NOMENCLATURE

MOUNTING

1.  Position the coil such that the liquid header is at the 
 

entering airside of the coil and the hot gas header is at the

 

leaving airside of the coil. This orientation provides counter   

 

flow heat exchange, which is required for proper coil 

 

performance. (Figure 1).

2.  The hot gas connection is located at the top of the hot gas   
 

header and the liquid connection is located at the bottom    

 

of the liquid header when properly installed. (Figure 1)

NOMENCLATURE AND INSTALLATION

Figure 1 - Condenser Coils

5 = Tube Outside Diameter

  

3 = 0.375”

4 = 0.500” 

5 = 0.625”

C = Coil Type

C = Condenser

N = Circuiting

N = Normal - Single Circuit
F = Face Control - Multiple Circuits
Q = 

1/4

 serp

H = 

1/2

 serp

L = 

3/4

 serp

S = 1 serp
C = 1 1/4 serp
M = 1 1/2 serp
D = 2 serp

14 = Fins Per Inch

06 = Rows Deep

C = Fin Design

A - flat (Al, Cu)

B - corrugated (Al, Cu)

C - sine wave (Al, Cu)
D - raised lance (Al) 

3/8

 

and 1/2

F - flat (SS, CS)

G - corrugated (SS, CS)

H - sine wave (SS, CS, Al, Cu)

 

24.00 = Fin Height (in)

minimum of 6 inches

144.00 = Finned Length (in)

minimum of 6 inches

5    C    N     14    06    C   24.00   x    144.00