INSTRUCTION MANUAL
Specifications:
• Operating Voltage is 12~24 VAC/DC
• Current Draw: Holding: 22mA, Pull-In: 66mA@12VAC/DC
Holding: 12mA, Pull-In: 32mA@24VAC/DC
• Relays Electric Current: 12A@14VDC, 7A@120VAC
• Optimal Operating Temperature: -20 to +70 ˚C (-4 to +158 ˚F)
• Invalid Code Lock Out: The system will shut down for 60 seconds after 5 invalid
PIN are attempted.
Dimensions & Contents
SOUND SIGNAL
• 1 Short Beep: Key In
• 1 Long Beep: Valid PINs
• 2 Beeps: Enter / Exit Programming Mode
• 3 Beeps: Incorrect Input
• 5 Beeps: Reset master code to default value (1234),
clear all PINs
System Signals
LED SIGNAL
•
Green LED: First Relay Active
•
Red LED:
Second Relay Active
•
Yellow LED: Normal (Power On)
5”
6½”
MAK-200
SCREWS & PLASTIC
WALL ANCHORS X 4
4
3
/
8
”
GASKET
KEYS X 2
Installation and Wiring Instructions & Diagrams
+
-
REED
+
-
ELECTRIC LOCK 2
FAIL-SECURE MODE
INPUT
AC/DC
12-24V
COM
P.B.
N.O.
COM
N.C.
N.O.
COM
N.C.
TA
M
P
E
R
S
W
IT
C
H
R
E
L
A
Y 2
3
2
1
N.C.
N.C.
TA
M
P
E
R
* RESET MASTER CODE:
INSERT THE JUMPER
INTO CONTACTS 2&3
SEE: Figure 1
For DC use only
-
+
IMPORTANT!
1.
It is suggested to use #22~26 AWG insulation wire
2.
The door strike or relay must have a varistor or a diode across the door
strike terminals to suppress back the EMF of the strike - failure to do so
will damage the relay contacts and electronic components, or even burn
the controller.
For AC/DC
-
+
~
~
ELECTRIC LOCK 1
FAIL-SAFE MODE
EXIT BUTTON
POWER SUPPLY UNIT
12 VDC
DOOR CLOSED = N.O.
DOOR OPENED = N.C.
Gate Operator
Magnetic Lock
Electric Strike
+
-
+
-
RESET
Master Code resetting to
Factory Code “1234”
Resetting
Normal
3 2 1
3 2 1
Figure 1
FACTORY DEFAULT SETTINGS
Master Code
1234 (4 digits)
Relay Strike Time (Time Delay Setting)
5 sec.
Pressed Key Time Delay
5 sec. (fixed)
Programming Mode Time Delay
25 sec. (fixed)
PIN Digits
4 digits
DESIGNED FOR THE PROFESSIONAL INSTALLER
OUR QUALITY CAN’T BE MEASURED
®
MAK-200
MAK-200
ACCESS KEYPAD
OUR QUALITY CAN’T BE MEASURED
®