница 37: ...or protective relay K1M Motor contactor M1 Motor Current ranges of the motor protective relays The rated motor current is set on the Z relays by means of a current setting dial The various types can be used to monitor motors operating at a rated current of 0 1 to 32 A M1 M U V W F2 F1 L1 L2 L3 Q11 2 4 6 2 4 6 97 97 95 96 1 3 5 PE 3 L1 Q11 1 95 96 21 22 13 14 F2 0 S11 I 13 14 Q11 A1 A2 Q11 N F0 ...

Страница 38: ... to 0 6 ZB12 1 0 0 6 to 1 0 ZB12 1 6 1 0 to 1 6 ZB12 2 4 1 6 to 2 4 ZB12 4 2 4 to 4 0 ZB12 6 4 0 to 6 0 ZB12 10 6 0 to 10 ZB12 12 9 to 12 ZB12 16 12 to 16 Type Current range I A ZB32 0 16 0 1 to 0 16 ZB32 0 24 0 16 to 0 24 ZB32 0 4 0 24 to 0 4 ZB32 0 6 0 4 to 0 6 ZB32 1 0 0 6 to 1 0 ZB32 1 6 1 0 to 1 6 ZB32 2 4 1 6 to 2 4 ZB32 4 2 4 to 4 0 ZB32 6 4 0 to 6 0 ZB32 10 6 0 to 10 ZB32 16 10 to 16 ZB32 ...

Страница 39: ...he deflecting action of all three bimetallic releases is directed towards a tripping bridge that switches over a quick break switch when the limit value is reached At the same time all three bimetallic releases shift the differential bridge If the path of action of one of the bimetallic releases is reduced due to a phase loss the differential bridge is retarded and the distance is converted into a...

Страница 40: ...tacts automatically fall back after the bimetallic releases have cooled down whereas in manual mode the tripping must be acknowledged locally on the motor protective relay h When a ZB12 or ZB32 relay is to be used for monitoring an AC or DC motor the current must flow across all three current paths in order to avoid early tripping j Warning To ensure explosion proof operation the motor protective ...

Страница 41: ...act NC 95 96 The open contact will return to the closed position as soon as the button is released This function can also be used to switch off the motor manually Pulling the button will trip the motor protective relay The break contact 95 96 opens and the make contact 97 98 closes After the test button is released the motor protective relay must be reset in the same way as after a normal tripping...

Страница 42: ...38 05 05 AWB2300 1527D GB ...

Страница 43: ...er since EEx e motors are not intrinsically safe explosion safety is only achieved by taking special measures during installation and by selecting appropriate operating conditions PTB testing regulations e g by a combination of the circuit with a correctly rated and set overload current protection Adjusting the overload current protection j Warning The selected current overload protection system m...

Страница 44: ...ective relays The motor protective relays are short circuit protected by means of fuses When the relay is mounted directly onto a contactor relay the corresponding primary fuse of the contactor relay is taken into account accordingly 1 0 1 0 2 0 4 0 6 0 8 1 2 4 6 8 10 20 40 1 2 4 6 8 10 2 3 4 5 6 7 8 9 10 J min s N 1 i Caution Only co ordination type 2 is permissible for the protection of EEx e mo...

Страница 45: ...ntactor relay Fuse gG gL A Rated short circuit Type of assignment 1 1 Type of assignment 2 1 current Iq kA ZB12 0 16 DILM7 DILM9 DILM12 DILM15 25 0 5 100 ZB12 0 24 1 ZB12 0 4 2 ZB12 0 6 4 ZB12 1 0 4 ZB12 1 6 6 ZB12 2 4 10 ZB12 4 16 ZB12 6 20 ZB12 10 50 25 ZB12 12 50 25 ZB12 16 50 25 1 to IEC EN 60947 ...

Страница 46: ...of the ZB32 Contactor relay Fuse gG gL A Type of assignment 1 1 Type of assignment 2 1 ZB32 0 16 DILM17 DILM25 DILM32 25 0 5 100 ZB32 0 24 1 ZB32 0 4 2 ZB32 0 6 4 ZB32 1 0 4 ZB32 1 6 6 ZB32 2 4 10 ZB32 4 16 ZB32 6 20 ZB32 10 50 25 ZB32 16 63 35 ZB32 24 100 35 ZB32 32 125 63 1 to IEC EN 60947 ...

Страница 47: ...0a directive for the protection of EEx e motors Furthermore motors in zones 21 and 22 areas with combustible dusts can be protected conform to EN 50281 1 1 and EN 50281 1 2 The motor outgoer wiring must be implemented conform to IEC EN 60947 1 table 9 ZB12 PTB 04 ATEX 3022 ZB32 PTB 04 ATEX 3022 The relays are approved by UL and CSA for the USA and Canada Further approvals exist for c U s China 010...

Страница 48: ...44 05 05 AWB2300 1527D GB ...

Страница 49: ... operation the motor protective relay may only be reset switched on manually or automatically via a control interlock circuit for the motor or electrical machinery after the bimetallic release has cooled down A manual reset may be carried out by trained personnel locally or in the control room j Warning Particularly in EEx e applications an automatic restart must be prevented after an interruption...

Страница 50: ...ic restart F1 Fuse F2 Motor protective relay K1M Contactor relay M1 Motor The latching function of the K1M contactor relay prevents an automatic restart M1 M U V W F2 F1 L1 L2 L3 Q11 2 4 6 2 4 6 97 97 95 96 1 3 5 PE 3 L1 Q11 1 95 96 21 22 13 14 F2 0 S11 I 13 14 Q11 A1 A2 Q11 N F0 ...

Страница 51: ...ally be used in combination with an individual mounting Table 5 Direct mounting Table 6 Individual installation X Mount the devices as shown in the figures below Figure 8 Mounting ZB12 ZB32 Contactor relay Motor protective relay DILM7 DILM9 DILM12 DILM15 ZB12 DILM17 DILM25 DILM32 ZB32 Motor protective relay Individual mounting ZB32 ZB32 XEZ ZB32 XEZ ZB32 ZB12 ZB32 ...

Страница 52: ...B32 XEZ can be mounted on a top hat rail or directly on a mounting plate Table 7 Mounting dimensions X Wire the motor cables Figure 9 Mains wiring The following conductor cross sections can be used ZB32 XEZ Bore dimensions W x H mm 35 x 75 Screw mm 2 x M4 x 12 1h H 3 ...

Страница 53: ...rcuit Auxiliary voltage circuit ZB12 ZB32 95 96 97 98 1 x 1 6 1 x 1 6 1 x 0 75 4 mm2 2 x 1 6 2 x 1 6 2 x 0 75 4 1 1 x 1 6 1 x 1 6 1x 0 75 2 5 mm2 2 x 1 6 2 x 1 6 2x 0 75 2 5 AWG 1 x 14 8 1 x 14 8 1 x 18 12 2 x 14 8 2 x 14 8 2 x 18 12 Tightening torque N m 1 8 1 8 1 2 1 Ferrule to DIN 46228 ...

Страница 54: ...50 05 05 AWB2300 1527D GB ...

Страница 55: ... of the Reset selector button Figure 10 Switching options of the reset selector button The factory set position H on the motor protective relay prevents automatic restarts In position H the relay must be reset manually after it has tripped by pressing the selector button i Caution If the overload relay is installed at a cool location e g 5 C and the motor is installed at a warm motor location e g ...

Страница 56: ...options of the test button The auxiliary contact 95 96 is opened by pressing the button and can thus be used to switch off the contactor relay The function of both auxiliary contacts can be tested in current less state by pressing the button TEST NC 95 NC 96 NO 97 NO 98 OFF j Warning Faulty devices may not be opened for repairs and may only be replaced suitably qualified personnel ...

Страница 57: ...e zu den jeweiligen Typen sind der nachfolgenden Tabelle 9 zu entnehmen For information on the assignment of values to the relevant types please refer to Tabelle 9 Uimp 6000 V Uimp 6000 V Ith 6 A Ue 690 V h Normal 97 95 98 96 97 95 98 96 Test A F 97 95 98 96 max A gL 1 2 AC 15 Ue 220 240 95 96 Ie 1 5 97 98 Ie 1 5 380 415 500Vh 0 9 0 8 A 0 5 0 5 A IEC EN 60947 C D II 2 GD PTB 04 ATEX 3022 0102 A014...

Страница 58: ...B12 1 6 1 1 6 A 25 6 ZB122 4 1 6 2 4 A 25 10 ZB12 4 2 4 4 A 25 16 ZB12 6 4 6 A 25 20 ZB12 10 6 10 A 50 25 ZB12 12 9 12 A 50 25 ZB12 16 12 16 A 50 25 ZB32 0 16 0 1 0 16 A 25 0 5 ZB32 0 24 0 16 0 24 A 25 1 ZB32 0 4 0 24 0 4 A 25 2 ZB32 0 6 0 4 0 6 A 25 4 ZB32 1 0 6 1 A 25 4 ZB32 1 6 1 1 6 A 25 6 ZB322 4 1 6 2 4 A 25 10 ZB32 4 2 4 4 A 25 16 ZB32 6 4 6 A 25 20 ZB32 10 6 10 A 50 25 ZB32 16 10 16 A 63 3...

Страница 59: ...Auslösekennlinien Tripping characteristics 55 05 05 AWB2300 1527D GB Auslösekennlinien Tripping characteristics ...

Страница 60: ... Range 0 1 0 16 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 23 17 5 21 14 7 2 x I 5 5 4 6 5 2 4 0 ...

Страница 61: ...Auslösekennlinien Tripping characteristics 57 05 05 AWB2300 1527D GB Abbildung Figure 13 ZB12 0 16 und and ZB32 0 16 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Страница 62: ... Range 0 16 0 24 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 21 15 21 13 5 7 2 x I 5 1 4 5 1 3 6 ...

Страница 63: ...Auslösekennlinien Tripping characteristics 59 05 05 AWB2300 1527D GB Abbildung Figure 14 ZB12 0 24 und and ZB32 0 24 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Страница 64: ...ange 0 24 0 4 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 23 5 18 22 13 5 7 2 x I 5 9 4 8 5 5 4 0 ...

Страница 65: ...Auslösekennlinien Tripping characteristics 61 05 05 AWB2300 1527D GB Abbildung Figure 15 ZB12 0 4 und and ZB32 0 4 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Страница 66: ...ange 0 4 0 6 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 27 19 5 25 15 5 7 2 x I 6 5 5 4 6 2 4 6 ...

Страница 67: ...Auslösekennlinien Tripping characteristics 63 05 05 AWB2300 1527D GB Abbildung Figure 16 ZB12 0 6 und and ZB32 0 6 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Страница 68: ...ange 0 6 1 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 29 4 22 26 15 7 2 x I 7 3 5 9 6 5 4 6 ...

Страница 69: ...Auslösekennlinien Tripping characteristics 65 05 05 AWB2300 1527D GB Abbildung Figure 17 ZB12 1 und and ZB32 1 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Страница 70: ...h Range 1 1 6 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 29 20 27 16 7 2 x I 6 9 5 5 6 5 4 4 ...

Страница 71: ...Auslösekennlinien Tripping characteristics 67 05 05 AWB2300 1527D GB Abbildung Figure 18 ZB12 1 6 und and ZB32 1 6 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Страница 72: ...ange 1 6 2 4 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 28 5 19 25 15 3 7 2 x I 6 8 5 3 6 3 4 7 ...

Страница 73: ...Auslösekennlinien Tripping characteristics 69 05 05 AWB2300 1527D GB Abbildung Figure 19 ZB12 2 4 und and ZB32 2 4 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Страница 74: ...nge 2 4 4 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 32 1 24 30 17 9 7 2 x I 7 8 6 5 7 3 5 2 ...

Страница 75: ...Auslösekennlinien Tripping characteristics 71 05 05 AWB2300 1527D GB Abbildung Figure 20 ZB12 4 und and ZB32 4 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Страница 76: ...Range 4 6 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 32 5 24 5 30 19 2 7 2 x I 7 4 6 6 9 5 ...

Страница 77: ...Auslösekennlinien Tripping characteristics 73 05 05 AWB2300 1527D GB Abbildung Figure 21 ZB12 6 und and ZB32 6 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Страница 78: ... Range 6 10 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 33 5 23 7 31 19 7 2 x I 7 5 3 6 2 4 4 ...

Страница 79: ...Auslösekennlinien Tripping characteristics 75 05 05 AWB2300 1527D GB Abbildung Figure 22 ZB12 10 und and ZB32 10 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Страница 80: ... A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 30 7 18 8 27 2 15 7 7 2 x I 6 1 4 1 5 6 3 6 ...

Страница 81: ...Auslösekennlinien Tripping characteristics 77 05 05 AWB2300 1527D GB Abbildung Figure 23 ZB12 12 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Страница 82: ...12 16 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 30 24 29 19 7 2 x I 4 3 3 6 4 1 3 ...

Страница 83: ...Auslösekennlinien Tripping characteristics 79 05 05 AWB2300 1527D GB Abbildung Figure 24 ZB12 16 1 0 1 1 10 100 1000 2 3 4 5 6 7 8 9 10 b c d a ...

Страница 84: ... 16 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 30 22 28 16 4 7 2 x I 4 1 3 2 3 8 2 4 ...

Страница 85: ...Auslösekennlinien Tripping characteristics 81 05 05 AWB2300 1527D GB Abbildung Figure 25 ZB32 16 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Страница 86: ... 24 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 34 5 24 5 30 19 7 2 x I 6 3 4 9 5 6 4 ...

Страница 87: ...Auslösekennlinien Tripping characteristics 83 05 05 AWB2300 1527D GB Abbildung Figure 26 ZB32 24 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Страница 88: ... A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 30 2 21 8 26 6 17 8 7 2 x I 6 1 4 7 5 4 3 9 ...

Страница 89: ...Auslösekennlinien Tripping characteristics 85 05 05 AWB2300 1527D GB Abbildung Figure 27 ZB32 32 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Страница 90: ...Anhang Appendix 86 05 05 AWB2300 1527D GB Konformitätserklärung Declaration of Conformity ...

Страница 91: ... Bonn E Mail info moeller net Internet www moeller net 2002 by Moeller GmbH Subjekt to alteration AWB2300 1527D GB Doku Doku Eb 05 05 Printed in the Federal Republic of Germany 09 05 Article No 284910 4 patpks v y Rückentext Hardware und Projektierung Hardware and Engineering 05 05 AWB2300 1527D GB A A A Think future Switch to green Think future Switch to green Rückenbreite bis 10 mm 1 Blatt 0 106...

Отзывы: