background image

LP-446-r4 Rev. 10.12.16

15

A. General Plumbing Information

Use two wrenches when tightening water piping at boiler. Use 
one  wrench  to  prevent  the  boiler  return  or  supply  line  from 
turning.  Failure  to  prevent  piping  connections  from  turning 
could cause damage to boiler components.

The building piping system must meet or exceed the the piping 
requirements in this manual.

NOTE: 

The  addition  of  a  high  temperature  limiting  device  is 

important  if  the  boiler  is  to  be  connected  to  a  domestic  hot 
water system.
Connect  the  cold  water  supply  to  both  the  storage  bottom 
port  and  the  supply  side  of  the  boiler  (shown  in Applications, 
this  manual).  It  is  important  that  you  install  a  flow  check  on 
the supply line of the boiler BEFORE connecting the feed line 
to the storage tank. This allows the cold feed to flow through 
the storage tank first. It is recommended that you install shut 
off valves on the cold feed line for future ease of service. If there 
is  a  back  flow  preventer  or  any  type  of  no  return  valve  in  the 
system,  then  you  must  install  an  additional  tee  for  a  suitable 
potable  hot  water  expansion  tank.  Connect  the  storage  tank 
return line to the return connection located on the boiler (shown 
in Applications, this manual). Then connect the storage tank hot 
water outlet to the hot water plumbing lines.

C. Backflow Preventer

Use  a  backflow  preventer  specifically  designed  for  boiler 
installations. This valve should be installed on the cold water 
fill supply line per local codes.

D. Potable Expansion Tank

A  potable  hot  water  expansion  tank  is  required  to  offset 
heated water expansion. In most city plumbing systems, the 
water  meter  has  a  no  return  or  back  flow  device  built  into 
the system to prevent back flowing of water into city mains. 
Some local codes require back flow preventers on all incoming 
water supplies. The hot water expansion tank must be listed 

B. Relief Valve

To avoid water damage or scalding due to relief valve operation:

• 

Discharge line must be connected to relief valve outlet 
and  run  to  a  safe  place  of  disposal.  Terminate  the 
discharge line in a manner that will prevent possibility of 
severe burns or property damage should the relief valve 
discharge.

• 

Discharge line must be as short as possible and the same 
size  as  the  valve  discharge  connection  throughout  its 

Plumbing  of  this  product  should  only  be  done  by  a  qualified, 
licensed plumber in accordance with all local plumbing codes. 
The boiler is designed to be connected to a storage tank to supply 
domestic hot water. HTP offers 119 and 175 gallon size storage 
tanks in either stainless steel or glass-lined construction. These 
storage tanks will be directly connected to the boiler supply and 
return connection.

Connect discharge piping to a safe disposal location following 
the guidelines below.

entire length.

• 

Discharge  line  must  pitch  downward  from  the  valve 
and terminate at least 6” above the floor drain, making 
discharge clearly visible.

• 

The discharge line shall terminate plain, not threaded, 
with a material serviceable for temperatures of 375

o

or greater.

• 

Do not pipe discharge to any location where freezing 
could occur.

• 

No valve may be installed between the relief valve and 
boiler or in the discharge line. Do not plug or place any 
obstruction in the discharge line.

• 

Test the operation of the relief valve after filling and 
pressurizing the system by lifting the lever. Make sure 
the valve discharges freely. If the valve fails to operate 
correctly,  immediately  replace  with  a  new  properly 
rated relief valve.

• 

Test T&P  valve  at  least  once  annually  to  ensure  the 
waterway is clear. If valve does not operate, turn the 
boiler “off” and call a plumber immediately.

• 

Take  care  whenever  operating  relief  valve  to  avoid 
scalding injury or property damage.

FAILURE  TO  COMPLY  WITH  THE  ABOVE  GUIDELINES 
COULD RESULT IN FAILURE OF RELIEF VALVE OPERATION, 
RESULTING  IN  POSSIBILITY OF  SUBSTANTIAL  PROPERTY 
DAMAGE, SEVERE PERSONAL INJURY, OR DEATH.

RE-INSPECTION OF T&P RELIEF VALVES: T&P valves 
should be inspected AT LEAST ONCE EVERY THREE 
YEARS, and replaced if necessary,

 by a licensed plumbing 

contractor or qualified service technician to ensure that the 
product has not been affected by corrosive water conditions 
and to ensure that the valve and discharge line have not been 
altered or tampered with illegally. Certain naturally occuring 
conditions  may  corrode  the  valve  and  its  components  over 
time,  rendering  the  valve  inoperative.  Such  conditions  can 
only be detected if the valve and its components are physically 
removed  and  inspected. 

Do not attempt to conduct an 

inspection on your own.

 Contact your plumbing contractor 

for a re-inspection to assure continued safety.

Do  not  thread  a  cap  or  plug  into  the  relief  valve  or  relief 
valve line under any circumstances! Explosion and property 
damage, serious injury, or death may result.

FAILURE TO RE-INSPECT THE T&P VALVE AS DIRECTED 
COULD RESULT IN UNSAFE TEMPERATURE AND/OR 
PRESSURE BUILD-UP WHICH CAN RESULT IN PROPERTY 
DAMAGE, SERIOUS PERSONAL INJURY, OR DEATH.

VWH  units  must  be  connected  to  a  storage  tank.  Failure  to 
connect the VWH boiler to a storage tank of the minimum size 
requirements  (119  gallons  for  a  single  500VWH;  175  gallons 
for a single 700/850VWH) will result in property damage and/
or premature boiler failure. Damages  resulting from incorrect 
installation or from use of products not approved by HTP, Inc. 
ARE NOT covered by warranty.

The control module uses temperature sensors to provide both 
high limit protection and modulating temperature control. The 
control module also provides low water protection by sensing 
the water level in the heat exchanger. Some codes/jurisdictions 
may require additional external controls..

Содержание MODCON500

Страница 1: ...personal injury or death HTPreservestherighttomakeproductchangesorupdateswithoutnoticeandwillnotbeheldliablefortypographical errors in literature NOTETO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTUR...

Страница 2: ...VICINITY OFTHIS OR ANY OTHER APPLIANCE WHATTO DO IFYOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Do not use any phone in your building Immediately call your gas su...

Страница 3: ...dividual such as a fire chief fire marshal chief of a fire prevention bureau labor department or health department building official or electrical inspector or others For the Installer This boiler mus...

Страница 4: ...ating System 5 D BoilerWater 6 E Freeze Protection 6 F High Elevation Installations 6 G WaterTemperature Adjustment 6 Part 2 BeforeYou Start 7 A What s in the Box 8 B How the Boiler Operates 8 C Optio...

Страница 5: ...e boiler warranty and could result in property damage personal injury or death This boiler has been designed to heat potable water ONLY Using this boiler to heat non potable fluid WILL VOID product wa...

Страница 6: ...utes 125oF 1 1 2 to 2 minutes 130oF About 30 seconds 135oF About 10 seconds 140oF Less than 5 seconds 145oF Less than 3 seconds 150oF About 1 1 2 seconds 155oF About 1 second Table 1 ApproximateTime T...

Страница 7: ...StorageTanks Contact HTP for Available StorageTanks 40o 1414 859 883 894 1980 1206 1217 1260 2404 1449 1459 1502 50o 1131 872 902 915 1584 1225 1238 1292 1923 1467 1481 1534 60o 943 884 920 937 1320 1...

Страница 8: ...oilers Each cascaded boiler will have its own pump to provide maximum flow and control heat exchanger flow rate Text Display and Operational LED Light Indicators The display allows the user to change...

Страница 9: ...y damage severe personal injury or death A Locating the Boiler Incorrect ambient conditions can lead to damage to the heating system and put safe operation at risk Ensure that the installation locatio...

Страница 10: ...orrect operating conditions IS NOT covered by product warranty Use extreme care not to drop the boiler or cause bodily injury while lifting the boiler Gas conversion should be performed BEFORE the boi...

Страница 11: ...orted Boiler exhaust and intake connections are not designed to carry heavy weight Vent support brackets must be within 1 of the boiler and the balance at 4 intervals Boiler must be readily accessible...

Страница 12: ...15 cm below the space ceiling the other 6 15cm above the space floor Each opening should have a free area of one square inch per 1 000 BTU hr 22cm2 kW of the total input of all appliances in the space...

Страница 13: ...G of ANSI Z223 1 Figure 4 CO Warning Label I Water Chemistry Requirements Chemicalimbalanceofthewatersupplymayaffectefficiencyand cause severe damage to the boiler and associated equipment HTP recomme...

Страница 14: ...in property damage severe personal injury or death Dielectric unions or galvanized steel fittings must not be used in a system with this boiler Doing soWILLVOID the warranty Useonlycopper brass orsta...

Страница 15: ...al location following the guidelines below entire length Discharge line must pitch downward from the valve and terminate at least 6 above the floor drain making discharge clearly visible The discharge...

Страница 16: ...The boiler circulator location is selected to ensure adequate flow through the boiler Failure to comply with this caution could result in unreliable performance and nuisance shutdowns from insufficie...

Страница 17: ...ve flows and friction loss This is provided to aid in circulator selection SystemTemperature Rise Chart 20 t 25 t 30 t Model Friction Ft Flow Rate GPM Friction Ft Flow Rate GPM Friction Ft Flow Rate G...

Страница 18: ...ion must be replaced The manufacturer of the boiler has no control of water quality especially TDS levels in your system Total dissolved solids in excess of 2 000 ppm will accelerate lime and scale fo...

Страница 19: ...rect tank sensor or system pipe sensor mounted on common return to the boiler 12 Aquastat or system pipe sensor connects to DHW sensor input on boiler 13 The minimum storage tank size for a 500VWH is...

Страница 20: ...oiler Manifold Piping Chart this manual 6 All pumps are shown with isolation flanges or full port ball valves for isolation The alternative is standard flanges with full port ball valves and a separat...

Страница 21: ...for connecting a boiler is 2 When sizing and installing a multiple boiler system see Multiple Boiler Manifold Piping Chart this manual 6 All pumps are shown with isolation flanges or full port ball va...

Страница 22: ...contamination often contained in indoor air it is best to pipe all intake combustion air directly to the outdoors NOTE If exhaust vent pipe system passes through an unheated space such as an alcove or...

Страница 23: ...d vent system must not be interchanged with other vent systems or unlisted pipe fittings Cellular foam core piping may be used on air inlet piping only DO NOT mix components from different venting sys...

Страница 24: ...er to center Minimum distance between exhaust vents and intake pipes on multiple boilers is 10 0 255 m center to center L When adjacent to a public walkway locate exit terminal at least 7 feet above g...

Страница 25: ...am core piping may be used on air inlet piping only 2 Remove all burrs and debris from joints and fittings 3 When using PVC or CPVC pipe all joints must be properly cleaned primed and cemented Use onl...

Страница 26: ...given in theVenting section of this manual When installing a combustion air intake from outdoors care must be taken to utilize uncontaminated combustion air NOTE To prevent combustion air contaminati...

Страница 27: ...4 foot intervals on the vent pipe Venting must be readily accessible for visual inspection from the first three feet from the boiler NOTES A For every 1 of overhang the exhaust vent must be located 1...

Страница 28: ...re meant to demonstrate system venting only The installer is responsible for all equipment and detailing required by local codes Figure 18 UnbalancedVenting Roof Exhaust and Sidewall Intake An unbalan...

Страница 29: ...air is taken from the outdoors using a duct to deliver the air to the mechanical room each of the two openings should be sized based on a minimum free area of one square inch per 2000 BTU hr input See...

Страница 30: ...structions could result in property damage or personal injury Combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the boil...

Страница 31: ...he boiler prior to opening an electrical box within the unit Ensure the power remains off while any wiring connections are being made Failure to follow these instructions could result in component or...

Страница 32: ...the tank then one sensor should be used on the pipe carrying water from the tank s to the boiler To minimize temperature loss in the piping this sensor should be placed as close to the tank s as possi...

Страница 33: ...l ignite As the signal continues to rise towards its maximum of 10 volts the boiler will increase in set point temperature See Part 10 for details on the setting of function 16 2 Connect a building ma...

Страница 34: ...or to the terminals marked SYS SENSOR 4 Do not connect anything to the OUTDOOR SENS or THERMOSTAT terminals 5 If 0 10 volt positive going DC signal input is used connect to marked terminals O Cascade...

Страница 35: ...LP 446 r4 Rev 10 12 16 35 Figure 29 Cascade Master and FollowerWiring...

Страница 36: ...SWITCH FOR VWH APPLICATION OPTIONAL FOR STANDARD BOILER APPLICATION LOW WATER LEVEL APPLICATION FOR STANDARD BOILER ONLY NOT FOR VWH X6 5 FLAME RECTIFICATION PROBE BVPS FUSE THERMAL X5 4 926 CONTROL X...

Страница 37: ...rtant to support gas piping as the unit is not Support gas supply piping with hangers not by the boiler or its accessories The boiler gas valve and blower will not support the weight of the piping Mak...

Страница 38: ...upply at the manual gas valve before disconnecting the hose from the gas monitoring device Tighten screw on the pressure tap and turn gas on Check for leaks with soapy solution Bubbles will appear on...

Страница 39: ...death Strainonthegasvalveandfittingsmayresult in vibration premature component failure and gas leakage and result in fire explosion property damage severe personal injury or death Adjustments to the t...

Страница 40: ...al 1 The boiler is a high efficiency condensing boiler Therefore the unit has a condensate drain Condensate fluid is nothing more than water vapor derived from combustion products similar to that prod...

Страница 41: ...set temperature installer 4 or that boiler is at high firing rate If the command from the master boiler control gets to the high firing rate of the follower boiler but the system sensor is below the r...

Страница 42: ...building Immediately call your gas supplier from a neighbor s phone Follow the gas suppliers instructions If you cannot reach your gas supplier call the fire department Turn off the gas shutoff valve...

Страница 43: ...the user to adjust the ignition differential set point from 1oF to 36oF Factory Default 7oF Degrees below set point must be equal to or below tank differentials TANK SETPOINT 120 oF Adjusts the tank s...

Страница 44: ...set point that the burner will maintain its outlet water temperature while there is a demand for heat Factory Default is 20oF Range 1oF to 45oF Function 6 VWH Post PumpTime VWH POST PUMP TIME 0 MINUTE...

Страница 45: ...a connected and powered Modbus communication adapter p n 7350P 629 will result in improper appliance operation Service calls associated with this ARE NOT covered by warranty Table 19 System Setting Pr...

Страница 46: ...ting press ENTER Press the and v keys to make adjustments Press ENTER when reset is complete Part 10 Start Up Procedures for the Installer A Boiler Control Status Menu The boiler control also has the...

Страница 47: ...ate and time that the fault occurred Press v once FAULT HISTORY 4 08 28 2009 Fr 5 19A This screen displays the fourth oldest boiler control lockout fault The top line will alternate between the words...

Страница 48: ...tom line shows the status of the system pump output contacts Press v once CASCADE PWR 100 PRESENT 01234567 This screen displays overall cascade power output The range of this value is the number of bo...

Страница 49: ...mp to run in an attempt to cool the boiler 2 Note the displayed fault code and refer to Section D for an explanation of the message along with several suggestions for corrective actions 3 Press RESET...

Страница 50: ...n FLU error Faulty switch MUST be replaced Failure to follow this instruction could result in serious personal injury or death 24 VOLT LOW LOU PUMP ON LOU indicates the 24 volt power supply on the con...

Страница 51: ...h the boiler or b poor heat transfer from the water to the load 5 If no switches are tripped push RESET on the boiler If the boiler tries to ignite or ignites and only runs for a short time and the F0...

Страница 52: ...exists The boiler will not restart until a technician determines and repairs the cause of excessive temperature and pushes RESET on the display If the red FAULT light is not illuminated and this messa...

Страница 53: ...he combustion chamber the refractory wall may be damaged and should be replaced 5 Turn the gas on at the service valve after corrective action is taken 6 If the refractory wall falls against the recti...

Страница 54: ...for boiler operation FLUE TEMP HIGH E07 PUMP OFF TIME E07 indicates the flue sensor temperature is excessive and above 210oF When E07 is displayed the boiler will not respond to a demand for heat When...

Страница 55: ...manufacturers and phone numbers are also listed on this website Wear long sleeved loose fitting clothing gloves and eye protection Apply enough water to the combustion chamber lining to prevent dust...

Страница 56: ...ers as shown in the piping diagrams in this manual Slowly open the ball valves and release pressure into a bucket Once pressure is released connect a hose to the water line to flush the boiler Scale r...

Страница 57: ...LP 446 r4 Rev 10 12 16 57 Figure 35 500 Model Combustion System Replacement Parts...

Страница 58: ...LP 446 r4 Rev 10 12 16 58 Figure 36 700 850 Models Combustion System Replacement Parts...

Страница 59: ...250P 152 7250P 152 O RING SILICONE 2 007 BARBED FITTING 22 7350P 605 7350P 605 FLOW SWITCH KIT FOR MOD CON VWH 07 28 16 ITEM MOD CON 500VWH MOD CON 700 VWH MOD CON 850VWH DESCRIPTION 1 7500P 033 7500P...

Страница 60: ...LP 446 r4 Rev 10 12 16 60 Figure 38 Cabinet Replacement Parts All Models...

Страница 61: ...If necessary convert the boiler to the proper fuel type Locate the stickers in the appropriate locations on the boiler Verify combustion settings after gas conversion Carbon Dioxide CO2 High Fire CO2...

Страница 62: ...Ignitor and Flame Probe Check ionization in uA d7 in Status Menu in Start Up Procedures Record high fire and low fire Clean probe with plumbers cloth to remove oxides Condensate 1stYear 2ndYear 3rdYe...

Страница 63: ...ONOXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fueled equipment the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with...

Страница 64: ...ENTING SYSTEM PROVIDED When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment the instru...

Страница 65: ...ating components must be maintained in good operating condition 3 All lines must be checked to confirm that all condensate drains properly from the unit 4 Operate the VWH at pressures not exceeding th...

Страница 66: ...CEPTED IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING WITHOUT LIMITATION THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE AND ANY OBLIGATION LIABILI...

Страница 67: ...LP 446 r4 Rev 10 12 16 67 Maintenance Notes...

Страница 68: ...of Installation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Customer P...

Отзывы: