Starting the PLC with a
memory module plugged in
63
06/99 AWB 2700-1364 GB
Starting the PLC with a
memory module
plugged in
Follow the steps below if you wish to start the
PS 4-271 with a memory module plugged in:
왘
Switch off the PLC and plug in the memory
module. The mode selector switch can be in any
position.
왘
Switch on the PLC. The program in the memory
module will be transferred to the PS 4-271 and
the PLC will run with the set start conditions
(see Table 9).
Programming via
Suconet K
Several networked stations can be programmed and
test and commissioning functions run from a single
PC attached to Suconet K. This method applies to all
stations connected to line 1 which is served directly
by the master. If one of these stations (e.g.
LE 4-501-BS1) is at the head of another line, it will
not be possible to access the remote stations
attached to this line (dashed line in the diagram
below). Further information on this topic can be
found in the “Sucosoft S 40 user interface” manual
(AWB 2700-1305-GB).