71
-
(2)
Flare connecting procedures and precautions
a) Make sure that the flare and union portions do not have any scar or dust, etc.
b) Correctly align the processed flare surface with the union axis.
c) Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is same as that for
conventional R22. Incidentally, when the torque is weak, the gas leakage may occur. When it is strong, the flare nut may crack
and may be made nonremovable. When choosing the tightening torque, comply with values designated by manufacturers.
Table 9 shows reference values.
Note : When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and
cause the compressor to burn out.
7.2.3 Storage of piping materials
(1)
Types and storage of piping materials
Refrigerant piping materials for air conditioners are broadly classified into the following types.
As R410A features pressure about 1.6 times higher than R22, it is necessary to use a copper pipe which has a thickness stated in
Table 3 (see on page 68) and which contains less contaminants. It is necessary to carefully treat/store copper pipes so that they are
not collapsed, deformed or damaged. Due care must also be exercised so that foreign matters such as dust and water do not enter
the pipe interior.
A piping set’s open end is sealed with a cap, etc. When storing it, make sure that it is sealed securely. When storing a cladded
copper pipe or bare copper pipe, securely seal the opening with pinching, taping, etc.
Table 8. Flare and flare nut dimensions for R22
Nominal
Outer diameter
Thickness
Dimension (mm)
Flare nut width
diameter
(mm)
(mm)
A
B
C
D
1/4
6.35
0.8
9.0
9.2
6.5
13
17
3/8
9.52
0.8
13.0
13.5
9.7
20
22
1/2
12.70
0.8
16.2
16.0
12.9
20
24
5/8
15.88
1.0
19.4
19.0
16.0
23
27
[unit: mm]
Table 9. Tightening torque of flare for R410A [Reference values]
Nominal
Outer diameter
Tightening torque
diameter
(mm)
N·m (kgf·cm)
1/4
6.35
14~18 (140~180)
16 (160), 18 (180)
3/8
9.52
33~42 (330~420)
42 (420)
1/2
12.70
50~62 (500~620)
55 (550)
5/8
15.88
63~77 (630~770)
65 (650)
Refrigerant piping
materials
Tightening torque of torque
wrenches available on the
market N·m (kgf·cm)
with heat
insulation
without heat
insulation
(bare copper pipe)
with flare processing
without flare processing
without flare processing
General name
: (a) Piping set
: (b) Copper pipe with insulation
: (c) Bare copper pipe
Содержание SRK63ZEA-S1
Страница 2: ...TECHNICAL MANUAL...
Страница 59: ...57 Service data record form 0 1 2 3 4 5 6 7...
Страница 84: ...PARTS LIST SRK63ZEA S1 SRK71ZEA S1 SRC63ZEA S1 SRC71ZEA S1...
Страница 88: ...MEMO 86...
Страница 89: ...CRAE0168 21 1 9 3 8 7 6 5 4 2 23 11 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 87...
Страница 94: ...MEMO 92...
Страница 95: ...CRAE0168 21 1 9 3 8 7 6 5 4 2 23 11 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 93...
Страница 97: ...05 0 CRBE0207 2 12 6 1 7 14 3 24 16 19 4 9 10 5 11 11 13 15 8 18 17 20 23 21 22 PANEL FAN ASSY 95...
Страница 101: ...05 0 CRBE0207 2 12 6 1 7 14 3 24 16 19 4 9 10 5 11 11 13 15 8 18 17 20 23 21 22 PANEL FAN ASSY 99...
Страница 105: ...MEMO...
Страница 106: ...Manual No 06 SRK T 053 ROOM AIR CONDITIONING TECHNICAL MANUAL PARTS LIST...