TESTING FOR EMERGENCY LUMINAIRES

Recommended routine test procedure in accordance with BS5266 
• Daily check – check LED charge indicator is illuminated
• Monthly functional test - simulate a mains supply failure for approx. 30 seconds by 
   operation of key switch or switching off circuit breaker. Ensure normal supply is restored 
   after test and ensure charge indicator is illuminated
• Annual 3-hour duration test - simulate a mains supply failure for 3-hour 
  continuous test by operation of key switch or switching off circuit breaker. Ensure normal 
  supply is restored after test and ensure charge indicator is illuminated
• If the luminaire fails any of the above tests, please contact a qualified electrician. See 
  below/overleaf for test record sheet

Содержание EMPOWER3

Страница 1: ...INSTALLATION MAINTENANCE MANUAL EMPOWER3 ...

Страница 2: ...gulations If in any doubt consult a qualified electrician Please isolate mains prior to installation or maintenance Check the total load on the circuit including when this luminaire is fitted does not exceed the rating of the circuit cable fuse or circuit breaker Please note the IP Ingress Protection rating of this luminaire when deciding the location for installation Allow 50mm above and around t...

Страница 3: ... Ingress Protection rating of this luminaire when deciding the locatio installation Allow 50mm above and around the fitting for air dissipation do not cover the fitting with i This product is Class II double insulated This product is IP20 rated TALLATION Provide power to the required point of installation Cut a suitable hole in the mounting surface as per the cut out details see Fig 1 ensurin infr...

Страница 4: ...ity is observed Connect the downlight to the inverter via the plug and socket provided Change the bezel if required by unscrewing from the downlight and replacing with the required bezel Place the inverter and battery into the ceiling via the cut out Lift both spring clips on the sides of the fitting and push into the ceiling Switch on and check for correct operation ensuring the green indicator L...

Страница 5: ...cessories reserve the right to alter product specification without prior notice The LED lamps fitted in this product are non replaceable The product should be recycled in the correct manner when it reaches the end of its life Check local authorities for where facilities exist The batteries in this luminaire are Lithium Ion and must be disposed of correctly Please contact the local authorities for ...

Страница 6: ... off circuit breaker Ensure normal supply is restored after test and ensure charge indicator is illuminated Annual 3 hour duration test simulate a mains supply failure for 3 hour continuous test by operation of key switch or switching off circuit breaker Ensure normal supply is restored after test and ensure charge indicator is illuminated If the luminaire fails any of the above tests please conta...

Страница 7: ...AR THIRD YEAR FOURTH YEAR FIFTH YEAR SIGNED DATE SIGNED DATE SIGNED DATE SIGNED DATE SIGNED DATE 1 FUNCTIONAL 2 FUNCTIONAL 3 FUNCTIONAL 4 FUNCTIONAL 5 FUNCTIONAL 6 FUNCTIONAL 7 FUNCTIONAL 8 FUNCTIONAL 9 FUNCTIONAL 10 FUNCTIONAL 11 FUNCTIONAL 12 3 HOUR Installed by Installation date Contact number ...

Страница 8: ...AVSEP21_V2 ML Accessories Limited LU5 4LT www mlaccessories co uk 54 INTERNATIONAL CONTACT DETAILS INTERNAT CONTACT D 5 60 C TA ...

Отзывы: