background image

LP-446-r4 Rev. 10.12.16

46

NOTE: 

For the following functions, you must have your 

maintenance function turned on.

To change these functions, press 

ENTER

. The left most digit will 

begin to blink. Use the 

or 

v

 arrows to change the digit. Use 

the 

< >

 arrow keys to switch between digits. When you’ve made 

your selection, press 

ENTER

 again.

Screen

Description

Function 33

Year

SERVICE   SCHEDULE
YEAR  00/00/2000               33

Allows the user to set the year of the 
next service reminder.

Hours

SERVICE   SCHEDULE
10000’s  

00

0000                      33

Allows the user to set the left two digits 
of the amount of run hours before next 
service reminder.

Function 34

Month

SERVICE   SCHEDULE
MONTH  00/00/2000             34

If the date function was selected, this 
function  programs  the  month.  If  you 
selected  the  run  hour  function,  you 
will  need  to  program  10,000  hours,  if 
required.

Hours

SERVICE   SCHEDULE
10000’s  00

00

00                      34

Allows the user to set the middle two 
digits  of  the  amount  of  run  hours 
before next service reminder.

Function 35

Day

SERVICE   SCHEDULE
DAY   00/00/2000                35

Sets the day of next service reminder.

Hours

SERVICE   SCHEDULE
10000’s  0000

00

                      35

Sets the two right digits of the amount 
of  run  hours  for  the  next  service 
reminder.

Function 36

Telephone

TELEPHONE   #
000 000 0000                        36

Allows  the  user  to  input  a  telephone 
number  that  will  display  when 
maintenance is required.

Table 20 - Maintenance Reminder Function Screens

G. Resetting the Maintenance Schedule

When  the  system  control  flashes  MAINTENANCE  REQUIRED, 
it  is  advisable  that  you  call  for  service.  After  the  service  is 
performed, reset the schedule for the next required service by 
using the following steps.
Press 

ENTER

  on  the  display  for  3  seconds.  The  Menu  code 

will appear as 000. This does not change. Press 

ENTER

 again. 

SERVICE SCHEDULE RESET will be displayed. Using the 

>

 key 

scroll to the selection of year or hours. Press 

ENTER

 to reset the  

selected Service Schedule. To change a setting, press 

ENTER

Press the 

^

 and 

v

 keys to make adjustments. Press 

ENTER 

when 

reset is complete.

Part 10 - Start-Up Procedures for the Installer

A. Boiler Control Status Menu

The boiler control also has the ability to review system status. 
To  access  the  status  screens,  press 

>

.  Once  the  first  value  is 

displayed, press 

^

 and 

v

 to scroll through additional information. 

At any point press 

RESET

 to exit the status screens.

Screen

Description

SUPPLY   SEN                   180

o

F       

RETURN   SEN                         150

o

F

This is the first screen that appears 
after  pressing 

>

,  and  shows  the 

actual  temperatures  measured 
by  the  supply  and  return  sensors. 
NOTE: If the boiler is configured to 
use  a  0  –  10  volt  input,  the  return 
sensor  is  disabled  and  the  second 
line of the display will be blank.

Press v once.

NA                                           NA
SUPPLY   SEN                   122

o

F       

The  actual  temperature  measured 
by the supply sensor is displayed on 
the bottom.

Press v once.

0-10   SIGNL   ON       
*

Shows if 0-10 volt is enabled.

Press v once.

This screen appears only when the 
boiler is set as a Master Boiler.

CAS   SET                        190

o

F       

SYSTEM                          112

o

F

This screen displays the cascade set 
point  (maximum  190

o

F)  on  the  top 

line.  The  system  sensor  reading  is 
on  the  second  line. The  control  will 
cascade  the  boilers  up  to  this  set 
point depending on demand.

Press v once.

TANK   SET                        120

o

F       

RET / TANK                          OFF

Displays 

the 

current 

tank 

temperature set point on the top line. 
The  actual  temperature  measured 
by  the  tank  or  return  sensor  (HTP 
7250P-325)  is  displayed  on  the 
bottom line. If a mechanical aquastat 
is used in place of the recommended 
sensor,  the  second  line  will  display 
‘OFF’  in  place  of  the  temperature 
if  the  aquastat  measures  close  to 
its  set  temperature,  or  ‘ON’  if  the 
aquastat temperature is too low.

Press v once.

NA                                        11

o

F       

FLUE                                   95

o

F

The second line displays the current 
boiler flue temperature.

Press v once.

FLAME                               0.0uA
FAN   SPEED            3497 RPM

This  screen  displays  boiler  flame 
current on the top line. The second 
line displays boiler fan speed.

Press v once.

0-10   V                                   0.0V
*

The top line displays the voltage on 
the  optional  input.  This  voltage  is 
only relevant if an external 0-10 volt 
signal  is  being  used  to  control  the 
boiler.

Press v once.

Содержание MODCON500

Страница 1: ...personal injury or death HTPreservestherighttomakeproductchangesorupdateswithoutnoticeandwillnotbeheldliablefortypographical errors in literature NOTETO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTUR...

Страница 2: ...VICINITY OFTHIS OR ANY OTHER APPLIANCE WHATTO DO IFYOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Do not use any phone in your building Immediately call your gas su...

Страница 3: ...dividual such as a fire chief fire marshal chief of a fire prevention bureau labor department or health department building official or electrical inspector or others For the Installer This boiler mus...

Страница 4: ...ating System 5 D BoilerWater 6 E Freeze Protection 6 F High Elevation Installations 6 G WaterTemperature Adjustment 6 Part 2 BeforeYou Start 7 A What s in the Box 8 B How the Boiler Operates 8 C Optio...

Страница 5: ...e boiler warranty and could result in property damage personal injury or death This boiler has been designed to heat potable water ONLY Using this boiler to heat non potable fluid WILL VOID product wa...

Страница 6: ...utes 125oF 1 1 2 to 2 minutes 130oF About 30 seconds 135oF About 10 seconds 140oF Less than 5 seconds 145oF Less than 3 seconds 150oF About 1 1 2 seconds 155oF About 1 second Table 1 ApproximateTime T...

Страница 7: ...StorageTanks Contact HTP for Available StorageTanks 40o 1414 859 883 894 1980 1206 1217 1260 2404 1449 1459 1502 50o 1131 872 902 915 1584 1225 1238 1292 1923 1467 1481 1534 60o 943 884 920 937 1320 1...

Страница 8: ...oilers Each cascaded boiler will have its own pump to provide maximum flow and control heat exchanger flow rate Text Display and Operational LED Light Indicators The display allows the user to change...

Страница 9: ...y damage severe personal injury or death A Locating the Boiler Incorrect ambient conditions can lead to damage to the heating system and put safe operation at risk Ensure that the installation locatio...

Страница 10: ...orrect operating conditions IS NOT covered by product warranty Use extreme care not to drop the boiler or cause bodily injury while lifting the boiler Gas conversion should be performed BEFORE the boi...

Страница 11: ...orted Boiler exhaust and intake connections are not designed to carry heavy weight Vent support brackets must be within 1 of the boiler and the balance at 4 intervals Boiler must be readily accessible...

Страница 12: ...15 cm below the space ceiling the other 6 15cm above the space floor Each opening should have a free area of one square inch per 1 000 BTU hr 22cm2 kW of the total input of all appliances in the space...

Страница 13: ...G of ANSI Z223 1 Figure 4 CO Warning Label I Water Chemistry Requirements Chemicalimbalanceofthewatersupplymayaffectefficiencyand cause severe damage to the boiler and associated equipment HTP recomme...

Страница 14: ...in property damage severe personal injury or death Dielectric unions or galvanized steel fittings must not be used in a system with this boiler Doing soWILLVOID the warranty Useonlycopper brass orsta...

Страница 15: ...al location following the guidelines below entire length Discharge line must pitch downward from the valve and terminate at least 6 above the floor drain making discharge clearly visible The discharge...

Страница 16: ...The boiler circulator location is selected to ensure adequate flow through the boiler Failure to comply with this caution could result in unreliable performance and nuisance shutdowns from insufficie...

Страница 17: ...ve flows and friction loss This is provided to aid in circulator selection SystemTemperature Rise Chart 20 t 25 t 30 t Model Friction Ft Flow Rate GPM Friction Ft Flow Rate GPM Friction Ft Flow Rate G...

Страница 18: ...ion must be replaced The manufacturer of the boiler has no control of water quality especially TDS levels in your system Total dissolved solids in excess of 2 000 ppm will accelerate lime and scale fo...

Страница 19: ...rect tank sensor or system pipe sensor mounted on common return to the boiler 12 Aquastat or system pipe sensor connects to DHW sensor input on boiler 13 The minimum storage tank size for a 500VWH is...

Страница 20: ...oiler Manifold Piping Chart this manual 6 All pumps are shown with isolation flanges or full port ball valves for isolation The alternative is standard flanges with full port ball valves and a separat...

Страница 21: ...for connecting a boiler is 2 When sizing and installing a multiple boiler system see Multiple Boiler Manifold Piping Chart this manual 6 All pumps are shown with isolation flanges or full port ball va...

Страница 22: ...contamination often contained in indoor air it is best to pipe all intake combustion air directly to the outdoors NOTE If exhaust vent pipe system passes through an unheated space such as an alcove or...

Страница 23: ...d vent system must not be interchanged with other vent systems or unlisted pipe fittings Cellular foam core piping may be used on air inlet piping only DO NOT mix components from different venting sys...

Страница 24: ...er to center Minimum distance between exhaust vents and intake pipes on multiple boilers is 10 0 255 m center to center L When adjacent to a public walkway locate exit terminal at least 7 feet above g...

Страница 25: ...am core piping may be used on air inlet piping only 2 Remove all burrs and debris from joints and fittings 3 When using PVC or CPVC pipe all joints must be properly cleaned primed and cemented Use onl...

Страница 26: ...given in theVenting section of this manual When installing a combustion air intake from outdoors care must be taken to utilize uncontaminated combustion air NOTE To prevent combustion air contaminati...

Страница 27: ...4 foot intervals on the vent pipe Venting must be readily accessible for visual inspection from the first three feet from the boiler NOTES A For every 1 of overhang the exhaust vent must be located 1...

Страница 28: ...re meant to demonstrate system venting only The installer is responsible for all equipment and detailing required by local codes Figure 18 UnbalancedVenting Roof Exhaust and Sidewall Intake An unbalan...

Страница 29: ...air is taken from the outdoors using a duct to deliver the air to the mechanical room each of the two openings should be sized based on a minimum free area of one square inch per 2000 BTU hr input See...

Страница 30: ...structions could result in property damage or personal injury Combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the boil...

Страница 31: ...he boiler prior to opening an electrical box within the unit Ensure the power remains off while any wiring connections are being made Failure to follow these instructions could result in component or...

Страница 32: ...the tank then one sensor should be used on the pipe carrying water from the tank s to the boiler To minimize temperature loss in the piping this sensor should be placed as close to the tank s as possi...

Страница 33: ...l ignite As the signal continues to rise towards its maximum of 10 volts the boiler will increase in set point temperature See Part 10 for details on the setting of function 16 2 Connect a building ma...

Страница 34: ...or to the terminals marked SYS SENSOR 4 Do not connect anything to the OUTDOOR SENS or THERMOSTAT terminals 5 If 0 10 volt positive going DC signal input is used connect to marked terminals O Cascade...

Страница 35: ...LP 446 r4 Rev 10 12 16 35 Figure 29 Cascade Master and FollowerWiring...

Страница 36: ...SWITCH FOR VWH APPLICATION OPTIONAL FOR STANDARD BOILER APPLICATION LOW WATER LEVEL APPLICATION FOR STANDARD BOILER ONLY NOT FOR VWH X6 5 FLAME RECTIFICATION PROBE BVPS FUSE THERMAL X5 4 926 CONTROL X...

Страница 37: ...rtant to support gas piping as the unit is not Support gas supply piping with hangers not by the boiler or its accessories The boiler gas valve and blower will not support the weight of the piping Mak...

Страница 38: ...upply at the manual gas valve before disconnecting the hose from the gas monitoring device Tighten screw on the pressure tap and turn gas on Check for leaks with soapy solution Bubbles will appear on...

Страница 39: ...death Strainonthegasvalveandfittingsmayresult in vibration premature component failure and gas leakage and result in fire explosion property damage severe personal injury or death Adjustments to the t...

Страница 40: ...al 1 The boiler is a high efficiency condensing boiler Therefore the unit has a condensate drain Condensate fluid is nothing more than water vapor derived from combustion products similar to that prod...

Страница 41: ...set temperature installer 4 or that boiler is at high firing rate If the command from the master boiler control gets to the high firing rate of the follower boiler but the system sensor is below the r...

Страница 42: ...building Immediately call your gas supplier from a neighbor s phone Follow the gas suppliers instructions If you cannot reach your gas supplier call the fire department Turn off the gas shutoff valve...

Страница 43: ...the user to adjust the ignition differential set point from 1oF to 36oF Factory Default 7oF Degrees below set point must be equal to or below tank differentials TANK SETPOINT 120 oF Adjusts the tank s...

Страница 44: ...set point that the burner will maintain its outlet water temperature while there is a demand for heat Factory Default is 20oF Range 1oF to 45oF Function 6 VWH Post PumpTime VWH POST PUMP TIME 0 MINUTE...

Страница 45: ...a connected and powered Modbus communication adapter p n 7350P 629 will result in improper appliance operation Service calls associated with this ARE NOT covered by warranty Table 19 System Setting Pr...

Страница 46: ...ting press ENTER Press the and v keys to make adjustments Press ENTER when reset is complete Part 10 Start Up Procedures for the Installer A Boiler Control Status Menu The boiler control also has the...

Страница 47: ...ate and time that the fault occurred Press v once FAULT HISTORY 4 08 28 2009 Fr 5 19A This screen displays the fourth oldest boiler control lockout fault The top line will alternate between the words...

Страница 48: ...tom line shows the status of the system pump output contacts Press v once CASCADE PWR 100 PRESENT 01234567 This screen displays overall cascade power output The range of this value is the number of bo...

Страница 49: ...mp to run in an attempt to cool the boiler 2 Note the displayed fault code and refer to Section D for an explanation of the message along with several suggestions for corrective actions 3 Press RESET...

Страница 50: ...n FLU error Faulty switch MUST be replaced Failure to follow this instruction could result in serious personal injury or death 24 VOLT LOW LOU PUMP ON LOU indicates the 24 volt power supply on the con...

Страница 51: ...h the boiler or b poor heat transfer from the water to the load 5 If no switches are tripped push RESET on the boiler If the boiler tries to ignite or ignites and only runs for a short time and the F0...

Страница 52: ...exists The boiler will not restart until a technician determines and repairs the cause of excessive temperature and pushes RESET on the display If the red FAULT light is not illuminated and this messa...

Страница 53: ...he combustion chamber the refractory wall may be damaged and should be replaced 5 Turn the gas on at the service valve after corrective action is taken 6 If the refractory wall falls against the recti...

Страница 54: ...for boiler operation FLUE TEMP HIGH E07 PUMP OFF TIME E07 indicates the flue sensor temperature is excessive and above 210oF When E07 is displayed the boiler will not respond to a demand for heat When...

Страница 55: ...manufacturers and phone numbers are also listed on this website Wear long sleeved loose fitting clothing gloves and eye protection Apply enough water to the combustion chamber lining to prevent dust...

Страница 56: ...ers as shown in the piping diagrams in this manual Slowly open the ball valves and release pressure into a bucket Once pressure is released connect a hose to the water line to flush the boiler Scale r...

Страница 57: ...LP 446 r4 Rev 10 12 16 57 Figure 35 500 Model Combustion System Replacement Parts...

Страница 58: ...LP 446 r4 Rev 10 12 16 58 Figure 36 700 850 Models Combustion System Replacement Parts...

Страница 59: ...250P 152 7250P 152 O RING SILICONE 2 007 BARBED FITTING 22 7350P 605 7350P 605 FLOW SWITCH KIT FOR MOD CON VWH 07 28 16 ITEM MOD CON 500VWH MOD CON 700 VWH MOD CON 850VWH DESCRIPTION 1 7500P 033 7500P...

Страница 60: ...LP 446 r4 Rev 10 12 16 60 Figure 38 Cabinet Replacement Parts All Models...

Страница 61: ...If necessary convert the boiler to the proper fuel type Locate the stickers in the appropriate locations on the boiler Verify combustion settings after gas conversion Carbon Dioxide CO2 High Fire CO2...

Страница 62: ...Ignitor and Flame Probe Check ionization in uA d7 in Status Menu in Start Up Procedures Record high fire and low fire Clean probe with plumbers cloth to remove oxides Condensate 1stYear 2ndYear 3rdYe...

Страница 63: ...ONOXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fueled equipment the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with...

Страница 64: ...ENTING SYSTEM PROVIDED When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment the instru...

Страница 65: ...ating components must be maintained in good operating condition 3 All lines must be checked to confirm that all condensate drains properly from the unit 4 Operate the VWH at pressures not exceeding th...

Страница 66: ...CEPTED IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING WITHOUT LIMITATION THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE AND ANY OBLIGATION LIABILI...

Страница 67: ...LP 446 r4 Rev 10 12 16 67 Maintenance Notes...

Страница 68: ...of Installation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Customer P...

Отзывы: