background image

OPERATION

1. Connect the 300 Series Pressure Sensor to the 270 with the appropriate sensor cable. Should there be

any more accessories they are wired in as outlined in Figure A.

2. Plug the power cable from the 270 into a 115 VAC-60Hz power source. For 230-50Hz sources, the power

entry module, Figure C-item D, must be set to the proper voltage.

3. Apply power by turning on the Power switch. (Figure B-item I)

4. Place the Sensor Range switch, Figure B-item J, to the full scale value of the pressure sensor in use.

5. Place the Display Units switch, Figure B-item K, to the mmHg position.

6. Place the Heater switch, Figure B-item G, to the REG position. This applies power to the proportional heater

circuit in the sensor. There will be a small delay between the closing of this switch and the lighting of the

HEATER lamp, Figure B-item F. The lamp should come on brightly, go out and then come on and remain

on at a lower intensity. Should the system contain a 274 multiplex unit, the heater supply is included in that

unit and the REG switch on the 270 must be placed in the OFF position. Allow a minimum of 4 HOURS

to stabilize a "cold" sensor. For sensors that have just been received, it is recommended that they be left
on heat overnight. To achieve the best possible accuracy the heater should always be on.

7. Place the Response switch, Figure B-item H, to the STD position. This provides the best all around response

vs. noise for pressure measurement. When using a series 200 controller, use the FAST position. The SLOW
position is used when low noise on the DC output is more important than fast response.

8. Place the Range SELECT switch, Figure B-item A, to the NULL position. If necessary, adjust the Null Con-

trol, Figure B-item, to produce a zero reading on the Digital Display. (Figure B-item N)

9. Place the Range SELECT to the F.S. position. If necessary, adjust the F.S. control, Figure B-item C, to pro-

duce a full scale reading of +10000* on the panel meter. *(100000 on a 270B-5)

10. Place the Range SELECT to the X0.01 position. Pump the pressure sensor below its resolution (or cross-

port differential units) and check the zero. Correct, if necessary, with the Coarse and Fine zero controls,
Figure B-item D&E. Should these controls lack the range for this adjustment, refer to the Zero and Span
adjustment section in the MKS Instruction Manual for 170 Series Sensors.

NOTE: SHOULD A MULTIPLEX UNIT BE IN USE, THE ABOVE CONTROLS ARE BYPASSED AND

THE ZERO CORRECTION IS DONE AT THE MULTIPLEX UNIT.

11. Place the Range SELECT in the System Check position and compare this reading with the system check

number on the sensor calibration sheet. If the reading is incorrect, refer to the maintenance section.

12. Place the Range SELECT in the X1 position. The system is now ready to display the pressure range of

the sensor. For 1/10 of that range, use the X0.1 position, for 1/100 use the X0.01 position.

Содержание 270C

Страница 1: ...underutilized and idle equipment along with credit for buybacks and trade ins Custom engineering so your equipment works exactly as you specify Critical and expedited services Leasing Rentals Demos I...

Страница 2: ...Instruction Manual I I i I TYPE 270C HIGH ACCURACY SIGNAL CONDITIONER SIX S H AT T U C K R O A D A N D O V E R M A S S A C H U S E T T S 0 1 8 1 0 x 5 0 8 9 7 5 2 3 5 0 T E L E X 9 1 0 2 4 0 9 0 0 5 F...

Страница 3: ...Troubleshooting 5 1 Section P a r t s Lists LIST OF F GORE Fig ire I n t e r c o n n e c t i o n Cables 2 i Fig o n t e I Control 3 3 Fig C R e a r Panel Controls 3 3 Fi i r e D 2 7 0 Block Diagra 4...

Страница 4: ...CCURACY SIGNAL CONDITIONER Section 1 GENERAL DESCRIPTION The 270 is a complete signal conditioner and 41 2 or 51 2 digit display packaged in the standard MKS 1 2 rack mount unit This unit contains the...

Страница 5: ...logic Decimal points channel ID and range ID outputs are buffered TTL levels All outputs can drive 1 TTL load 1 2rack size cabinet 8 lbs Operating Temperature 1 5 to 40 C Operating Voltage Power Consu...

Страница 6: ...ULATION ABOUT THE UNIT The 270 can be mounted in a panel cutout or a 19 rack when supplied with the RM 6 Rack Mount option FIGURE A shows the cables necessary to connect between the 270 and other inst...

Страница 7: ...C 4 100 17 N C 5 10 18 N C 6 1 19 N C 7 N C 20 N C 8 CH 1 ID Input 21 Remote Read 9 CH 2 ID Input 22 Digital Ground 10 CH 3 ID Input 23 Digital Ground 11 Multiplex Select 24 N C 12 N C 25 Chassis Grou...

Страница 8: ...t 2 8 1 9 N C 10 100 11 200 12 40 13 400 14 20 15 1000 16 10 17 Enable Digit 1 Used only by MKS 270 4 BCD OUTPUT CONNECTOR 41 2 DIGIT DPM 18 5 V 025 mA 19 HOLD 20 Good Data 21 Decimal 4P 22 Decimal 3P...

Страница 9: ...d when the DATAREADY line goes high When these lines are left open or connected to 5V then all of the BCD outputs are open This is done when several meters are connected in parallel to a common bus Ea...

Страница 10: ...he Sensor Coarse Zero to provide an approximate zero setting SENSOR ZERO FINE E This control is used in conjunction with the 270 Coarse Zero to provide high resolution in the zero setting HEATER F Thi...

Страница 11: ...in this connector to receive excitation heater power etc POWER ENTRY MODULE D This module contains 1 RFI power line filter 2 IEC power line connector 3 Line voltage selector 4 Power line fuses 2 The f...

Страница 12: ...R 1 S T D SLOW R E S P O N S E O 010 1 x l a T Y P E 2 7 0 sacova CONDITIONER 11 1 0 0 1 OAPS mmHg R o l m P H I 1 A P B a S S E N S O R R A N G E D I S P L A Y U N I T S REW TE X I M O W x l 1 X 01 O...

Страница 13: ...item H to the STD position This provides the best all around response vs noise for pressure measurement When using a series 200 controller use the FAST position The SLOW position is used when low noi...

Страница 14: ...2 4 1 HI HI 0 1 LO HI 0 01 HI LO REMOTE RANGE SELECTION 114 NC I q ray 10 it le The X1 X0 1 X0 01 ranges can be remotely selected by placing the Range Select in the Remote position and applying the p...

Страница 15: ...e oscillator to block quadrature signals The DC amplifier acts as an integrator and filters the input signal to produce a smooth DC output signal This circuit also has a Response Speed Selector switch...

Страница 16: ...p Divider Circuit Heater Controls 13v 13v 1 3 Ana Gnd 13 5v G n d Digital Gnd 40v 40v CAC and Zero XFMR Range Selection Circuit 2nd AC amp Demodu lator 10 KHz Oscil lator Multiplex Connector Digital I...

Страница 17: ...temperature regulated precision reference VR2 This reference voltage is applied to the positive input of the integrating amplifier U14 The negative input of this amplifier is connected to precision h...

Страница 18: ...ranges The command to select the X0 1 or X0 01 range by the range switch is done by applying a ground closure via S1 while the REMOTE position is left in the hi state to LOCKOUT any commands from the...

Страница 19: ...overranged 11V or otherwise suspect make the checks listed below Check to be sure that all vacuum fittings are tight and that the sensor is properly pumped down Low range absolute sensors 100mmHg and...

Страница 20: ...sensor cable 2 Place the RANGE SELECTOR in the system check position 3 Place the REG switch in the OFF position 4 Use the VOM to check the voltages at the sensor end of the cable Reference the VOM to...

Страница 21: ...ecessary to perform the following calibration check 1 Adjust the NULL for a zero setting 2 Place the DIPSLAY UNITS SELECTOR in the mmHg position 3 Switch the RANGE SELECTOR to the F S position and adj...

Страница 22: ...uipment Have surplus equipment taking up shelf space We ll give it a new home Learn more Visit us at artisantg com for more info on price quotes drivers technical specifications manuals and documentat...

Отзывы: