Glossary
83
11/01 AWB2700-1426GB
Appendix
Protection against direct contact
Protective measures incorporated in the design, which
prevent direct touch (without tools) of live plant compon-
ents (safe from finger touch, back-of-hand proof).
Rated conditional short-circuit
current I
q
(see IEC/EN 60 947-1 / IEV
441-17-20)
Short-circuit current that can be carried through a short-
circuit safety facility, for example, a switching device
protected by a motor-protective circuit-breaker, for
example, a contactor, during the break time of the safety
facility.
Rated operational power P
N
(see IEC/EN 60 947-1)
Power rating, with which a switching device can switch at
the assigned
⇒
rated operational voltage
correspon-
ding to the utilization category, for example, contactor of
the utilization category AC-3:
37 kW at 400 V
Rated operational voltage U
e
(see IEC/EN 60 947-1)
Voltage to which the characteristic values of a switching
device relate. The highest rated operational voltage must
never be higher that the
⇒
rated insulation voltage
.
Rated operational current I
e
(see IEC/EN 60 947-1)
Current that a switching device can carry, taking in to
consideration
⇒
the
rated operational voltage
, service
life, utilization category and ambient temperature.
Rated uninterrupted current I
u
(see IEC/EN 60 947-1)
Current that a switching device can carry when in uninter-
rupted operation (for weeks, months or years).
Rated insulation voltage U
i
(see IEC/EN 60 947-1)
Voltage to which insulation test and creepage distances
relate. The highest
⇒
rated operational voltage
must
never be higher that the rated insulation voltage.
Safe from finger touch
A switching device is said to be safe from finger touch
when the electrically live parts cannot be touched when
the actuating elements are being operated. This is true also
for the operation of adjoining switching devices. The safe
from finger touch area of pressure operated electrical
equipment is a circle around the actuating element with a
minimum radius of 30 mm vertical to the operating facility.
Within this circle, parts that are dangerous to touch are
permitted to be arranged at a depth of at least 80 mm
below the operating level.
For Immediate Delivery call KMParts.com at (866) 595-9616
Содержание AWB2700-1426GB
Страница 8: ...11 01 AWB2700 1426GB 4 For Immediate Delivery call KMParts com at 866 595 9616...
Страница 12: ...8 11 01 AWB2700 1426GB For Immediate Delivery call KMParts com at 866 595 9616...
Страница 46: ...42 11 01 AWB2700 1426GB For Immediate Delivery call KMParts com at 866 595 9616...
Страница 67: ...For Immediate Delivery call KMParts com at 866 595 9616...
Страница 96: ...11 01 AWB2700 1426GB 92 For Immediate Delivery call KMParts com at 866 595 9616...