ATH15-501.0 (

Supplement to ATH15-500.10

)

Gas Heating Option Gas Pressure Setup

The Gas Heating Option requires gas pressure be measured 

and adjusted as required at several points on the unit. The 

instructions below must be followed and completed after 

all other steps have been completed through page 22 of 

Installation and Service Manual, literature #ATH15-500.10:

Carel Controller Settings

Setup of the gas heating option for units with furnace model 

number digit 11= 6, 9, A, B, C, OR D requires certain settings be 

entered in the main unit Carel controller to enable firing furnaces  

individually or together for testing.  Refer to the following 

instructions when necessary (refer to the Controls Manual that 

shipped with the unit for further information):
1.  From the home screen press the “Prg” button (center 

left button) to reach “Main Menu”. Refer to Figure 4.1 for 

location of buttons.

9. 

Use the arrow buttons to find “Analog Outputs” with the title 

“Furnace 1 Signal” on the next line below.  Press "Enter".

10.  The cursor should go to the line “Manual Y4”.  Use the 

arrow buttons to set the value to “On” and press "Enter".

11.  The cursor should now be in the “Manual Value” line.  Press 

the down arrow button once to set the values to 10.0vDC 

for high fire.  Values between 10.0vDC and 2.0vDC can be 

used to check modulation, if desired.  If the unit is operating 

and this value is set to 1.5vDC or lower, the burners will 

turn off.  If the unit is not operating, this value must be set 

above 2.0vDC to fire.

12.  Hit “Esc” to return to the “Manual Management” menu.
13.  Use the arrow buttons to select “d.Relay Outputs” and 

press "Enter".

14.  If the unit fan is running skip to step 15.  Otherwise use the 

arrow buttons to find “Relay Output” with the label “Supply 

Fan” and press "Enter". 

15.  Use the arrow buttons to set the “Manual Relay 08” to 

“Yes”, press "Enter" and then use the arrow buttons again 

to set “Manual Position” to "Yes".  At this point the supply air 

fan should start.  Press "Esc". 

16.  To operate the modulated furnace section use the arrows 

buttons to find “Relay Output” with the label “Furnace 1 

Ignition” to start the modulated furnace and press "Enter".

17.  Use the arrow buttons to set the “Manual Relay 09” to 

“Yes”, press "Enter" and then use the arrow buttons again 

to set “Manual Position” to Yes.  At this point, furnace 1 

should initiate a start sequence even without pressing 

"Enter".  Changing “Manual Position” to “Yes” or “No” at this 

point can be used to initiate and end furnace 1 operation 

as desired.  Once furnace 1 is fired, you can begin to 

program the main valve and modulating valve high and low 

settings as needed.  You can also press “Esc” and go back 

to “e.Analog Outputs” shown in steps 8-11 above to test 

various demand points. When you have completed setting 

and testing furnace 1, set manual position to "Off".  The 

furnaces will operate for 5 minutes in this condition before 

the control resets “Manual Relay” to “No” and turns off the 

furnace.  If a longer run time is needed, reset the “Manual 

Relay” and “Manual Position” to “Yes” to restart.

18.   

Furnace Digit 11=9 or C Only (dual furnaces with a two 

stage furnace section)

:  For units with dual furnaces, the 

“Relay Outputs” list will have one screen titled “Furnace 

2 Stage 2” that controls high fire and “Furnace 2 Stage 

1” that controls low fire.  Each is controlled by setting the 

“Manual Relay” and “Manual Position” to “Yes”, similar 

to step 14 above.  Note:  Stage 1 “Manual Relay” and 

“Manual Position” must be set to “Yes” for the furnace 

to fire.  The furnace will always fire on high input but will 

step to low after thirty seconds of burner operation.  To 

operate at high fire continuously, “Furnace 2 Stage 2”, 

“Manual Relay” and “Manual Position” must also be set to 

“Yes".  This is accomplished by setting “Furnace 2 Stage1", 

“Manual Relay” and “Manual Position” to “Yes.”  After 

setting “Manual Position” to “Yes”, press "Enter" and you 

will be able to navigate to “Furnace 2 Stage 2” using the 

arrow buttons and again set “Manual Relay” and “Manual 

Position” to “Yes”. The furnaces will operate for 5 minutes 

at a time in this condition before the control resets “Manual 

Relay” to “No” and turns off the furnace.  If a longer run time 

Figure 4.1 - Carel Controller Buttons and Screen

Prg Button

Esc Button

Enter Button

(between Up and 

Down arrow buttons)

2.  Arrow up or down to reach the “Service” menu and hit 

"Enter" (center right button).  Arrow up or down to “g. 

Manual Management” and press "Enter".

3.  At the password prompt use the arrow and "Enter" buttons 

to enter the password 1500.

4. 

If the unit is configured with a 2-position type damper (unit 

model digit 7=D, E, or F) and the damper is closed, arrow 

up to “d. Relay Outputs” and press "Enter". Use the arrow 

keys to find “OA Damper Open” and press “Enter”. The 

cursor should be on the “Manual Relay 05” line, set “Manual 

Relay 05” to “Yes” and press “Enter”.  The cursor should 

now be on the “Manual Position” line. Set “Manual Position” 

to “On” and press "Enter".

5.  Arrow up to “e.Analog Outputs” and press "Enter".  If the 

main fan is operating, skip to step 8.

6. 

If the fan is not running, use the arrow buttons to find 

“Supply Fan” and press "Enter".

7.  The cursor should be on the “Manual Y5:” line.  Set “Manual 

Y5:” to “On” and press "Enter".

8.  The cursor should now be on the “Manual Value:” line. Set 

the value to 10.0vDC for full speed fan operation and press 

"Enter". Note that depending on unit configuration, the 

maximum value delivered to the VFD may be displayed at 

less than 10.0vDC.  This is normal.

GAS HEAT START-UP PROCEDURE

Содержание Atherion MPR

Страница 1: ...adjustment alteration service or maintenance can cause serious injury death or property damage Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Leave the building immediately Immediately call your gas...

Страница 2: ... failure the input to the appliance as indicated on the serial plate must not exceed the rated input by more than 5 4 To prevent premature heat exchanger failure check to be sure the blower has been set to deliver the proper airflow for the application Refer to the Blower Adjustments section in ATH15 500 10 5 Start up and adjustment procedures must be performed by a qualified service agency 8 When...

Страница 3: ...ased on input Highest possible turn down and more consistent efficiency are possible with this control For C and D Cabinet with rating of 800MBH and lower The unit includes two heat exchangers with control as follows indicated by Digit 11 9 One heat exchanger equipped with a single manifold with advanced Beckett modulation control and the other equipped with two stage control The second heat excha...

Страница 4: ...ress Esc and go back to e Analog Outputs shown in steps 8 11 above to test various demand points When you have completed setting and testing furnace 1 set manual position to Off The furnaces will operate for 5 minutes in this condition before the control resets Manual Relay to No and turns off the furnace If a longer run time is needed reset the Manual Relay and Manual Position to Yes to restart 1...

Страница 5: ...the combination gas control valve to the ON position Note for C and D Cabinet sized units and units equipped with split manifolds the Gas Heating Option consists of one or more heating sections that are not modulated For this step only one combination gas valve on the modulated furnace or manifold section is to be set to the ON position 2 Enable the unit controls The LED display on the furnace con...

Страница 6: ...rol will default to the previously saved settings and return to normal operating mode 8 Adjust the Low Fire Setting as follows a Press and hold Button 2 on the modulating valve until the LED light blinks red then release b With the valve now in the low fire setting mode confirm or adjust the low fire manifold pressure to be no less than the minimum shown on the furnace serial plate in the box call...

Страница 7: ...manual shut off valve to the ON position and recheck all pipe plugs for gas leaks with soap solution Clearing Furnace Control Board Error Codes 1 Error codes on the primary control board VB1285 can be viewed by pressing the UP MODE button for at least 4 seconds until the LED display changes to display Lo9 and release the button Refer to Figure 5 1 for location of buttons and LED display and Table ...

Страница 8: ...A indicates an aged flame rod A07 Alert Loss of Inducer Motor Control The Air Pressure is not modulating down at minimum inducer drive A08 Alert Air Sensor Null Pressure Check out of tolerance The Air Pressure sensor zero reading appears to be out of tolerance A11 Alert Failed Ignition Split Manifold Failed Ignition Split manifold burner retries exhausted A15 Alert Weak Flame Signal split manifold...

Страница 9: ...power cycle 7 Flashes Lockout five many flame losses in a call for heat Will reset on next call for heat or in 1 hr Display Code Description Additional Notes Steady On Green Normal Operation Amber Flame is sensed Normal operation 1 Flash Pressure switch open Inducer on Check inducer pressure switch and tubing 2 Flashes Pressure switch open Inducer off after 5 min run Check inducer pressure switch ...

Страница 10: ...alve 4 High limit control hidden behind Item 2 on 80 efficiency furnace 5 Solid state ignition control board 6 Furnace control board 7 Vent differential pressure proving switch 8 Direct spark ignitor 9 Manifold pressure tap on manifold tee 10 Flame sensor 11 Manifold piping with gas orifices 12 Condensate drain float switch 94 efficiency furnace only 13 Compartment strip heater thermostat 94 effic...

Страница 11: ...rd for right side furnace but located on left side of cabinet 6 Valve state relay to Carel controller 90 furnaces only 7 Secondary furnace control board for left side furnace 8 Direct spark ignition control board cover removed 9 Vent differential pressure proving switch 10 Direct spark ignitor behind control boards on 90 furnaces 11 Manifold tee pressure tap primary furnace only 12 Flame sensor be...

Страница 12: ...g as shown 5 Solid state ignition control board cover removed 6 Furnace control board cover removed 7 Vent differential pressure proving switch 8 Direct spark ignitor 9 Manifold pressure tap on manifold tee primary furnace only 10 Flame sensor 11 Manifold piping with gas orifices 12 Heat exchanger tube drain tray with drain line 1 3 5 7 2 4 6 8 10 11 12 9 Primary Furnace Right Side of Cabinet Seco...

Страница 13: ...ts 900 000 Btu hr and Larger 81 Eff Secondary Furnace B k Primary Furnace k Secondary Furnace A k Secondary Furnace C k j Refer to Figure 7 1 for location of furnace positions k Refer to Figure 12 1 for identification of furnace components j Refer to Figure 7 1 for location of furnace positions k Refer to Figure 12 1 for identification of furnace components GAS HEAT OPTION COMPONENT LOCATION ...

Страница 14: ...5 Solid state ignition control board 6 Furnace control board cover removed 7 Vent differential pressure proving switch 8 Direct spark ignitor 9 Manifold pressure tap on manifold tee primary furnace only 10 Flame sensor 11 Manifold piping with gas orifices 12 Heat exchanger tube drain tray with drain line 13 Cabinet strip heater 1 3 5 7 2 4 6 8 10 11 12 9 Primary Furnace Right Side of Cabinet Secon...

Страница 15: ...k Secondary Furnace C k j Refer to Figure 7 1 for location of furnace positions k For identification of furnace components refer to Figure 12 1 for the 81 efficient modules on the bottom and Figure 14 1 for the condensing modules on the top j Refer to Figure 7 1 for location of furnace positions k For identification of furnace components refer to Figure 12 1 for the 81 efficient modules on the bot...

Страница 16: ...ue Racine WI 53403 Phone 1 800 828 4328 HEAT www modinehvac com Modine Manufacturing Company 2021 As Modine Manufacturing Company has a continuous product improvement program it reserves the right to change design and specifications without notice ...

Отзывы: