Mobrey MCU200 Series Скачать руководство пользователя страница 8

Fig. 8

in the normal condition.  The example uses 1 MHz 
sensors and 2 seconds delay before alarm, to prevent 
wave action produced by stirrers triggering the alarm.

Gain adjustment:

(i) With sensor dry, reduce time delays to 2 seconds for
simpler adjustment.  Set gain switch to “LO” and reduce
pot to “MIN”.  Red LED will illuminate - this is the “false
wet”.  Rotate the gain potentiometer clockwise slowly
until the green LED illuminates:  note the setting (X).
(ii) Increase the gain  setting X + 3 if it is necessary
to switch to the “HI” gain range, re-check for a “false
wet” position on the “HI” range, or assume an overlap
between “LO” and “HI” of 2 divisions of gain.
(iii) Check that the sensor when immersed in water
gives an alarm output.  Recheck in the liquid to be
monitored.
(iv) Reset the time delays as needed.

Special site conditions:

In the above application the time delay can be used to 
prevent high level alarms caused by splashing of the 
sensor, by setting the green switch to “Delay to NE”.  
Avoiding severe splashing or condensation effects may 
require a slight increase in the gain setting to X + 4.  To 
detect splashing or for use on light oils the gain can be 
reduced to X + 2.

3.3 Pump control and latching alarms

The output relay of the MCU200 can be latched into 
the de-energised state.  This latch is achieved by short 
circuiting the two terminals of the Auxiliary input, labelled 
as terminals 3 & 4 on the pc board (see figure 5).  The 
relay will remain de-energised while the latching short 

circuit is applied.  Only after this circuit is broken can the 
relay re-energise under the control of the sensor.
A latching alarm can therefore be achieved by 
connecting one pole of the output relay into the auxiliary 
input, through a push to break “reset” button.  NC1 and 
C1 should be used to create this latch, with NC2, C2 and 
NO2 being used for the external alarm circuit.

For a pump control application, switching a pump to 
control a liquid between two sensors in a tank, this 
auxiliary input can be used to monitor the second sensor.  
The control system must be designed as follows:

(i) The pump to be latched “on” must be driven by the
MCU200 output relay.
(ii) The sensor attached directly to the MCU200 must
initiate the pump action to be latched.
(iii) The latched pump action occurs when the MCU200
relay is de-energised.
(iv) The separate sensor must be used to detect the
liquid presence at the switch off point.
(v) The signal from the separate sensor to switch off the
pump must be an open circuit, and is connected to the
auxiliary input in the MCU200.

In this example the number 6 switch (blue) on the 
MCU200 would be set to OSC = E, so that when the 
lower gap sensor sees air it de-energises the relay 
to bring on the pump.  With switch number 4 (yellow) 
set to E = GREEN, the red LED illuminates when the 
pump is running.  With “Delay to NE” set at 2 seconds, 
the sensor will ignore occasional bubbles or surface 
turbulence which could trigger a pump start.

Switch Switchings:

Cable

Checking In

1 MHz

0.5 secs

E = Green

OSC = E

Page 8

Fig. 9

1 MHz

Cable

Checking In

OSC = NE

2 secs

E = Green

Delay to NE

Normal 

Green

Normal 

Green

Alarm

Red

Alarm

Red

Содержание MCU200 Series

Страница 1: ...one direction only 50msecs in other direction Approx LED indicators Red for alarm Green for normal Yellow for cable fault LED state Green Red indication selectable for either sensor state Sensors comp...

Страница 2: ...tud before control or signal leads are connected The ground connections must have a current rating of 25A AC SUPPLY Never operate the equipment from a line voltage or frequency in excess of that speci...

Страница 3: ...iled to perform an intended operation Equipment has been subjected to prolonged storage under unfavourable conditions Equipment has been subjected to severe physical stress If in any doubt as to the s...

Страница 4: ...cal to avoid build up of solids on the sensor faces on either side of the gap In this condition the switching level will be half way up the face if the sensor is mounted from the side of the tank this...

Страница 5: ...inal for neutral and one of the 115V or 230V terminals depending on the voltage supply available BEWARE the terminal not connected externally will be live once the transformer is powered via the other...

Страница 6: ...l cables attached to the sensors normally these are linked at the sensor to the metal body of the fitting or to each other in the case of non metallic sensors If this continuity is broken the FAULT LE...

Страница 7: ...eration of any ultrasonic sensor system This adjusts the gain of the feedback amplifier in the control unit which produces oscillation of the sensor when the coupling between the ultrasonic crystals i...

Страница 8: ...e the latching short circuit is applied Only after this circuit is broken can the relay re energise under the control of the sensor A latching alarm can therefore be achieved by connecting one pole of...

Страница 9: ...uence of operation to 1 MHz see fig 5 if the sensor will operate at this frequency ii With sensor or pipe in relatively clean water supernatant set gain switch to LO and reduce gain pot see fig 5 unti...

Страница 10: ...periodic inspection by a qualified person to ensure that the installation including wiring and equipment housing is safe 5 Spares and fault finding 5 1 The following parts are suitable for replacement...

Страница 11: ...r by reflection method Page 11 iv Check the incorrect operation has not been produced by incorrect setting of the frequency selection switch or an external short circuit on the auxiliary input termina...

Страница 12: ...ited Riverside Business Park Dogflud Way Farnham GU9 7SS UK 44 0 1252 729140 44 0 1252 729168 mobrey delta mobrey com Linkedin com company delta mobrey ltd Twitter com DeltaMobreyUK Facebook com Delta...

Отзывы: