Страница 1: ...d perform the installation and maintenance of any coil Protective equipment such as safety glasses steel toe boots and gloves are recommended during the installation and routine maintenance of the coil RECEIVING INSTRUCTIONS All Heatcraft coils are factory tested inspected and carefully packaged Damage to the coils can occur after they have left the factory Therefore the coils should be inspected ...
Страница 2: ...uid header when properly installed Figure 1 NOMENCLATURE AND INSTALLATION Figure 1 Condenser Coils 5 Tube Outside Diameter 3 0 375 4 0 500 5 0 625 C Coil Type C Condenser N Circuiting N Normal Single Circuit F Face Control Multiple Circuits Q 1 4 serp H 1 2 serp L 3 4 serp S 1 serp C 1 1 4 serp M 1 1 2 serp D 2 serp 14 Fins Per Inch 06 Rows Deep C Fin Design A flat Al Cu B corrugated Al Cu C sine ...
Страница 3: ...ar from the pump as possible the vacuum at the pump will be greater than the rest of the system Evacu ate the coil to 500 microns or less then close the valve between the pump and the system If the vacuum holds to 500 microns or less for one minute the system is ready to be charged or refrigerant pumped down in another portion of the system can be opened to the coil A steady rise in microns would ...