![Mitsubishi SUZ-KA09NA Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/mitsubishi/suz-ka09na/suz-ka09na_service-manual_1808184027.webp)
27
L Check of inverter P.C. board
Check the outdoor fan motor.
(Refer to "10-5. . Check of outdoor fan motor".)
Is the fuse (F901) blown on the inverter
P.C. board?
Check the connection of the connectors
(CN931, CN932) of the outdoor fan motor.
If the connection is poor, make it correct.
Operate the outdoor unit by starting
TEST RUN.
Check the LED indication on the in-
verter P.C. board.
Does the LED flash 10 times?
Replace the inverter P.C. board.
Check the remedy following LED
indication.
(Refer to "10-3. HOW TO PRO-
CEED "SELF-DIAGNOSIS".)
Yes
No
Yes
(10-time flash)
No
OCH467C
Содержание SUZ-KA09NA