Programming the Address in Case of Configuration Errors
5.5.1
Automatic Address Assignment
For automatic programming to work, some requirements must be met:
1.The AS-i master must be in the protected operating mode.
2.The “Auto_Address_Assign” release flag must be set.
3.Only one of the projected slaves may not be detected.
If these requirements are met, the AS-i master’s “
prg enable
” LED lights up and a
slave with address zero will be automatically assigned to the operating address of the
missing slave. The "Automatic Address Assignment" can be activated and deactivat-
ed via the software "AS-i Control Tools".
5.5.2
Manual Address Assignment
In protected operating mode, wrong assignments are displayed as errors (see chapter
5.3). By pressing the “set” button, you can display all faulty assignments one after the
other. By pressing the “set” button for more than five seconds, you can select the cur-
rently displayed address as a potential target address, and the display starts to blink.
If the faulty slave was previously replaced by a slave with address zero, the new slave
can now be programmed for the blinking address by pressing the “set” key again. As
a requirement, the new slave’s configuration data must match the configuration data
for the blinking address.
After the address has been successfully set, the next faulty assignment is displayed
and the address assignment can begin from the start. Otherwise, the system displays
an error code (chapter 9). When all faulty assignments are eliminated the display is
empty.
One of AS-i’s great advantages is the automatic address assignment. If
a slave fails, it can be replaced by one of the same type with address
zero. The master will detect the replacement and automatically
addresses the new slave with the address of the faulty one.
If the two slaves have different configuration data, i.e. are not of the
same type as far as AS-i is concerned, the automatic address assign-
ment will not be carried out.
If several slaves fail, they cannot be replaced automatically by the AS-i
master. Then these addresses have to be set manually. If this should
not be done via the host interface(using the AS-i Control Tools) or with a
hand held addressing device, the slave addresses can also be changed
with the help of the push buttons and the figure display of the device.
Содержание CM4-505-GV1
Страница 2: ......
Страница 6: ...AS i PROFIBUS Gateway The Used Symbols issue date 22 6 2001 6 ...
Страница 8: ...AS i PROFIBUS Gateway Safety issue date 22 6 2001 8 ...
Страница 16: ...AS i PROFIBUS Gateway Connections Displays and Operating Keys issue date 22 6 2001 16 ...
Страница 22: ...AS i PROFIBUS Gateway Operating the AS i PROFIBUS Gateway issue date 22 6 2001 22 ...
Страница 62: ...AS i PROFIBUS Gateway PROFIBUS DP issue date 22 6 2001 62 ...
Страница 68: ...AS i PROFIBUS Gateway Commissioning Tools and Accessories issue date 22 6 2001 68 ...
Страница 77: ......