Recommended routine test procedure in accordance with BS5266 
• Daily check – check LED charge indicator is illuminated
• Monthly functional test - simulate a mains supply failure for approx. 30 seconds by operation of key switch 

or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is 
illuminated

• Annual 3-hour duration test - simulate a mains supply failure for 3-hour continuous test by operation of key 

switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator 
is illuminated

• If the luminaire fails any of the above tests, please contact a qualified electrician. See below for test record 

sheet