DIP Switch

 

On the PCB, there is a 10-position DIP switch for configuration setting. Each position 
has two states: ON or OFF. The DIP switch inputs are identified by their reference 
designator on the PCB followed by their switch position.  

 

3. Set 

appropriate 

dipswitches: 

 
DIPSWITCH BANK 1

 

 

 

 

 

1. 

The device provides two mounting holes to mechanically affix the case to a solid surface. Double-sided tape may be used to affix 
the device. When using tape, ensure that the tape is approved for use within the anticipated operating temperature ranges. 

2. 

Install the transformer as per Canadian Electrical Code, Canadian building code and local codes compliance, and manufacturer’s 
installation instructions. 

3. 

Connect the RMF-CA200-V1 cable to the connector CN105 on the indoor unit control board. 

Device Configuration: 

Heat Pump Mode Connector Pin Layout 

Pin Signal  Description 

1 TC  Common 

(IN) 

Transformer 

Common (Out) To Thermostat 

TR 

24 VAC (IN) Transformer 

24 VAC (OUT) to Thermostat 

Y2 

Heat Pump Stage 2 Heat/Cool 

Y1 

Heat Pump Stage 1 Heat/Cool 

7 AUX1 N/A 

OB 

Heat pump Heat / Cool mode 

AUX2 

Stage 4 Heat 

10 G 

Fan 

11 

Stage 3 Heat (Out) 

12 EO 

Error 

Output 

(Out) 

Input 

Description (Factory Default -

 all switches are placed in the OFF position

1 SW1-1 

If 

ON

 enable single stage heat / cool operation, default 

OFF

 (dual stage 

W1, W2 & Y1, Y2

) operation 

2 SW1-2 

Conventional 

(default 

OFF

) or Heat Pump (

ON

) mode selection 

3 SW1-3 

Defines default fan speed when thermostat G signal is active

 

a) 

LOW:

 

SW1-3 

is 

OFF

SW1-4

 is 

OFF

 (default) 

b) 

MEDIUM:

 

SW1-3

 is 

OFF

SW1-4

 is 

ON

 

c) 

HIGH:

 

SW1-3

 is 

ON

SW1-4

 is 

OFF

 

d) 

QUIET:

 

SW1-3

 is 

ON

SW1-4

 is 

ON

 

 

4 SW1-4 

5 SW1-5 

Simulated 2

nd

 stage heat / cool mode during single stage operation is defined by continuous 

Y1 / W1

 call time: 

and auxiliary heat ouput signal (O)  time delay 

SW1

5

 

SW1

6

 

Simulated

 

Logic

 

Delay

 

O

 

Signal

 

Delay

 

OFF

 

OFF

 

10

 

Minutes

 

(Default)

 

2.5

 

Minutes

 

(Default)

 

OFF

 

ON

 

5

 

Minutes

 

5

 

Minutes

 

ON

 

OFF

 

15

 

Minutes

 

7.5

 

Minutes

 

ON

 

ON

 

20

 

Minutes

 

10

 

Minutes

 

 

6 SW1-6 

SW1-7 
SW1-8 
SW1-9 

Default vane position on power up 

a) Automatic: 

SW1-7 

OFF

, SW1-8 

OFF

, SW1-9 

OFF

 

b) Position 

1: 

SW1-7 

ON

, SW1-8 

OFF

, SW1-9 

OFF

 

c) Position 

2: 

SW1-7 

OFF

, SW1-8 

ON

, SW1-9 

OFF

 

d) Position 

3: 

SW1-7 

ON

, SW1-8 

ON

, SW1-9 

OFF

 

e) Position 

4: 

SW1-7 

OFF

, SW1-8 

OFF

, SW1-9 

ON

 

f) Position 

5: 

SW1-7 

ON

, SW1-8 

OFF

, SW1-9 

ON

 

g)  Swing 1: SW1-7 

OFF

, SW1-8 

ON

, SW1-9 

ON

 

h)  Swing 2: SW1-7 

ON

, SW1-8 

ON

, SW1-9 

ON

 

 

10 SW1-10 

Diagnostic

 

Mode

 

a)

 

Default

 

position

 

(

OFF

)

  

b)

 

Diagnostic

 

Mode

 

Enabled

 

(

ON

)

 