Connection of motorized turnouts 

When  connecting  motorized  turnouts,  the 
extension  kit  ESMot  must  be  populated  (for 
the concerned outputs). Basically the connec-
tion of all motorized turnouts is the same: Both 
contacts of the motor are directly connected to 
the  outputs  of  the  Accessory  Decoder 
WDMiba, each at terminals a and c – terminal 
b is left unconnected.  
Some  vendors  of  motorized  turnouts  equip  their  motors  with  an 
additional circuitry (in most cases two diodes) which leads to more 
than  just  two  contacts.  Usually  there  is  one  common  ground  (or 
voltage supply) which is to be connected to terminal a. Additionally 
there should be a contact for each turning direction which are to be 
both connected to terminal c. There might be further wires but they 
are  not  of  interest  for  the  connection  to  the  Accessory  Decoder 
WDMiba. 

Parameters and Programming 

Programming 
By  programming  the  address  of  this  module  and  all  further  pa-
rameters  are  set.  In  this  section  all  parameters  are  explained. 
Refer to the last page of these instructions for an example for the 
programming procedure. 

Convention Bit and Key 
In information technology “Bit 0” to “Bit 7” is common. 

For model railroaders a numbering of “bit 1” to “bit 8” is much more 
convenient,  as  “Bit  1”  becomes  equal  to  “Key  1”  or  “position  1”. 
This convention is used in these instructions. 

Overview of parameters 

Address 0:  Address of this module 

1 to 103 / 111 (80) 

 

 

see table of addresses 

Address 1:  Timer assignment): 

 

Bit value 0 (Off, “0” or “-“) 

assigns timer 1 

 

Bit value 1 (On, “1” or “/”) 

assigns timer 2 

Address 2:  Timer 1 

1 to 254, 255 (16) 

 

Pulse length: 1 to 254: (80ms increments) 

 

Continuous current: 255 (all bits 1) 

 

Factory setting: 16 = pulse length 1.2 seconds. 

Address 3:  Timer 2 

1 to 254, 255 (255) 

 

Pulse length: 1 to 254: (80ms increments) 

 

Continuous current: 255 (all bits 1) 

 

Factory setting: 255 = continuous current 

Address of this module 
The  address  of  this  module  can  be  set  to  any  value  in  the  range 
from  1  to  111.  Note  that  at certain  central  units  addresses  104  to 
111 are reserved for internal purposes during operation and should 
thus not be used. 
Also, addresses 0 to 3 are often used for programming parameters 
of modules. Therefore these addresses should also not be used. 

Operation mode 

The  Accessory  Decoder  WDMiba  offers  2  operation  modes: 
Pulsed current and continuous current. 
To allow controlling accessory types with different current require-
ments,  for  each  of  decoder’s  eight  output  channels  one  of  two 
timers can be selected individually. Both timers (1 and 2) can have 
either  a  pre-determined  pulse  length  value  or  set  to  continuous 
current. 

Operation mode pulsed current 

The operation mode pulsed current enables the output current only 
for a specific time (set by the timer) after switching to this direction. 
Afterwards, the output is off. 

Not all solenoid powered accessories have the same requirements 
for the duration of pulsed current to operate them. For instance, a 
turnout with a double solenoid and limit stop can usually be oper-
ated with a 0.5 to 1 second pulse length. Theoretically it is possible 
to  operate  this  type  of  turnout  with  continuous  current,  but  if  the 
limit  stop  is  not  working,  the  solenoid  will  get  damaged.  Solenoid 

turnouts without limit stop should be controlled with pulses lasting 
0.2 to 0.5 seconds. 
On  the  other  hand,  there  are  slowly  moving  turnouts  and  sema-
phore  signals.  These  might  require  pulse  lengths  of  4  to  8  sec-
onds. 
Uncoupler  tracks  should  as  well  not  be  operated  with  continuous 
current. Instead, select  a  pulse  with  a  length  of  up  to  20 seconds 
for uncouplers. 

Operation mode continuous current 

The operation mode continuous current enables the output current 
permanently, so one of the dual-port outputs is always active. 

For a light signal an output of continuous current is required which 
lights up red on Stop but lights up green on Go instead. Only one 
of the two lights is activated at the same time. 

Timers 1 and 2 

Both  timers  of  the  Accessory  Decoder  WDMiba  are  equal  which 
means  that  they  can  be  programmed  independently  to  any  pulse 
length  between  0.08s  (80ms)  and  20  seconds  with  80ms  incre-
ments, by selecting values from 1 to 254. Both timers can also be 
set to  identical  pulse  lengths  or continuous current mode  (by  pro-
gramming value 255). 
For each of the 8 decoder output channels one of those 2 timers is 
assigned. 
Timer 1 is assigned for all output channels where operation mode 
0  is  selected;  timer  2  is  assigned  for  all  output  channels  where 
operation mode 1 is selected, respectively. 

Overview of timers 
The  pulse  length  is  calculated  by  summation  of  the  separate  bit 
values (1 to 254) multiplied with the increment (0.08 s = 80 ms) 
Bit 

Value 

16 

32 

64 

128 

Pulse 

0,08 

0,16 

0,32 

0,64 

1,28 

2,56 

5,12 

10,24 

Value 255 (all bits ON) selects continuous current. 
On the next page you’ll find a table with some examples. 

Delayed output 
In  computer  controlled  and  other  automatic  layouts  several  turn-
outs  or  signals  are  typically  switched  simultaneously.  This  could 
result  in  excessive  power  consumption  which  exceeds  the  output 
capacity of the decoder. 
To prevent problems due to current peaks decoder outputs config-
ured for pulse type outputs are activated with 80 ms delay between 
them  when  operated  simultaneously.  For channels  set  to continu-
ous  current  output,  there  is  no  delay  between  them  in  simultane-
ous operation. 

Security monitoring system 
Poorly  laid  wiring  or  malfunctions  of  system  components  may 
result in a situation where a pulse type output is not switched off in 
time.  This  can  cause  overheating  or  even  burn  a  solenoid  con-
nected to decoder output. 
The  Accessory  Decoder  WDMiba  is  equipped  with  a  security 
monitoring system (Watchdog) which cuts off the output current of 
all output channels after about 2 seconds when an output pulse is 
not terminated in time normally due to SX system malfunctions. 

Factory default settings 

Address of this module:  80 
Operation mode: 

0 0 0 0 0 0 0 0 

(all output channels use timer 1) 
Timer 1: 

16 

(1.28 seconds) 

Timer 2: 

255 

(continuous current output) 

If the address of this module is set to a value greater than 111, it 
will be reset to the factory default setting (90). 

Setting the address of this module to the value of 255 will reset all 
parameters to their factory default settings. 

Revert back to previous settings 
Entering  0  as  address,  response  or  dropout  delay  reverts  the 
corresponding value to its previously programmed one. 
 

Содержание WDMiba 3

Страница 1: ...hen re powering the Selectrix bus the accessory decoder feeds back its last state position of the turnouts etc to the central unit before the system was switched off the last time Special features Especially for Selectrix Further improved reliability by using input comparators at the SX bus Population option for motorized consumers already foreseen ESMot no additional PCB is required Space for ser...

Страница 2: ...delivered Keep all electro conductive tools assembly kits and cables away from the module during operation A negligently and by external circumstances caused short circuit impinging on the module from above or from the bottom may destroy the module If that happens all terms of warranty will become invalid Update The heart of the module is a PIC that stores the software A socket for the PIC provide...

Страница 3: ...SMot are mounted with the cathode marked with a stripe to the inner side of the PCB D17 D32 1N4001 4 IC Socket for PIC Place and solder the PIC socket and ICs with the notches according to the component layout diagram on the PCB IC2 LM393 Sockel Socket for PIC 5 Push button Place on the reserved spot accordingly and solder 6 LED The cathode of the LED is to be placed to face the corner of the PCB ...

Страница 4: ...tifier circuit is 1 4 times the voltage of the input alternating current Light signals equipped with LEDs designed for 16 V AC should be fed with either 11 V AC or the value of the LED resistor should be increased respectively Output numeration of the Accessory Decoder WDMiba Connections of output channels Pin Tournout Signal Uncoupler a Tangent Stop Not used b VS VS VS c Tournout Go Activate Norm...

Страница 5: ... current but if the limit stop is not working the solenoid will get damaged Solenoid turnouts without limit stop should be controlled with pulses lasting 0 2 to 0 5 seconds On the other hand there are slowly moving turnouts and sema phore signals These might require pulse lengths of 4 to 8 sec onds Uncoupler tracks should as well not be operated with continuous current Instead select a pulse with ...

Страница 6: ...mer 2 Select address 03 in Control Panel Enter switching mode by key Adr and enter 0 3 Current value of timer 2 is displayed in binary e g all bits are on equals continuous output current Adr 255 002 12345678 aus Enter new value for timer 2 Enter value for timer 2 binary e g 0 16 seconds by key 2 Adr 002 002 12345678 aus Exit programming mode Press the programme button of the occupancy detector or...