Designation of wires, cutting & stripping the cable

The factory delivered cable has the wires marked with 

the numbers 1 - 2 - 3 as to the table to the right. If the 

cable needs to be cutted and stripped, the shield should 

be connected as the no. 3 wire.
Do NOT connect any of the colored programming wires 

as it may damage the transmitter. The programming 

wires should be cut off in different lengths to prevent 

them from short circuit.

Take care not to block or squeeze the air pressure 

compensation tube

 

Designations:
1:

 Positive (+) wire, red

2:

 Negative (-) wire, brown

3:

 Shield 

(NOT signal ground!)

4:

 Moisture filter for com-

pensation tube

5:

 Air pressure  

compensation tube

6:

 Programming wires

Factory delivery

Cutted and 

stripped

Do not connect a programming unit to the transmitter 
or make any attemt to program the tranmitter while the 
transmitter is located in an explosion hazardous zone!

Electrical mounting

Cable length vs. supply voltage

The cable can be lengthened with any type of cable 

using connection box 202922. Although the measuring 

signal is not sensitive to electrical noise, we recommend 

the use of a screened cable.
Ensure that no moisture can enter the pressure compen-

sation tube inside the cable.
The length of the cable is only limited by the total resist-

ance (A) of the cable cond the input impedance 

of the analog input on the MJK 704, MJK 713, PLC etc. 

(typically 10 to 100 

) and the available supply voltage 

(B) (typically 24 V DC).

Example:

 

The nominal resistance for 1 conductor in a  transmitter 

cable is 0,036 

/m. A standard 12 m cable will therefore 

add 2 x 0,036 x 12 =  0,86 

 to the loop resistance. If the 

analog input has an impedance of 50 

., the total 

resistance will be approx. 51 

(B) 

Supply voltage [V DC]

Necessary supply voltage in relation to the total loop resistance.

(A)

 

Total loop resistance [

]

According to the diagram above, approx. 12 V DC will  

be sufficient.

Содержание 202925

Страница 1: ...l 45 45 56 06 56 Fax 45 45 56 06 46 mjk mjk com www mjk com As our products are continuously improved we reserve the right to make any change in the stated specifications and dimensions without prior...

Страница 2: ...ct complies with the requirements concerning electromagnetic compatibility EMC stipulated in Council directive no 89 336 EEC of 3rd May 1989 altered at directive no 92 31 EEC on the approximation of t...

Страница 3: ...air 4 Mechanical mounting 5 Model 1400 5 Model 3400 5 Model 3400 with thread top 5 Electrical mounting 6 Cable length vs supply voltage 6 Designation of wires cutting stripping the cable 6 Explosion h...

Страница 4: ...s are printed on a label on the transmitter housing For all versions the pressure range is indicated on the label Safety instructions 1 Read this manual carefully 2 Be aware of the environment on the...

Страница 5: ...itting by sliding the two plastic jaws upwards place the cable between the jaws and slide the jaws downwards until the cable locks Secure the cable fitting by pulling the cable downwards 3 Lower the p...

Страница 6: ...transmitter or make any attemt to program the tranmitter while the transmitter is located in an explosion hazardous zone Electrical mounting Cable length vs supply voltage The cable can be lengthened...

Страница 7: ...r The Z788 Zener Barrier MJK part no 202995 has a safety fuse which will blow if the current exceeds the limit The voltage protection in the Zener barrier contains a number of zener diodes which are c...

Страница 8: ...ength Cmax Ci Ccable 129 m Cable length based of the inductance Max cable length Lmax Li Lcable 2862 m In this case the capacitance sets the limit of the cable length to 129 m If another approved isol...

Страница 9: ...ur or mists Equipment category Explosive gas air mixtures G Category 1 Zone 0 1 or 2 Category 2 Zone 1 or 2 Category 3 Zone 2 Designation of explosion protection EEx ia IIC T6 Electrical apparatus wit...

Страница 10: ...02993 the max cable length is 129 m Using The Z788 Zener Barrier MJK Order no 202995 the max cable length is 99 m Alternatively other cable types with equivalent specifica tions may be used If a cable...

Страница 11: ...mechanical parameters 4 Install the device only in media for which the wetted materials have sufficient durability 5 Expert transmitter type 1400 3400 hydrostatics level transmitter may not be used i...

Страница 12: ...tter than 0 2 FS 0 2 FS Measurement accuracy Better than 0 1 FS 10 to 30 C Better than 0 2 FS full temperature range Long time stability Better than 0 1 FS per year Materials Housing stainless steel A...

Страница 13: ...op 203955 Expert 3400 range 0 10 mWG 203963 Expert 3400 range 0 3 m 1 RG top 203956 Expert 3400 range 0 30 mWG 202925 Expert 3400 w special meas range MJK Expert 3400 Hydrostatic Level Transmitter Nom...

Страница 14: ...14 Manual Manual Expert 1400 3400 GB 0704 MJK Automation A S Byageren 7 DK 2850 Naerum Denmark Tel 45 45 56 06 56 Fax 45 45 56 06 46 mjk mjk com www mjk com This page intentionally left blank...

Страница 15: ...15 Manual Manual Expert 1400 3400 GB 0704 MJK Automation A S Byageren 7 DK 2850 Naerum Denmark Tel 45 45 56 06 56 Fax 45 45 56 06 46 mjk mjk com www mjk com This page intentionally left blank...

Страница 16: ...16 Manual Manual Expert 1400 3400 GB 0704 MJK Automation A S Byageren 7 DK 2850 Naerum Denmark Tel 45 45 56 06 56 Fax 45 45 56 06 46 mjk mjk com www mjk com...

Отзывы: